G3PA ETC

Document overview

  • Manufacturer or author: Provided By www.digicamel.com(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 16

Technical content

Power Solid-state Relay G3PA-(VD) J-21 SSR Power Solid-state Relay G3PA-(VD) Extremely Thin Relays Integrated with Heat Sink  Downsizing achieved through optimum design of heat sink.  Mounting possible via screws or via DIN track.  Close mounting possible for linking terminals. (Except for G3P A-260B-VD, G3P A-450B-VD-2.)  Applicable with 3-phase loads.  Replaceable power element cartridges.  Conforms to VDE 0160 (finger protection), with a dielectric strength of 4,000 V between input and load.  Conforms to VDE 0805, IEC 950.  Approved by UL, CSA, and VDE (reinforced insulation).

Ordering Information

Model Isolation Zero cross function Indicator Applicable output load Rated input voltage G3P A-210B-VD Phototriac coupler Y es Y es 10 A at 24 to 240 VAC 5 to 24 VDC G3P A-220B-VD 20 A at 24 to 240 VAC G3P A-240B-VD 40 A at 24 to 240 VAC G3P A-260B-VD 60 A at 24 to 240 VAC G3P A-210BL-VD No 10 A at 24 to 240 VAC G3P A-220BL-VD 20 A at 24 to 240 VAC G3P A-240BL-VD 40 A at 24 to 240 VAC G3P A-260BL-VD 60 A at 24 to 240 VAC G3P A-210B-VD Y es 10 A at 24 to 240 VAC 24 VAC G3P A-220B-VD 20 A at 24 to 240 VAC G3P A-240B-VD 40 A at 24 to 240 VAC G3P A-260B-VD 60 A at 24 to 240 VAC G3P A-420B-VD 20 A at 180 to 400 VAC 12 to 24 VDC G3P A-430B-VD 30 A at 180 to 400 VAC G3P A-420B-VD-2 20 A at 200 to 480 VAC G3P A-430B-VD-2 30 A at 200 to 480 VAC G3P A-450B-VD-2 50 A at 200 to 480 VAC

J-22 Power Solid-state Relay G3PA-(VD) Replacement Parts IOther Units (Order Separately) Units that Enable 2-line Switching of 3-phase Power Name Carry current Load voltage Model Applicable SSR Conforms to VDE Power Device Cartridge

10 A 19 to 264 VAC G32A-A10-VD DC5-24 G3P A-210B-VD DC5-24 Y es

G32A-A10L-VD DC5-24 G3P A-210BL-VD DC5-24 G32A-A10-VD AC24 G3P A-210B-VD AC24

20 A G32A-A20-VD DC5-24 G3P A-220B-VD DC5-24

G32A-A20L-VD DC5-24 G3P A-220BL-VD DC5-24 G32A-A20-VD AC24 G3P A-220B-VD AC24

40 A G32A-A40-VD DC5-24 G3P A-240B-VD DC5-24

G32A-A40L-VD DC5-24 G3P A-240BL-VD DC5-24 G32A-A40-VD AC24 G3P A-240B-VD AC24

60 A G32A-A60-VD DC5-24 G3P A-260B-VD DC5-24

G32A-A60L-VD DC5-24 G3P A-260BL-VD DC5-24 G32A-A60-VD AC24 G3P A-260B-VD AC24

20 A 150 to 440 VAC G32A-A420-VD DC12-24 G3P A-420B-VD DC12-24

30 A G32A-A430-VD DC12-24 G3P A-430B-VD DC12-24

20 A 180 to 528 VAC G32A-A420-VD-2 DC12-24 G3P A-420B-VD-2 DC12-24

30 A G32A-A430-VD-2 DC12-24 G3P A-430B-VD-2 DC12-24

50 A G32A-A450-VD-2 DC12-24 G3P A-450B-VD-2 DC12-24

10 A 75 to 264 VAC G32A-A10 G3P A-210B DC5-24 No

20 A G32A-A20 G3P A-220B DC5-24

40 A G32A-A40 G3P A-240B DC5-24

20 A 180 to 528 VAC G32A-A420 G3P A-420B DC5-24

30 A G32A-A430 G3P A-430B DC5-24

Name Current flow Model Applicable SSR Short-circuit Unit 10 A G32A-D20 G3P A-210B-VD, G3P A-210BL-VD

