M9C01101 SCHNEIDER

Document overview

  • PDF pages: 2

Technical content

Page 1

M9C01101

Product data sheet

Multi 9 - C60CTRL - MCB - 1P - 1 A - C Curve -

Characteristics

240 V - 100 kA

PDF page 1 diagram

Main

Range

Multi 9

Product name

Multi 9 C60

Product or component type

Miniature circuit-breaker

Device short name

C60CTRL

Device application

Distribution

Poles description

1P

Number of protected poles

1

Line Rated Current

1 A

Network type

AC DC

Trip unit technology

Thermal-magnetic

Curve code

C 100 kA Icu 240 V AC 50/60 Hz EN/IEC 60947-2

Breaking capacity

25 kA Icu 60 V DC EN/IEC 60947-2

Utilisation category

Category A EN/IEC 60947-2

Suitability for isolation

Yes EN/IEC 60947-2

Standards

EN/IEC 60947-2

Product certifications

CE

Complementary

Network frequency

50/60 Hz 240 V AC 50/60 Hz between phase and neutral

[Ue] rated operational voltage

60 V DC

Magnetic tripping limit

8.5 x In +/- 20 % AC 12 x In +/- 20 % DC 50 kA 50 % EN/IEC 60947-2 - 240 V AC 50/60 Hz

[Ics] rated service breaking capacity

25 kA 100 % EN/IEC 60947-2 - 60 V DC 500 V AC 50/60 Hz EN/IEC 60947-2

[Ui] rated insulation voltage [Uimp] rated impulse withstand voltage 6 kVEN/IEC 60947-2 Contact position indicator

Yes

Control type

Toggle

Local signalling

ON/OFF indication

Mounting mode

Clip-on

Mar 16, 2020

Page 2

Mounting support

DIN rail

9 mm pitches

2

Height

3.19 in (81 mm)

Width

0.71 in (18 mm)

Depth

2.83 in (72 mm)

Net weight

0.26 lb(US) (0.12 kg)

Color

Grey

Mechanical durability

20000 cycles

Electrical durability

10000 cycles

Provision for padlocking

Padlockable Tunnel type terminal top or bottom) 0.00…0.04 in² (1…25 mm²) - rigid

Connections - terminals

Tunnel type terminal top or bottom) 0.00…0.04 in² (1…25 mm²) - flexible Tunnel type terminal top or bottom) 0.00…0.04 in² (1…25 mm²) - flexible with ferrule

Wire stripping length

0.55 in (14 mm) top or bottom

Tightening torque

17.70 lbf.in (2 N.m) top or bottom

Earth-leakage protection

Separate block

Environment

IP degree of protection

IP20IEC 60529 IP40 modular enclosure)IEC 60529

Pollution degree

3 EN/IEC 60947-2

Tropicalisation

2 IEC 60068-1

Relative humidity

95 % 131 °F (55 °C)

Ambient air temperature for operation

-22…158 °F (-30…70 °C)

Ambient air temperature for storage

-40…176 °F (-40…80 °C)

Ordering and shipping details

GTIN

03606480631368