HA6025 ETC1
Document overview
- Manufacturer or author: Provided By www.digicamel.com(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 3
Technical content
MODEL NUMBERS AC CONTROL HA6025 HA6050 HA6090 HA60125 DC CONTROL HD6025 HD6050 HD6090 HD60125 OUTPUT SPECIFICATIONS ➀ Nominal Line Voltage (±10%) [Vrms] 600 600 600 600 Operating Voltage Range (47-63 Hz) [Vrms] 48-660 48-660 48-660 48-660 Max. Load Current ➂ [Arms] 25 50 90 125 Min. Load Current, [mArms] 40 40 40 150 Transient Overvoltage [Vpk] 1200 1200 1200 1200 Max. Surge Current, (16.6ms) [Apk] 250 625 1,200 1,750 Thermal Resistance Junction to Case (RθJC) [˚ C/W] 1.02 0.63 0.28 0.22 Maximum I2 t for Fusing, (8.3 msec.) [A2sec] 260 1,620 6,000 12,700 Max. Off-State Leakage Current @ Rated Voltage [mArms] ➆ 5555 Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec]➁ 500 500 500 500 Max. Turn-On Time➄ 1/2 Cycle (DC Input), 10.0 msec (AC Input) Max. Turn-Off Time 1/2 Cycle (DC Input), 40.0 msec (AC Input) INPUT SPECIFICATIONS ➀ DC CONTROL AC CONTROL AC CONTROL (D PREFIX) (A PREFIX) ➃ (E SUFFIX) Control Voltage Range 3-32 Vdc 90-280 Vrms (60Hz) 18-36 Vrms Max. Reverse Voltage -32 Vdc --- --- Max. Turn-On Voltage 3.0 Vdc 90 Vrms 18 Vrms Min. Turn-Off Voltage 1.0 Vdc 10 Vrms 4.0 Vrms Nominal Input Impedance See Note ➅ 60K Ohms 9.0K Ohms Typical Input Current 2.0 mA➅ 2mA @ 120 Vrms, 4mA @ 240 Vrms 3mA @ 24 Vrms GENERAL NOTES ➀ All parameters at 25˚C unless otherwise specified. ➁ Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1 ➂ Heat sinking required, for derating curves see page 2. ➃ 24 Vac Input option, E suffix. ➄ Turn-on time for random turn-on versions is 0.02 msec (DC Control Models). ➅ Input circuitry incorporates active current limiter. ➆ No internal snubber.
- Zero Voltage and Random Turn-On Switching
- Panel Mount
- 1200V Blocking Capability
- 600Vac - the preferred choice in Canada FastFax Document No.159 SERIES HA/HD60. Rev. 031802 PAGE 1 OF 3 Featuring state-of-the-art Surface Mount Technology, these SPST-NO relays deliver proven reliability in the most demanding applications. Output consists of an SCR AC switch and is available in zero-cross, random turn-on (phase controllable) and ver- sions with either AC or DC input (coil) control. Manufactured in Crydom’s ISO 9001 Certified facility for optimum product performance and reliability. Series HA60/HD60 25-125Amp • 600 Vac • AC Output © 2002 CRYDOM CORP, Specifications subject to change without notice. Integrated Overvoltage Protection by Automatic Self Turn-On (Suffix P) For recommended applications and more information contact: USA : Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540 Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154 Email: sales@crydom.com WEB SITE: http://www.crydom.com UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com. GERMANY: +49 (0)180 3000 506
Dielectric Strength 50/60Hz Input/Output/Base 4000 Vrms Insulation Resistance (Min.) @ 500 Vdc 10 9 Ohm Max. Capacitance Input/Output 8 pF Ambient Operating Temperature Range -40 to 80˚C Ambient Storage Temperature Range -40 to 1 25˚C MECHANICAL SPECIFICATIONS Weight: (typical) 3.0 oz. (86.5g) Encapsulation: Thermally Conductive Epoxy Terminals: Screws and Saddle Clamps Furnished, Unmounted APPROVALS UL E116950 CSA LR81689 VDE 10143 UG Crydom Heat Sinks offer excellent thermal management and are per- fectly matched to the load