20 A G3P A-220B-VD, G3P A-220BL-VD

G3P A-420B-VD, G3P A-420B-VD-2

30 A G32A-D40 G3P A-430B-VD, G3P A-430B-VD-2

40 A G3P A-240B-VD, G3P A-240BL-VD

Power Solid-state Relay G3PA-(VD) J-23 SSR Specifications IRatings (at 25°C) Input Output Refer to Engineering Data for further details. Model Rated voltage Voltage range Input current impedance Voltage level Must operate voltage Must release voltage G3PA-210B-VD 5 to 24 VDC 4 to 30 VDC 7 mA max. 4 VDC max. 1 VDC min. G3PA-220B-VD G3PA-240B-VD G3PA-260B-VD G3PA-210BL-VD 5 to 24 VDC 4 to 30 VDC 20 mA max. 4 VDC max. 1 VDC min. G3PA-220BL-VD G3PA-240BL-VD G3PA-260BL-VD G3PA-220B-VD G3PA-240B-VD G3PA-260B-VD G3PA-430B-VD G3PA-420B-VD-2 G3PA-430B-VD-2 G3PA-450B-VD-2 Model Applicable load Rated load voltage Load voltage range Load current Inrush current G3PA-210B(L)-VD 24 to 240 VAC (50/60 Hz) 19 to 264 VAC (50/60 Hz) 0.1 to 10 A 150 A (60 Hz, 1 cycle) G3PA-220B(L)-VD 0.1 to 20 A 220 A (60 Hz, 1 cycle) G3PA-240B(L)-VD 0.5 to 40 A 440 A (60 Hz, 1 cycle) G3PA-260B(L)-VD 0.5 to 60 A 440 A (60 Hz, 1 cycle) G3PA-420B-VD 180 to 400 VAC (50/60 Hz) 150 to 440 VAC (50/60 Hz) 0.5 to 20 A 220 A (60 Hz, 1 cycle) G3PA-430B-VD 0.5 to 30 A 440 A (60 Hz, 1 cycle) G3PA-420B-VD-2 200 to 480 VAC (50/60 Hz) 180 to 528 VAC (50/60 Hz) 0.5 to 20 A 220 A (60 Hz, 1 cycle) G3PA-430B-VD-2 0.5 to 30 A 440 A (60 Hz, 1 cycle) G3PA-450B-VD-2 0.5 to 50 A 440 A (60 Hz, 1 cycle)

J-24 Power Solid-state Relay G3PA-(VD) ICharacteristics Item G3PA- 210B(L)-VD G3PA- 220B(L)-VD G3PA- 240B(L)-VD G3PA- 260B(L)-VD G3PA- 420B-VD G3PA- 420B-VD-2 G3PA- 430B-VD G3PA- 430B-VD-2 G3PA- 450B-VD-2 Operate time 1/2 of load power source cycle + 1 ms max. (DC Input, -B models) 1 1/2 of load power source cycle + 1 ms max. (AC Input) 1 ms max. (-BL models) Release time 1/2 of load power source cycle + 1 ms max. (DC Input) 1 1/2 of load power source cycle + 1 ms max. (AC Input) Output ON voltage drop 1.6 V (RMS) max. 1.8 V (RMS) max. Leakage current 5 mA max. (at 120 VAC) 10 mA max. (at 230 VAC) 10 mA max. (at 120 VAC) 20 mA max. (at 230 VAC) 20 mA max. (at

