Page 1

M8650C4C0H5E1A1A

Product data sheet

ION8650 meter 32MB, FT21 panel,

Characteristics

120VAC/160VDC 50Hz, Ethernet No I/O,

password

PDF page 1 diagram

Main

Range

PowerLogic

Device short name

ION8650C

Product or component type

Energy and power quality meter

Complementary

Power quality analysis

up to the 31st harmonic harmonic distortion voltage sag and swell detection programmablity (logic and math functions)

Device application

Co-generation and IPP monitoring Equipment monitoring and control Load curtailment Demand and power factor control Tariff metering Instrument transformer correction Energy pulsing and totalisation

Type of measurement

Current Voltage Frequency Apparent power total Power factor total Apparent power per phase Power factor per phase Active power total Active power per phase Reactive power total Reactive power per phase

Supply voltage

120...277 V AC 47...63 Hz 120...480 V AC 47...63 Hz 65...120 V AC 47...63 Hz 80...160 V DC

Network frequency

50 Hz

Outlet standard

American

May 21, 2020

Page 2

Line Rated Current

2 A 1 A 5 A

Type of network

3P + N 1P + N 3P

Power consumption in VA

24 VA

Maximum power consumption in VA

33 VA

Display type

FSTN transflective LCD

Form designation

36S 2½-element 4 9 3-element 4 35 2-element 3 29 2½-element 4

Sampling rate

1024 samples/cycle

Measurement current

0.001…24 A

Input type

current 0.01...20 A 0.05 Ohm)

Measurement voltage

57…277 V AC phase to neutral 100…480 V AC phase to phase

Number of inputs

0

Measurement accuracy

Current 0.1 % Voltage 0.1 % Power 0.1 % Power factor 0.1 % Frequency 0.001 Hz Energy 0.1 %

Accuracy class

Class 0.2S energy IEC 62053-23 Class 0.2 energy ANSI C12.20 Class 0.2S energy IEC 62053-22

Number of outputs

2 pulse

Communication port protocol

DNP3 300...115200 bauds ION 300...115200 bauds Ansi C12.18 <= 19200 bauds IEC 61850 ed. 2 10/100 Mbit/s TCP/IP 10/100 Mbit/s DLMS 300...115200 bauds Modbus 57600 bauds DNP3 10/100 Mbit/s ION 10/100 Mbit/s Modbus RTU, slave 300...115200 bauds Modbus TCP, slave 10/100 Mbit/s EtherGate

Communication port support

RJ45 Ethernet SUB-D 9 RS485/RS232 Terminal block RS485 infrared

Time synchronisation protocol

IRIG-B GPS: Truetime/Datum

Data recording

GPS synchronisation Data logs Sag and swell logs Revenue logs Event logs Historical logs Alarms Harmonics logs Time stamping

Transmission rate

300...115200 bauds 57600 bauds <= 19200 bauds 10/100 Mbit/s

Memory capacity

32 MB

Web services

Port addressing user designed Alarm notification by e-mail Robust security logs Web server

Ethernet service

Enable/disable serial ports Enable/disable Ethernet protocols

Page 3

SNMP-Traps and SYSLOG

Tamperproof of settings

Protected by access code Hardware lock by jumper

Provided equipment

Break out panel

Compatibility code

ION8650C

Environment

Electrostatic discharge immunity test IEC 61000-4-2

Electromagnetic compatibility

Conducted RF disturbances IEC 61000-4-6 Immunity to impulse waves IEC 61000-4-12 Electrical fast transient/burst immunity test IEC 61000-4-4 Susceptibility to electromagnetic fields IEC 61000-4-3 1.2/50 µs shock waves immunity test IEC 61000-4-5 Conducted and radiated emissionsB CISPR 22

Mounting mode

Flush-mounted

Enclosure type

FT21 switchboard

Type of installation

Indoor installation

Overvoltage category

III

IP degree of protection

Front face IP50 Back IP30

Relative humidity

5…95 %

Pollution degree

2

Ambient air temperature for operation

-40…185 °F (-40…85 °C)

Ambient air temperature for storage

-40…185 °F (-40…85 °C)

Operating altitude

0...9842.52 ft (0...3000 m)

Standards

ANSI C12.1 IEC 62052-11

Width

6.42 in (163 mm)

Depth

8.98 in (228 mm)

Height

11.22 in (285 mm)

Net weight

15.43 lb(US) (7 kg)

Offer Sustainability

Sustainable offer status

Green Premium product WARNING: This product can expose you to chemicals including: Dichloromethane (Methylene

California proposition 65

chloride) and Bisphenol A (BPA) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov

REACh free of SVHC

Yes

EU RoHS Directive

Compliant EU RoHS Declaration

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

China RoHS declaration Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental Disclosure

Product Environmental Profile

Circularity Profile

End of Life Information The product must be disposed on European Union markets following specific waste collection and

WEEE

never end up in rubbish bins.

Contractual warranty

Warranty

18 months