SPLIT CORE CURRENT

TRANSFORMER
P4018

Current transformer for measuring or monitoring current for con-
trol and/or load centers
Split core design allows easy installation mounting without remov-
ing existing cables
High accuracy of 0.5% for precise current measurement
Compact size for easy installation in tight spaces
RoHS Compliant Product
Custom design available
| ELECTRICAL PARAMETERS @25°C | |||
|---|---|---|---|
| Rated Primary Current: | 200A NOM (400A MAX) | Protection Level: | 7.5V peak |
| Turns Ratio: | 1:2000±1%, (K-L):(1-2) | Dielectric Withstanding Voltage: | 4kV, 1mA, 60s |
| Current Ratio: | 200A/100mA | Insulation Resistance: | 500Vdc/100MΩ Min |
| Accuracy @ RL≤10Ω: | 0.5% | Impluse Withstand Voltage: | 5kV Peak |
| Phase error @ rated current range: | ≤1° | Operating Temperature: | -40 to +85°C |
| DC Resistance: | 85Ω Max | Storage Temperature: | -40 to +90°C |

Product performance is limited to specified parameters. Data is subject to change without prior notice.
Tel: 310-325-1043 Fax: 310-325-1044
Dimensions Unless otherwise specified, all tolerances are: inch: .XX : ±0.010 .XXX : ±0.005 mm: X,X : ±0,254 X,XX : ±0,13
www.mpsind.com sales@mpsind.com