400 VAC)

20 mA max. (at

480 VAC)

max. (at 20 mA max. (at 480 VAC) I 2t 260 A 2S 810 A 2S 260 A 2S 810 A 2S 810 A 2S Insulation resistance 100 MΩ min. (at 500 VDC) Dielectric strength 4,000 VAC, 50/60 Hz for 1 min Vibration resistance Destruction: 10 to 55 to 10 Hz, 0.375–mm single amplitude (0.75-mm double amplitude) (Mounted to DIN track) Shock resistance Destruction: 300 m/s2 (mounted to DIN track) Ambient temperature Operating: –30°C to 80°C (with no icing or condensation) Storage: –30°C to 100°C (with no icing or condensation) Approved standards UL508, CSA C22.2 (No.14, No.950), EN60950 File No. 5915ÜG UL508, CSA C22.2 (No.14), EN60947- 4-3 File No. 6642ÜG UL508, CSA C22.2 (No.14), EN60947-4-3 File No. 133127ÜG UL508, CSA C22.2 (No.14), EN60947- 4-3 File No. 6642ÜG UL508, CSA C22.2 (No.14), EN60947-4-3 File No. 133127ÜG Ambient humidity Operating: 45% to 85% Weight Approx. 260 g Approx. 340 g Approx. 460 g Approx. 900 g Approx. 290 g Approx. 290 g Approx. 410 g Approx. 410 g Approx. 900 g

Power Solid-state Relay G3PA-(VD) J-25 SSR Operation IReplacement Parts G32A-A Power Device Cartridge The G32A-A Power Device Cartridge (a T riac Unit) can be replaced with a new one. When the temperature indicator has changed from pink to red, the triac circuitry may have malfunctioned possibly by an excessive flow of current, in which case, dismount the damaged cartridge for replacement. The damaged cartridge can be replaced with a new one without disconnecting the wires from the G3P A. Improve the heat radiation efficiency of the G3P A before replacing the cartridge. The G32A-A Power Device Cartridge can withstand an excessive current for a short period of time, such as may be caused accident ally by the short circuitry of the load, in which case the temperature indicator will not turn red. Appearance Replacing Power Device Cartridges When replacing Power Device Cartridges, use the specified model. Using a Power Device Cartridge other than the specified one will result in faulty operation and destruction of the elements. Noise Terminal Voltage according to EN55011 Conformance to EN55011 is possible if a capacitor is connected to the load power supply as shown in the diagram below. (G3P A-VD) Recommended capacitor: NISSEI ELECTRIC Co., LTD, TYPE R40 (MKT Series), 1 µF (Japan only). Loss Time The loss time increases for low voltages and currents. Ensure that the loss time does not increase to an inappropriate level. Caution Be sure to turn OFF the power supply when replacing the Cartridge. Supplying power with the Cartridge removed may result in malfunction. G32A-A10(L)-VD G32A-A20(L)-VD G32A-A40(L)-VD G32A-A60(L)-VD G32A-A420-VD(-2) G32A-A430-VD(-2) G32A-A10 G32A-A20 G32A-A40 G32A-A450-VD-2

