M9U11106 SCHNEIDER

Document overview

  • PDF pages: 3

Technical content

Page 1

M9U11106

Product data sheet

Multi 9 - C60H-DC - MCB - 1P - 6 A - B Curve -

Characteristics

250 V DC - 10 kA

Product availability : Non-Stock - Not normally stocked in distribution facility

Price\*\* : 182.00 USD

PDF page 1 diagram

Main

Range

Multi 9

Product name

Multi 9 C60H-DC

Product or component type

Miniature circuit-breaker

Device short name

C60H-DC

Device application

Distribution

Poles description

1P

Number of protected poles

1

Line Rated Current

6 A 77 °F (25 °C) EN/IEC 60947-2

Network type

DC

Trip unit technology

Thermal-magnetic

Curve code

B 10 kA Icu 220 V DC EN/IEC 60947-2

Breaking capacity

6 kA Icu 250 V DC EN/IEC 60947-2 20 kA Icu 110 V DC EN/IEC 60947-2 5 kA AIR 12...250 V DC UL 1077 10 kA Icu 220 V DC GB 14048.2 6 kA Icu 250 V DC GB 14048.2 20 kA Icu 110 V DC GB 14048.2

Utilisation category

Category A EN/IEC 60947-2

Suitability for isolation

Yes EN/IEC 60947-2

Standards

EN/IEC 60947-2 GB 14048.2 UL 1077

Product certifications

IEC CCC UR

Complementary

[Ue] rated operational voltage

250 V DC 110 V DC 220 V DC

Magnetic tripping limit

3…7 x In DC 7.5 kA 75 % EN/IEC 60947-2 - 220 V DC

[Ics] rated service breaking capacity

4.5 kA 75 % EN/IEC 60947-2 - 250 V DC

Mar 16, 2020

Page 2

15 kA 75 % EN/IEC 60947-2 - 110 V DC 7.5 kA 75 % GB 14048.2 - 220 V DC 4.5 kA 75 % GB 14048.2 - 250 V DC 15 kA 75 % GB 14048.2 - 110 V DC

[Ui] rated insulation voltage

500 V DC EN/IEC 60947-2

[Uimp] rated impulse withstand voltage 6 kVEN/IEC 60947-2 Contact position indicator

Yes

Control type

Toggle

Local signalling

ON/OFF indication

Mounting mode

Clip-on

Mounting support

DIN rail

9 mm pitches

2

Height

3.19 in (81 mm)

Width

0.71 in (18 mm)

Depth

2.87 in (73 mm)

Net weight

0.28 lb(US) (0.128 kg)

Color

Grey

Mechanical durability

20000 cycles

Electrical durability

3000 cycles 250 V DC L/R = 2 ms 6000 cycles 250 V DC

Provision for padlocking

Padlockable Tunnel type terminal top or bottom) 0.00…0.04 in² (1…25 mm²) AWG 18...AWG 4) - rigid stranded

Connections - terminals

Tunnel type terminal top or bottom) 0.00…0.02 in² (1…16 mm²) AWG 18...AWG 6) - flexible Tunnel type terminal top or bottom) 0.00…0.02 in² (1…16 mm²) AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal top or bottom) - 2 0.00…0.02 in² (1…10 mm²) AWG 18...AWG 8) - rigid stranded Tunnel type terminal top or bottom) - 2 0.00…0.02 in² (1…10 mm²) AWG 18...AWG 8) - flexible Tunnel type terminal top or bottom) - 2 0.00…0.02 in² (1…10 mm²) AWG 18...AWG 8) - flexible with ferrule Tunnel type terminal top or bottom) - 3 0.00 in² (1 mm²) AWG 18) - flexible stranded

Wire stripping length

0.55 in (14 mm) top or bottom

Tightening torque

22.13 lbf.in (2.5 N.m) top or bottom

Earth-leakage protection

Without

Environment

Heat dissipation

2.7 W 220 V - 6 A

IP degree of protection

IP20IEC 60529 IP40 modular enclosure)IEC 60529

Pollution degree

3 EN/IEC 60947-2

Tropicalisation

2 IEC 60068-2 2 GB 14048.2

Relative humidity

95 % 131 °F (55 °C)

Ambient air temperature for operation

-13…158 °F (-25…70 °C)

Ambient air temperature for storage

-40…185 °F (-40…85 °C)

Ordering and shipping details

Category

00948 - M9 GEN 2 CB UL1077 / IEC

Discount Schedule

DE2

GTIN

00785901588962

Returnability

No

Country of origin

CN

Offer Sustainability

REACh Regulation

REACh Declaration

REACh free of SVHC

Yes

EU RoHS Directive

Compliant EU RoHS Declaration

Page 3

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

China RoHS declaration Pro-active China RoHS declaration (out of China RoHS legal scope) The product must be disposed on European Union markets following specific waste collection and

WEEE

never end up in rubbish bins.