M9C01101 SCHNEIDER
Document overview
- PDF pages: 2
Technical content
Page 1
M9C01101
Product data sheet
Multi 9 - C60CTRL - MCB - 1P - 1 A - C Curve -
Characteristics
240 V - 100 kA

Main
Range
Multi 9
Product name
Multi 9 C60
Product or component type
Miniature circuit-breaker
Device short name
C60CTRL
Device application
Distribution
Poles description
1P
Number of protected poles
1
Line Rated Current
1 A
Network type
AC DC
Trip unit technology
Thermal-magnetic
Curve code
C 100 kA Icu 240 V AC 50/60 Hz EN/IEC 60947-2
Breaking capacity
25 kA Icu 60 V DC EN/IEC 60947-2
Utilisation category
Category A EN/IEC 60947-2
Suitability for isolation
Yes EN/IEC 60947-2
Standards
EN/IEC 60947-2
Product certifications
CE
Complementary
Network frequency
50/60 Hz 240 V AC 50/60 Hz between phase and neutral
[Ue] rated operational voltage
60 V DC
Magnetic tripping limit
8.5 x In +/- 20 % AC 12 x In +/- 20 % DC 50 kA 50 % EN/IEC 60947-2 - 240 V AC 50/60 Hz
[Ics] rated service breaking capacity
25 kA 100 % EN/IEC 60947-2 - 60 V DC 500 V AC 50/60 Hz EN/IEC 60947-2
[Ui] rated insulation voltage [Uimp] rated impulse withstand voltage 6 kVEN/IEC 60947-2 Contact position indicator
Yes
Control type
Toggle
Local signalling
ON/OFF indication
Mounting mode
Clip-on
Mar 16, 2020
Page 2
Mounting support
DIN rail
9 mm pitches
2
Height
3.19 in (81 mm)
Width
0.71 in (18 mm)
Depth
2.83 in (72 mm)
Net weight
0.26 lb(US) (0.12 kg)
Color
Grey
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Provision for padlocking
Padlockable Tunnel type terminal top or bottom) 0.00…0.04 in² (1…25 mm²) - rigid
Connections - terminals
Tunnel type terminal top or bottom) 0.00…0.04 in² (1…25 mm²) - flexible Tunnel type terminal top or bottom) 0.00…0.04 in² (1…25 mm²) - flexible with ferrule
Wire stripping length
0.55 in (14 mm) top or bottom
Tightening torque
17.70 lbf.in (2 N.m) top or bottom
Earth-leakage protection
Separate block
Environment
IP degree of protection
IP20IEC 60529 IP40 modular enclosure)IEC 60529
Pollution degree
3 EN/IEC 60947-2
Tropicalisation
2 IEC 60068-1
Relative humidity
95 % 131 °F (55 °C)
Ambient air temperature for operation
-22…158 °F (-30…70 °C)
Ambient air temperature for storage
-40…176 °F (-40…80 °C)
Ordering and shipping details
GTIN
03606480631368