240 VAC

24 VDC Input G3PA-VD

J-26 Power Solid-state Relay G3PA-(VD) IReplacement Procedure G32A-A10(L)-VD/G32A-A20(L)-VD/G32-A420-VD(-2) Use the special tool (provided) to extract the cartridge for replacement with a new one. Extraction Follow the procedures below to dismount the Power Device Car- tridge from the G3P A. 1. Switch off the power. 2. Remove the terminal cover. 3. Hook the indented part of the cartridge with the tool and pull up on the cartridge to remove it. Mounting Follow the procedures below to mount the Power Device Cartridge on the G3P A. 1. Apply silicone grease (provided with the G32A-A) to the entire surface of the heat radiator. 2. Make sure that there is no dust or pieces of wire on the heat radi- ator of the G32A-A or the G3P A. 3. Insert the cartridge into the opening of the G3P A so that the let- ters on the cartridge and those on the G3P A are in the same direction and side A and side B are even. 4. Attach the terminal cover. 5. Switch on the power and check the G3P A to be sure it works properly. G32A-A40(L)-VD/G32A-A60(L)-VD/G32A-A430-VD(-2)/G32A-A450-VD-2 The G32A Power Device Cartridge is mounted and secured with screws to the G3P A Unit. Extraction Follow the procedures below to dismount the G32A-A Power Device Cartridge from the G3P A. Switch off the power. 2. Remove the terminal cover. 3. Loosen the two centered screws on the sides to dismount the car- tridge. The screws are connected to terminals 1 and 2. 4. Loosen the screws on both the corners. 5. Hold the indented part of both the corners to dismount the car- tridge. Mounting 1. Apply silicone grease to the entire surface of the heat radiator. 2. Make sure that there is no dust or pieces of wire on the radiator of the G32A-A or the G3P A. Remover Hook here with Remover. Apply silicone grease here. Side A Side B Loosen Loosen Loosen Loosen Apply silicone grease here.

Power Solid-state Relay G3PA-(VD) J-27 SSR 3. Insert the cartridge into the opening of the G3P A so that side A and side B are even. 4. Tighten the screws on both the corners with a tightening torque of 0.59 to 0.78 N·m. 5. Tighten the screws on both the sides with a tightening torque of 0.59 to 0.78 N·m. 6. Attach the terminal cover. 7. Switch on the power and check the G3P A to be sure it works properly. ILinking Terminal Connection  Connecting with linking terminal for G3P A-210B(L)-VD, -220B(L)- VD, -240B(L)-VD and G3P A-420B-VD(-2), G3P A-430B-VD(-2).  Connecting with linking terminal for G32A. Side B Side A SSR1 SSR2 SSR1 SSR2 1. When SSRs are close mounted, loosen the M3.5 Sems screw and flip the linking terminal down. 2. Insert the linking terminal securely into the center of the screw and tighten the screw. SSR G32A Unit SSR G32A Unit * The cover will not fit if the terminal protrudes. 1. When SSR are close mounted, loosen the M3.5 Sems screw on the G32A and flip the linking terminal down. 2. Insert the linking termi- nal securely into the center of the screw and tighten the screw. En- sure that the linking ter- minal does not pro- trude. Linking terminal Linking terminal Connect the terminal with power off. G3PA-420B-VD Refer to the instruction manual for the G32A-A Power Device Cartridge to replace the G3PA's triac part. When the temperature indicator has turned from pink to red, the G32-A-A Power Device Car- tridge may have malfunctioned, in which case the cartridge must be replaced with a new one. Use the terminal cover to prevent accidents due to electric shock. Linking terminal Linking terminal

J-28 Power Solid-state Relay G3PA-(VD) Mounting DIN track G3PA G3PA Panel DIN track Panel The rated ambient temperature is 40°C. (30°C for 400 V.) Vertical mounting Close mounting Horizontal mounting

  • Screw or DIN track mounting is possible.
  • Vertical mounting should usually be used.
  • Close mounting is also possible.
  • Close mounting is possible for up to 3 G3PA SSRs. (If there are 4 or more SSRs, mount at intervals of 10 mm min.) Reduce the load current by 10% for G3PA-210B-VD, -220B-VD, -240B-VD and by 20% for G3PA-260B-VD, - -450B-VD-2.
  • Leave a distance of 80 mm
  • With vertical mounting, reduce the load current by 30%. (Refer to the Load Current vs. Ambient Temperature graph.) 80 mm Note: Leave a distance of 60 mm min. between SSRs and ducts (especially above the SSR). ↔↔ Vertical VerticalVertical