current ratings of Crydom panel mount relays. Request Crydom’s Heat Sink specification sheet for all the details. FastFax Document No.159 SERIES HA/HD60. Rev. 031802 PAGE 2 OF 3 Series HA60/HD60 25-125Amp • 600 Vac • AC Output © 2002 CRYDOM CORP, Specifications subject to change without notice. Screw Torque Requirements: 6-32 Screws - 10 in./lbs., 8-32 and 10-32 Screws - 20in./lbs. (Screws dry without grease.) Fastons: Single pair (up to 25A) Double pair* (up to 50A). *Caution: User must connect to both pairs .90 (22.9) FASTON TERMINAL .187 X .032 (2 PLCS.) BASE PLATE .125 (3.2) FASTON TERMINAL .250 X .032 (2 PLCS.) 1.87 (47.5) .78 (19.8) 2.30 (58.4) 1.70 (43.2) .87 REF. (22.2)
12 OUTPUT
43 INPUT
1.00 (25.4) 1.80 (45.7) .45 (11.4) 1.10 (27.9)MOUNTING HOLE/SLOT 0.17 (4.3) DIA. .90 (22.9) FASTON TERMINAL .187 X .032 (2 PLCS.) BASE PLATE .125 (3.2) FASTON TERMINAL .250 X .032 (2 PLCS.) 1.87 (47.5) .78 (19.8) 2.30 (58.4) 1.70 (43.2) .87 REF. (22.2) 1.00 (25.4) 1.80 (45.7) .45 (11.4) 1.10 (27.9)MOUNTING HOLE/SLOT 0.17 (4.3) DIA. All dimensions are in inches (millimeters) AVAILABLE OPTIONS E 24 VAC Input (18-36 Vac) Example: HA6025E -10 Random Turn-On (AC & DC Control) Phase Controllable (DC Control) Example: HD6090-10 F Faston Terminals (Up to 50 Amp Models) Example: HD6050F P Internal Overvoltage Protection. Relay Will Self Trigger Between 900-1200 Vpk. Not Suitable For Capacitive Loads. Agencies Approval Pending. Example: HD6025P G Input Status LED. Agencies Approval Pending Example: HD6050G Note: Control Voltage Range 4.5-32Vdc for DC Control Models. 1.87 (47.5) .78 (19.8) 2.30 (58.4) 1.70 (43.2) .90 (22.9) .45 (11.4) 1.10 (27.9) 8-32 TERMINAL (2 PLACES ) 1.00 (25.4) 6-32 TERMINAL (2 PLACES)1.80 (45.7) SOLID-STATE RELAY +-- INPUT MOUNTING HOLE/SLOT 0.17 (4.3) DIA. BASE PLATE .125 (3.2) Ordering System: Combination of the suffixes should be made in the following order: EFPG-10 . Example: HA6050EFPG-10 For recommended applications and more information contact: USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540 Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154 Email: sales@crydom.com WEB SITE: http://www.crydom.com UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com. GERMANY: +49 (0)180 3000 506
FastFax Document No.159 SERIES HA/HD60. Rev. 031802 PAGE 3 OF 3 Series HA60/HD60 25-125Amp 600 Vac AC Output Base Plate Temp [˚C] 10 20 40 5030 20 40 60 80 Load Current [Arms] Max Ambient Temp. [˚C] Power Dissipation 50A 2˚C/W .5˚C/W 100 110 120 1.5˚C/W NO HEATSINK 120 20 40 80 060 20 40 60 80 Load Current [Arms] Max Ambient Temp. [˚C] Power Dissipation 100 110 120 Base Plate Temp [˚C] 90A 1˚C/W .4˚C/W .5˚C/W 51 0 2 0 2 515 20 40 60 80 Load Current [Arms] Max Ambient Temp. [˚C] Power Dissipation 120 Base Plate Temp [˚C] 25A 1˚C/W 100 110 3˚C/W NO HEATSINK 2˚C/W 160 120 30 60 120 090 20 40 60 80 Load Current [Arms] Max Ambient Temp. [˚C] Power Dissipation 100 110 120 Base Plate Temp [˚C] 125A .5˚C/W .4˚C/W 1˚C/W .2˚C/W 1˚C/W .2˚C/W CURRENT DERATING CURVES © 2002 CRYDOM CORP, Specifications subject to change without notice. For recommended applications and more information contact: USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540 Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154 Email: sales@crydom.com WEB SITE: http://www.crydom.com UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com. GERMANY: +49 (0)180 3000 506