LDF36400U31X
Product data sheet
Circuit breaker, PowerPact L, Micrologic 3.3,
Characteristics
400A, 3 poles, 600 V, 14 kA, 80% rated,
Price\* : 4,827.00 USD

Main
Range of product
PowerPact L
Product or component type
Circuit breaker Electronic, standard, Micrologic 3.3, LI
Trip Unit Type Interrupt Code
D
Complementary
Line Rated Current
400 A
Number of Poles
3P
Interrupt Rating
25 kA 240 V AC 18 kA 480 V AC 14 kA 600 V AC
Voltage Rating
600 V AC
Continuous current rating
80 %
Protection technology
Current limiter
Mounting mode
Unit mount
Electrical connection
Busbar connection line Busbar connection load AWG 2/0...500 kcmil aluminium/copper)2
Wire Size Terminal Type
AL600LS52K3
I-Line Phase Connection
ABC
Height
11.3 in (287.02 mm)
Maximum Width
5.5 in (139.70 mm)
Maximum Depth
6.61 in (167.89 mm) 442.54 lbf.in (50 N.m) 0.11…0.37 in² (70…240 mm²) AWG 2/0...500 kcmil)
Tightening torque
Environment
Product certifications
CSA 22-2
\* Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price. Sep 25, 2020
Page 2
CCC IEC CE UL 489 NMX NEMA
Ordering and shipping details
01116-L ELEC TRIP UNIT MOUNT BREAKER/SW
Category Discount Schedule
DE2
GTIN
00785901086741
Package weight(Lbs)
15.00 lb(US) (6.804 kg)
Returnability
Yes
Country of origin
US
Offer Sustainability
Sustainable offer status
Green Premium product
EU RoHS Directive
Compliant EU RoHS Declaration
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS declaration Product out of China RoHS scope. Substance declaration for your information.
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End of Life Information
PVC free
Yes
Contractual warranty
Warranty
18 months
LDF36400U31X is replaced by:

Unit Mount LGF36400U31X
Circuit breaker, PowerPact L, Micrologic 3.3, 400A, 3 poles, 600 V, 18 kA, 80% rated
Qty 1
Reason for Substitution: End of life | Substitution date: 03 September 2020 | (Ref #) is replaced by (New Ref #)