Power Solid-state Relay G3PA-(VD) J-29 SSR Engineering Data Load Current vs. Ambient Temperature Note: Close mounting is possible for a maximum of three Units by reducing the load current by 20%. (A minimum clearance of 10 mm must be provided when mounting four or more Units.) 40 60 80 100200-20-30 Panel Ground Ambient temperature (°C) Ambient temperature ( °C) Ambient temperature ( °C) Load current (A) Load current (A) Load current (A) Horizontal Mounting to Ground G3PA-240B(L)-VD G3PA-260B(L)-VD G3PA-220B(L)-VD G3PA-210B(L)-VD G3PA-210B(L)-VD, G3PA-220B(L)-VD Ambient temperature (°C) Ambient temperature ( °C) Load current (A) Load current (A) G3PA-430B-VD, G3PA-430B-VD-2G3PA-420B-VD, G3PA-420B-VD-2 G3PA-450B-VD-2 Ambient temperature (°C) Load current (A)

J-30 Power Solid-state Relay G3PA-(VD) Input Voltage vs. Input Current G3PA-2@0B-VD Input current (mA) Input voltage (V) Input current (mA) Input voltage (V) G3PA-4@0-VD, G3PA-4@-VD-2 40201086421 0.1 0.2 0.4 0.6 0.8 Input impedance Input current Ta = 25°C 40201086421 0.1 0.2 0.4 0.6 0.8 Input impedance Input current T = 25°C Input impedance (kΩ) Input impedance (kΩ) 40 60 80 100200−20−30 4042 3.5 5.5 10 Panel Ground Vertical Mounting to Ground Ambient temperature (°C) Ambient temperature ( °C) Ambient temperature ( °C) Load current (A) Load current (A) Load current (A) G3PA-240B(L)-VD G3PA-260B(L)-VD G3PA-220B(L)-VD G3PA-210B(L)-VD, G3PA-220B(L)-VD G3PA-210B(L)-VD Ambient temperature (°C) Load current (A) G3PA-430B-VD G3PA-420B-VD G3PA-450B-VD-2 Ambient temperature (°C) Load current (A) G3PA-420B-VD, G3PA-430B-VD G3PA-420B -VD-2, G3PA-430B-VD-2

Power Solid-state Relay G3PA-(VD) J-31 SSR −30 10 30 80 −30 10 30 80 100 40 60 80 100200-20-30 4.5 149 Ambient temperature (°C) G3PA-430B-VD, G3PA-430B-VD-2 Load current (A) Ambient temperature (°C) Load current (A) G3PA-420B-VD, G3PA-420B-VD-2 DIN track Panel Ground Close Mounting (Up to Three) Ambient temperature (°C) Ambient temperature ( °C) Ambient temperature ( °C) Load current (A) Load current (A) Load current (A) G3PA-240B(L)-VD G3PA-260B(L)-VD G3PA-220B-VD G3PA-210B-VD G3PA-210B(L)-VD, G3PA-220B(L)-VD G3PA-450B-VD-2 Ambient temperature (°C) Load current (A)

J-32 Power Solid-state Relay G3PA-(VD) Inrush Current Resistivity: Non-repetitive Note: Keep the inrush current to half the rated value if it occurs repetitively. G3PA-210B(L)-VD G3PA-220B(L)-VD, G3PA-420B-VD, G3PA-420B-VD-2 G3PA-240B(L)-VD/260B(L)-VD, G3PA-430B-VD, G3PA-430B-VD-2, G3PA-450B-VD-2 Inrush current (A. Peak) Energizing time (ms) Inrush current (A. Peak) Energizing time (ms) Inrush current (A. Peak) Energizing time (ms)

