TeSys GV3L magnetic motor circuit breaker 73A EverLink Main Range TeSys Product name TeSys GV3 Device short name GV3L Device application Motor Poles description 3P Network type AC Utilisation category Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 Network frequency 50/60 Hz Breaking capacity 50 kA Icu at 440 V AC 50/60 Hz 12 kA Icu at 500 V AC 50/60 Hz 6 kA Icu at 690 V AC 50/60 Hz 50 kA Icu at 400/415 V AC 50/60 Hz 65 kA Icu at 230/240 V AC 50/60 Hz [Ics] rated service short-circuit breaking capacity 100 % at 230/240 V AC 50/60 Hz 50 % at 500 V AC 50/60 Hz 50 % at 690 V AC 50/60 Hz 60 % at 400/415 V AC 50/60 Hz 60 % at 440 V AC 50/60 Hz Trip unit technology Magnetic Magnetic tripping current 1120 A Complementary Fixing mode 35 mm symmetrical DIN rail: clipped Panel: screwed (with 3 x M4 screws) Operating position Any position Motor power kW 37 kW at 400/415 V AC 50/60 Hz 55 kW at 690 V AC 50/60 Hz 45 kW at 500 V AC 50/60 Hz Control type Rotary knob [Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications Apr 13, 2020
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 6 kV IEC 60947-2 Power dissipation per pole 8 W Mechanical durability 50000 cycles Electrical durability 20000 cycles for AC-3 at 415 V In Maximum operating rate 25 cyc/h Connections - terminals EverLink BTR screw connectors 1 cable(s) 1…35 mm² solid EverLink BTR screw connectors 2 cable(s) 1…25 mm² solid EverLink BTR screw connectors 1 cable(s) 1…35 mm² flexible with cable end EverLink BTR screw connectors 2 cable(s) 1…25 mm² flexible with cable end EverLink BTR screw connectors 1 cable(s) 1…35 mm² flexible EverLink BTR screw connectors 2 cable(s) 1…25 mm² flexible Tightening torque 5 N.m on EverLink BTR screw connectors for cable 25 mm² 8 N.m on EverLink BTR screw connectors for cable 35 mm² Mechanical robustness Shocks: 30 Gn for 11 ms opened conforming to IEC 60068-2-27 Vibrations: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks: 5 Gn for 11 ms closed conforming to IEC 60068-2-27 Suitability for isolation Yes conforming to IEC 60947-1 Height 132 mm Width 55 mm Depth 136 mm Net weight 0.96 kg Colour Grey (SE GREY 6) Green (SE GREEN 2) Environment Standards EN/IEC 60947-2 EN/IEC 60947-4-1 CSA C22.2 No 60947-4-1 UL 60947-4-1 Product certifications IECEE CB Scheme UL CSA CCC EAC ABS LROS (Lloyds register of shipping) DNV-GL BV Protective treatment TH IP degree of protection IP20 conforming to IEC 60529 IK degree of protection IK09 Ambient air temperature for operation -20…60 °C Ambient air temperature for storage -40…80 °C Fire resistance 960 °C conforming to IEC 60695-2-1 Operating altitude 0...3000 m Offer Sustainability Sustainable offer status Green Premium product REACh Regulation REACh Declaration EU RoHS Directive Compliant EU RoHS Declaration Mercury free Yes RoHS exemption information Yes China RoHS Regulation China RoHS declaration Product out of China RoHS scope. Substance declaration for your information Environmental Disclosure Product Environmental Profile WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Tripping Curves for GV3L Combined with Thermal Overload Relay LRD33 Average Operating time at 20 °C without Prior Current Flow 1 3 poles from cold state 2 2 poles from cold state 3 3 poles from hot state A Thermal overload relay protection zone B GV3L protection zone Current Limitation on Short-Circuit for GV3L (3-Phase 400/415 V) Dynamic Stress I peak = f (prospective Isc) at 1.05 Ue = 435 V
1 Maximum peak current
2 GV3L80 - GV3L73 - GV3L65
3 GV3L50
4 GV3L40
5 GV3L32
6 GV3L25
Thermal Limit on Short-Circuit for GV3L Thermal Limit in A2s Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
1 GV3L73 - GV3L80
2 GV3L65
GV3L, GV3P Dimensions (1) Blocks GVAN●●, GVAD●● and GVAM11. (2) Blocks GV3AU●● and GV3AS●●. X1 = Electrical clearance (ISC max) 40 mm for Ue ≤ 500 V, 50 mm for Ue ≤ 690 V NOTE: Leave a space of 9 mm between 2 circuit breakers: either an empty space or side-mounting add-on contact blocks. Side by side mounting is possible up to 40 °C. Mounting with Tesys contactor LC1D40A…D80A and relay LR3D313…380 (1) (2) (3) (1) Mountings with c.b. up to GV3L73, GV3P73. (2) For GV3L80, GV3P80 use cable between components for dissipating heat. Consult online datasheets for values. (3) S-shape busbar system suitable up to 73 A. Side by side mounting with Tesys contactor LC1D40A…D73A (S-shape busbar system GV3S(1)) (1) Mountings with c.b. up to GV3L73, GV3P73. Mounting on Rail AM1 DE200 or AM1 ED201 Panel Mounting, using M4 Screws
Mounting on Pre-Slotted Plate AM1 PA Mounting of External Operator GV3APN01, GV3APN02 or GV3APN04 for Motor Circuit Breakers GV3L Door cut-out (1) For IP65 only. Mounting of External Operator GVAPH03 for Motor Circuit Breakers GV3L b Minimum Maximum GV3APN●● + GVAPH03 200 300 GV3APN●● + GVAPH03 + GVAPK12 300 492
(1) For IP65 only.
GV3L••