PTTA13G13250916201L HUBERSUHNER
Document overview
- PDF pages: 2
Technical content
Page 1
DATA SHEET
1/2
PTTA / HTTA Boxes
PTTA Box for 3 RRH, power distribution with CB and OVP
PTTA-13G-13-25-09-16-201-L


Box Data
| Product family | PTTA |
| Number of remote radio heads (RRH) | 3 pcs |
| Dimensions (LxWxH) | 240mm x 240mm x 132mm |
| Weight | 2.3 kg |
| Housing material | Glass-filled polycarbonate |
| Housing colour | Grey (RAL 7035) |
| Impact resistance | IK07 |
| Operating voltage overall | -48V DC |
| Terminal type | Screwed |
| Max. cross section terminal input | 16 mm² |
| Max. cross section terminal output | 16 mm² |
| Ingress protection (IP Rating) | IP67 |
| UV resistance | Yes |
| Flammability rating | UL 94 V-0 |
| Free of halogene | Yes |
| Installation temperature | -10 °C ... 50°C |
| Operation temperature | -40 °C ... 75°C |
| Power cable capability | Entry: 1x Cable gland M32 Ø 13.0 to 25.0 mm (for 2 or 12-core cable) |
| Exit: 3x Cable gland M25 Ø 9.0 to 16.0 mm (for 2-core jumper) | |
| Grounding: 1x Cable gland M20 Ø 5.0 to 13.0 mm | |
| Fiber optic cable capability | Input: 1x Cable gland M32 for 2- or 12-core cable (Ø 13.0 to 25mm) |
| Output: 1x cable gland M20 for earthing cable (Ø 5 to 13mm) | |
| Output: 3x Cable gland M25 for 2-core jumper (Ø 9.0 to 16mm ) |
Circuit Breaker Data
| Circuit Breaker type | Miniature circuit breaker C 20A, type 5SY4120-7 (Siemens) |
|---|---|
| Amount of circuit breaker | 3 pcs |
| Amount of poles | 1 pcs |
| Operating voltage circuit breaker | 60V DC |
| Rated Current at 30 °C | 20 A |
| Rated Switching Capacity | 10 kA DC (EN 60898) |
| CB cross section max | 25 mm² |
hubersuhner.com
Page 2
DATA SHEET
2/2
PTTA / HTTA Boxes
PTTA Box for 3 RRH, power distribution with CB and OVP
PTTA-13G-13-25-09-16-201-L
Circuit Breaker Data
| Tripping Characteristic | C |
| Operation temperature circuit breaker | -25 °C ... 55°C |
SPD (Surge Protection Device) Data
| Surge Protection Device Type | SPD type 1+2 / class I+II |
|---|---|
| Amount of SPD | 1 pcs |
| SPD Cross section max | 25 mm² |
| Discharge Surge Current Nominal I n | 12.5 kA |
| Discharge Current I 8/20 us max Nominal max | 30 kA |
| Impulse Discharge Current | 12.5 kA |
| Voltage Protection Level Up | ≤ 0.4 kA |
| Operating Voltage SPD | 60 V AC / -48V DC |
| Operation temperature surge protection device | -40 °C ... 80°C |
Circuit drawing

Ordering Information Table
| Item number | Item description |
|---|---|
| 85024807 | PTTA-13G-13-25-09-16-201-L |
HUBER+SUHNER is certified by ISO 9001, ISO 14001, ISO 45001, IATF 16949, AS/ EN 9100 and ISO/TS 22163-IRIS. Waiver: Facts and figures herein are for information only and do not represent any warranty of any kind. DOCUMENT PIM-P16666 / Date of publication: 31.10.2023 / uncontrolled copy