METSEPM2110 SCHNEIDER
Document overview
- PDF pages: 3
Technical content
Page 1
METSEPM2110
Product data sheet
EasyLogic PM2110, Power & Energy meter, Total
Characteristics
Harmonic, LED, Pulse, class 1

Main
Range
EasyLogic
Product name
EasyLogic PM2100
Device short name
PM2110
Product or component type
Power meter
Complementary
Device application
Power monitoring Sub billing
Power quality analysis
total harmonic distortion Total current harmonic distortion THD (I) per phase
Type of measurement
Total voltage harmonic distortion THD (U) per phase Apparent energy total Active and reactive energy total Apparent power total Active and reactive power total Current average Voltage average Frequency average Power factor average
Metering type
Peak demand power PM, QM, SM Apparent power S, S1, S2, S3 Current I, I1, I2, I3 Reactive power Q, Q1, Q2, Q3 Calculated neutral current Voltage U, U21, U32, U13, V, V1, V2, V3 Peak demand currents Unbalance current Demand power P, Q, S Active power P, P1, P2, P3 Active, reactive, apparent energy (signed, four quadrant) Class 1 active energy conforming to IEC 62053-21
Accuracy class
Class 1 reactive energy conforming to IEC 62053-24
Measurement accuracy
Apparent power +/- 1 % Active energy +/- 1 % Reactive energy +/- 1 % Active power +/- 1 % Voltage +/- 0.5 % Power factor +/- 0.01 Current +/- 0.5 % Frequency +/- 0.05 %
Mar 29, 2020
Page 2
Measurement current
5…6000 mA 35…480 V AC 50/60 Hz between phases
Measurement voltage
20…277 V AC 50/60 Hz between phase and neutral 480…999000 V AC 50/60 Hz with external VT
Frequency measurement range
45…65 Hz
[Us] rated supply voltage
44...277 V AC 45...65 Hz +/- 10 % 44...277 V DC +/- 10 %
Network frequency
60 Hz 50 Hz
Ride-through time
100 ms 120 V AC typical 400 ms 230 V AC typical 50 ms 125 V DC typical
[In] rated current
5 A 1 A
Maximum power consumption in VA
6 VA at 277 V AC
Maximum power consumption in W
3.3 W (power lines (AC)) 2 W at 277 V (power lines (DC))
Input impedance
Current (impedance <= 0.3 mOhm) Voltage (impedance > 5 MOhm)
Tamperproof of settings
Protected by access code
Display type
7 segments LED
Display colour
Red
Messages display capacity
3 fields of 4 characters
Display digits
12 digit(s) - 14.2 mm in height
Demand intervals
Configurable from 1 to 60 min
Information displayed
Demand current (past value) Demand current (present value) Demand power (past value) Demand power (present value) Voltage Current Frequency Energy consumption Harmonic distortion Power factor Active power Apparent power Reactive power Unbalanced in %
Control type
3 x button Red LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh)
Local signalling
Green LED: module operating (RUN)
Number of inputs
0
Number of outputs
1 pulse Pulse: 20 ms (5...40 V DC, 20 mA max)1...9999000 pulse/ k_h (kWh, kVAh, kVARh)
POP parameter Impulse duration
20 ms
Communication port protocol
POP
Sampling rate
64 samples/cycle
Cybersecurity
Enable/disable communication ports
Communication service
Remote monitoring
Product certifications
CE conforming to IEC 61010-1 CULus conforming to UL 61010-1 CULus conforming to CSA C22.2 No 61010-1 RCM EAC C-Tick
Mounting mode
Clip-on
Mounting position
Vertical
Mounting support
Framework
Provided equipment
1 x installation guide
Measurement category
Category III 480 V
Page 3
Category II 480…600 V
Electrical insulation class
Double insulation Class II
Flame retardance
V-0 conforming to UL 94 Current transformer: screw connection (bottom) 6
Connections - terminals
Voltage inputs: screw connection (top) 4
Material
Polycarbonate
Width
96 mm
Depth
76.09 mm total: 61.64 mm embedded:
Height
96 mm
Net weight
300 g
Compatibility code
PM2110
Environment
Service life
7 year(s) IP54 front: conforming to IEC 60529
IP degree of protection
IP30 body: conforming to IEC 60529
Relative humidity
5…95 % at 50 °C
Pollution degree
2
Ambient air temperature for operation
-10…60 °C
Ambient air temperature for storage
-25…70 °C
Operating altitude
<= 2000 m Electrostatic discharge conforming to IEC 61000-4-2
Electromagnetic compatibility
Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 Surge immunity test conforming to IEC 61000-4-5 Conducted RF disturbances conforming to IEC 61000-4-6 Magnetic field at power frequency conforming to IEC 61000-4-8 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 Emission tests conforming to FCC part 15 class A
Overvoltage category
III
Offer Sustainability
REACh free of SVHC
Yes
EU RoHS Directive
Compliant EU RoHS Declaration
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS declaration The product must be disposed on European Union markets following specific waste collection and
WEEE
never end up in rubbish bins