R2868 HAMAMATSU

Document overview

  • PDF pages: 2

Technical content

Page 1

FLAME SENSOR

UV TRON® R2868

Quick Detection of Flame from Distance,

Compact UV Sensor with High Sensitivity and Wide Directivity,

Suitable for Flame Detectors and Fire Alarms.

Hamamatsu R2868 is a UV TRON ultraviolet detector that makes

use of the photoelectric effect of metal and the gas multiplication

effect. It has a narrow spectral sensitivity of 185 to 260 nm, being

completely insensitive to visible light. Unlike semiconductor

detectors, it does not require optical visible-cut filters, thus

making it easy to use.

In spite of its small size, the R2868 has wide angular sensitivity

(directivity) and can reliably and quickly detect weak ultraviolet

radiations emitted from flame due to use of the metal plate

cathode (eg. it can detect the flame of a cigarette lighter at a

distance of more than 5 m.).

The R2868 is well suited for use in flame detectors and fire

alarms, and also in detection of invisible discharge phenomena

such as corona discharge of high-voltage transmission lines.

APPLICATIONS

G Flame detectors for gas/oil lighters and matches G Fire alarms G Combustion monitors for burners G Inspection of ultraviolet leakage G Detection of discharge G Ultraviolet switching

GENERAL

Parameters Rating Units
Spectral Response 185 to 260 nm
Window Material UV glass —
Weight Approx. 1.5 g
Dimensional Outline See Fig. 3 —

MAXIMUM RATINGS

Parameters Rating Units
Supply Voltage 400 Vdc
Peak Current 1) 30 mA
Average Discharge Current 2) 1 mA
Operating Temperature -20 to +60 °C

CHARACTERISTICS (at 25°C)

Parameters Rating Units
Discharge Starting Voltage (with UV radiation) 280 Vdc Max.
Recommended Operating Voltage 325±25 Vdc
Recommended Average Discharge Current 100 µA
Background 3) 10 cpm Max
Sensitivity 4) 5000 cpm Typ.
PDF page 1 diagram

NOTES:

1) This is the maximum momentary current that can be handled if its full width at half maximum is less than 10 µs. 2) If the tube is operated near this or higher, the service life is noticeably reduced. Use the tube within the recommended current values. 3) Measured under room illuminations (approximately 500 lux) and recommended operating conditions. Note that these values may increase if the following environmental factors are present. 1. Mercury lamps, sterilization lamps, or halogen lamps are located nearby. 2. Direct or reflected sunlight is incident on the tube. 3. Electrical sparks such as welding sparks are present. 4. Radiation sources are present.

  1. High electric field (including static field) generates across the tube. 4) These are representative values for a wavelength of 200 nm and a light input of 10 pW/cm2. In actual use, the sensitivity will vary with the wavelength of the ultraviolet radiation and the drive circuitry employed.

Figure 1: UV TRON’s Spectral Response and Various

Light Sources

TPT B0009EA 100 UV TRON s SPECTRAL RESPONSE

SUNLIGHT

50

GAS TUNGSTEN FLAME LIGHT

0

WAVELENGTH (nm) ULTRAVIOLET

VISIBLE

INFRARED

Subject to local technical requirements and regulations, availability of products included in this promotional material may vary. Please consult with our sales office. Information furnished by HAMAMATSU is believed to be reliable. However, no responsibility is assumed for possible inaccuracies or omissions. Specifications are subjected to change without notice. No patent rights are granted to any of the circuits described herein. © 1997 Hamamatsu Photonics K. K.

Page 2

FLAME SENSOR UV TRON® R2868

Figure 2: Angular Sensitivity (Directivity)

PDF page 2 diagram

TPT B0010EA

Figure 4: Recommended Operating Circuit

Figure 3: Dimensional Outline (Unit: mm)

10MΩ

4.7 kΩ\*

PDF page 2 diagram
PDF page 2 diagram

\* Be sure to connect the 4.7 kΩ resistor within 2.5 cm from the anode lead end of UV TRON.

  • UV TRON Driving Circuit C3704 series (Option)
PDF page 2 diagram

Hamamatsu also provide the driving circuit C3704 series for R2868 operation. C3704 series include a high voltage power supply and a signal processing circuit in printed circuit board, which allows to operate R2868 easily as a flame sensor with the low input voltage (DC 6 to 30 V)

For the details, please refer to the datasheet of C3704 series.

TPT A0024EA

PDF page 2 diagram

HAMAMATSU PHOTONICS K.K., Electron Tube Center 314-5, Shimokanzo, Toyooka-village, Iwata-gun, Shizuoka-ken, 438-0193, Japan, Telephone: (81)539/62-5248, Fax: (81)539/62-2205, U.S.A.: Hamamatsu Corporation: 360 Foothill Road, Bridgewater, N.J. 08807-0910, U.S.A., Telephone: (1)908-231-0960, Fax: (1)908-231-1218 Germany: Hamamatsu Photonics Deutschland GmbH: Arzbergerstr. 10, D-82211 Herrsching am Ammersee, Germany, Telephone: (49)8152-375-0, Fax: (49)8152-2658 France: Hamamatsu Photonics France S.A.R.L.: 8, Rue du Saule Trapu, Parc du Moulin de Massy, 91882 Massy Cedex, France, Telephone: (33)1 69 53 71 00, Fax: (33)1 69 53 71 10 United Kingdom: Hamamatsu Photonics UK Limited: Lough Point, 2 Gladbeck Way, Windmill Hill, Enfield, Middlesex EN2 7JA, United Kingdom, Telephone: (44)181-367-3560, Fax: (44)181-367-6384

North Europe: Hamamatsu Photonics Norden AB: Färögatan 7, S-164-40 Kista, Sweden, Telephone: (46)8-703-29-50, Fax: (46)8-750-58-95

TPT 1008E01

Italy: Hamamatsu Photonics Italia S.R.L.: Via Della Moia, 1/E, 20020 Arese, (Milano), Italy, Telephone: (39)2-935 81 733, Fax: (39)2-935 81 741

MAR.1998 CR Created in Japan