LINEFILTER VICOR

Document overview

  • Manufacturer or author: Provided By www.digicamel.com(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 2

Technical content

Features

 Compatible with VI-HAM-xL and VI-HAM-xM  RoHS compliant Product Highlights The VI-HAM Harmonic Attenuator Module requires an external filter to meet international standards for EMI/RFI emissions, and incorporates transient surge protection, as outlined in the specifications below. 4.6 x 2.4 x 1 in (116,8 x 61,0 x 25,4 mm) Parameter Min Typ Max Unit Notes Operating voltage 85 264 V ac Operating frequency 47 63 Hz Operating current (see Figure 1) 6.3 A Leakage current at 264 Vac, 63 Hz 1.2 mA (Either line to earth) Transient surge 1 kV 1.2/50µs p ulse as per EN61000-4-5 with external MOV P/N 30076 Withstand 2 jo ules 0 to 360° ph ase angle; exceeds IEC 801-5, Level B Dielectric withstand (line – case) 1500 V ac Residual voltage after 1 sec. 34 V Electrical Specifications Parameter Min Typ Max Unit Notes Weight 16 (457) oz (g) Size 2.4 x 4.6 x 1.0 in 6,1 x 11,7 x 2,54 cm Operating temperature (see Figure 1) -20 40 °C Agency approvals UL, CSA, TÜV General Specifications Note: The 30205 line filter is not hermetically sealed and therefore should not be subjected to post solder aqueous rinse. LINE LOAD R Cx LD LC Cy Cy HAM Filter P/N 30205 R = 235 KΩ D1,2 = 1.5KE130CA D3 = 1.5KE150CA MOV* P/N 30076 Cx = 1.5 uF(x2)SH Cy = 0.01 uF, Y2 type LC = 6.9 mH LD = 0.72 mH *MOV required external to filter to meet normal mode transient surge requirements