04/04/2013 HPL-ED2012 V2.0 EN 1 / 3 AUXILIARYCONTACTSNHI-PKZ2 Partno. NHI11-PKZ2 Articleno. 090677 Deliveryprogramme Product range Accessories: PKZ2 System - PRODUCT DISCONTINUATION IN 2012 Accessories Standard auxiliary contact For motor-protective circuit-breakers, circuit-breakers and (high- capacity) compact starters Contacts N/O = Normally open 1 N/O N/C = Normally closed 1 N/C Contact diagram Contact sequence Notes Can be fitted to circuit-breaker and (high-capacity) compact starter. Can be combined with AGM trip-indicating auxiliary contacts Notes Accessories Page
1 Motor-protective circuit-breaker, circuit-breakers → 021859
7 Remote operators → 063676
additional accessories → 026234 Accessories Page 2 (High-capacity) compact starter → 063472
9 Clip plate → 052710
additional accessories → 026234 Approvals Product Standards UL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE marking UL File No. E29184 UL CCN NKCR CSA File No. 12528 CSA Class No. 3211-05 NA Certification UL listed, CSA certified Specially designed for NA No Auxiliarycontacts Rated impulse withstand voltage Uimp V AC 6000 Overvoltage category/pollution degree III/3
04/04/2013 HPL-ED2012 V2.0 EN 2 / 3 Rated operational voltage Ue V AC 500 Rated operational current Ie A AC-15 230 - 240 V Ie A 6 400 - 415 V Ie A 3 440 V Ie A 1.5 500 V Ie A 1.5 Lifespan, mechanical Operations x 106 0.1 Lifespan, electrical Operations x 106 0.05 Short-circuit rating without welding Fuse A gG/ gL Terminal capacities mm2 Solid or flexible conductor with ferrule mm2 1 x (0.75 - 2.5) 2 x (0.75 - 2.5) Solid or stranded AWG 1 x (22 - 14) 2 x (22 - 14) Safe isolation to VDE 0106 Part 101 and Part 101/A1 Between auxiliary contacts and main contacts V AC 690 TechnicaldataETIM4.0 Suitable for earth leakage circuit breaker No Type of electric connection Screw connection Rated operation current Ie at AC-15, 230 V A 6 Mounting type Side mounting Suitable for pendant switch No Suitable for front element No Suitable for circuit-breakers No Suitable for safety position switches No Suitable for step switches No Suitable for pressure switch/selector switch actuator No Suitable for cam switches No Suitable for motor protective circuit breakers YES Suitable for series-mounting relays No Suitable for solenoid No Suitable for compact switch-disconnector No Suitable for miniature circuit-breakers No Suitable for pulse relay No Suitable for contactor relay relay No Suitable for pendant pushbutton No Suitable for residual current device No Number of contacts as change-over contact 0 Number of contacts as N/O 1 Number of contacts as NC 1 Suitable for impulse relays No Suitable for position switches No Suitable for switch-disconnector/residual current device No Suitable for contactors No Suitable for installation contactor / installation relay No Dimensions
04/04/2013 Eaton Industries GmbH http://www.moeller.net/en © 11/2012 by Eaton Industries GmbH HPL-ED2012 V2.0 EN Additionalproductinformation(links) Motor starters and "Special Purpose Ratings" for the North American market http://www.moeller.net/binary/ver_techpapers/ver953en.pdf Busbar Component Adapters for modern Industrial control panels http://www.moeller.net/binary/ver_techpapers/ver960en.pdf