Power Solid-state Relay G3PA-(VD) J-33 SSR Dimensions Note: All units are in millimeters unless otherwise indicated. Two, 4.5 dia. or M4 holes 4.6 dia. Two, M4 100 max. G3PA-210B(L)-VD Mounting Holes Without Terminal Cover With Terminal Cover Linking terminal B1 Linking terminal B2 Two, M3.5 4.6 x 5.6 elliptical hole Terminal Arrangement/ Internal Connections Trigger circuit Input circuit Two, 4.5 dia. or M4 holes 4.6 dia. Two, M4 100 max. G3PA-220B(L)-VD Mounting Holes Without Terminal Cover With Terminal Cover Linking terminal B1 Two, M3.5 Linking terminal B2 4.6 x 5.6 elliptical hole Terminal Arrangement/ Internal Connections Trigger circuit Input circuit 4.6 dia. Two, M5 100 max. Two, 4.5 dia. or M4 holes G3PA-240B(L)-VD Mounting Holes Without Terminal Cover With Terminal Cover Linking terminal B1 Two, M3.5 Linking terminal B2 4.6 x 5.6 elliptical hole Terminal Arrangement/ Internal Connections Trigger circuit Input circuit

J-34 Power Solid-state Relay G3PA-(VD) Two, 4.5 dia. or M4 holes 4.6 dia. Two, M5 100 max. Two, M3.5 110 max. Mounting Holes With Terminal Cover Without Terminal Cover G3PA-260B(L)-VD G3PA-450B-VD-2 4.6 x 5.6 elliptical hole Terminal Arrangement/ Internal Connections Trigger circuit Input circuit 4.5 7.6 2.2 8.8 13.2 8.6 90±0.2 25±0.2 90±0.3 90 91 67 38 80 Two, M4 Two, M3.5 4.6 dia. 37 max.4.5 x 5.6 elliptic hole 100 max. G3PA-420B-VD, G3PA-420B-VD-2 Mounting Holes Terminal Arrangement/ Internal Connections Trigger circuit Input circuit 100 max.Linking terminal −B2 Linking terminal +B1 Two, 4.5 dia. or M4 Without Terminal Cover With Terminal Cover 89 91 4.5 7.6 35±0.2 35±0.3 90±0.367 38 8090±0.2 4.6 dia. 100 max.47 max. 4.6 x 5.6 elliptic hole G3PA-430B-VD, G3PA-430B-VD-2 Mounting Holes Two, 4.5 dia. or M4 Two, M5 Terminal Arrangement/ Internal Connections Trigger circuit Input circuit Linking terminal +B1 Linking terminal −B2 100 max. Without Terminal Cover With Terminal Cover

Power Solid-state Relay G3PA-(VD) J-35 SSR Precautions Refer to the T echnical Information for SSRs (Cat. No. J137) for gen- eral precautions. ICorrect Use Load Connection For an AC load, use a power supply rated at 50 or 60 Hz. The maximum operating frequency is 10 Hz. The G3P A-(VD) has a built-in varistor for overvoltage protection. At a low applied voltage, such as 24 VAC, the load current is not fully supplied. When the Unit is switched ON, the voltage required to power the Unit deprives the output signal of the necessary voltage level and thus creates loss time. The lower the load voltage is, the greater the loss time is. This condition, however, will not create any serious problems. For a DC or L load, a diode should be connected in parallel the load to absorb the counter electromotive force of the load. When attaching a heat sink to the G3P A-(VD), in order to facilitate heat dissipation, apply Silicone Grease or equivalent heat conductive grease on the heat sink. (T oshiba Silicon, Shinetsu Silicon, etc.) Tighten the mounting screws of the heat sink with a torque of 0.78 to 0.98 N·m. Noise Terminal Voltage according to EN55011 The G3P A-(VD) conforms to EN55011 standards when a capacitor is connected to the load power supply as shown in the following circuit diagram. Recommended Capacitor: NISSEI ELECTRIC Co., LTD, TYPE R40 (MKT Series), 1 µF Loss time SSRInput Load Load power supply G3PA-(VD) Output Load Input

J-36 Power Solid-state Relay G3PA-(VD) In the interest of product improvement, specifications are subject to change without notice. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. T o convert millimeters into inches, multiply by 0.03937. T o convert grams into ounces, multiply by 0.03527. Cat. No. K094-E1-04