TI01266F EH
Document overview
- Manufacturer or author: Provided By www.digicamel.com(free datasheet download site)
- PDF pages: 44
Technical content
Level measurement for liquids Application
- Ingress protection: IP66/68 / NEMA 4X/6P
- Measuring range: up to 12 m (39.37 ft)
- Process temperature: –40 to 60 °C (–40 to 140 °F)
- Process pressure: –1 to 3 bar (–14 to 43 psi)
- Accuracy: up to ± 5 mm (0.2 in) Your benefits
- Level measurement for liquids in storage tanks, open basins, pump shafts and canal systems
- Radar measuring device with Bluetooth® wireless technology
- Simple, safe and secure wireless remote access – ideal for installation in places difficult to reach
- Commissioning, operation and maintenance via free iOS / Android app SmartBlue – saves time and reduces costs
- Full PVDF body - for a long sensor lifetime
- Hermetically sealed wiring and fully potted electronics – eliminates water ingress and allows operation under harsh environmental conditions
- Most compact radar due to unique radar chip design – fits in limited space installations
- Best price-performance-ratio radar Products Solutions Services Technical Information Micropilot FMR10 Free space radar TI01266F/00/EN/08.20 71492915 2020-08-17
2 Endress+Hauser
Pressure equipment with allowable pressure Japanese Radio Law and Japanese Telecommunications
Important document information Symbols used Symbols for certain types of information and graphics Permitted Procedures, processes or actions that are permitted Forbidden Procedures, processes or actions that are forbidden Tip Indicates additional information Reference to documentation Reference to graphic Notice or individual step to be observed 1 . 2 . , 3 . Series of steps Result of a step 1, 2, 3, ... Item numbers A, B, C, ... Views
4 Endress+Hauser
Document type "Operating Instructions" KA Document type "Brief Operating Instructions" TI Document type "Technical Information" XA Document type "Safety Instructions" PN Nominal pressure MWP MWP (Maximum working pressure/max. process pressure) The MWP can also be found on the nameplate. ToF Time of Flight εr (Dk value) Relative dielectric constant Operating tool The term "operating tool" is used in place of the following operating software: SmartBlue (app), for operation using an Android or iOS smartphone or tablet BD Blocking Distance; no signals are analyzed within the BD. PLC Programmable logic controller (PLC)
Engineering • Proven radar measuring technology
- Flooding detection
- 2D/3D drawings
- Spec Sheet Producer
- Applicator Selection tool for selecting the perfect measurement solution Device not compatible with transmitters and sensors that use ultrasonic measurement technology (e.g. Prosonic FMU9x, FDU9x) Procurement • Best price-performance-ratio radar
- Easy to order through the global e-direct portal - delivery within 48 hours
- Global availability Installation Rear and front thread for flexible installation Commissioning • Quick and easy setup with the SmartBlue app
- No additional tools or adapters required
- Local languages (up to 15) Operation • Continuous self-monitoring
- Diagnostics information according to NAMUR NE107 with remedial measures in the form of plain text messages
- Signal curve via SmartBlue (app)
- Encrypted single point-to-point data transmission (tested by Fraunhofer Institute) and password- protected communication via Bluetooth® wireless technology Maintenance • No maintenance required
- Technical experts on-call around the world Retirement • Environmentally responsible recycling concepts
- RoHS compliance (restriction of certain hazardous substances), lead-free soldering of electronic components
6 Endress+Hauser
The Micropilot is a "downward-looking" measuring system, which functions according to the time-of- flight (ToF) method. It measures the distance from the reference point R to the product surface. Radar pulses are emitted by an antenna, reflected off the product surface and received again by the radar system. D Q R 100% D L FE A0028409 1 Level / flow calibration parameter E Empty calibration (= zero) F Full calibration (= span) D Measured distance L Level (L = E - D) Q Flow rate at measuring weirs or channels (calculated from the level using linearization) R Reference point Input The reflected radar pulses are received by the antenna and transmitted to the electronics. A microprocessor evaluates the signals and identifies the level echo caused by the reflection of the radar pulses at the product surface. This clear signal detection system benefits from over 30 years' experience with time-of-flight procedures. The distance D to the product surface is proportional to the time of flight t of the pulse: D = c · t/2, where c is the speed of light. Based on the known empty distance E, the level L is calculated: L = E – D Output The Micropilot is calibrated by entering the empty distance E (= zero point) and the full distance F (= span).
- Current output: 4 to 20 mA
- Digital output (SmartBlue): 0 to 8 m (0 to 26.25 ft) 1) or 0 to 12 m (0 to 39.37 ft) 2) installed in combination with "flooding protection tube" accessory. 1) order code 010 (approval) "GR": 0 to 5 m (0 to 16.4 ft) 2) order code 010 (approval) "GR": 0 to 8 m (0 to 26.2 ft)
Measured variable The measured variable is the distance between the reference point and the product surface. The level is calculated based on E, the empty distance entered. Measuring range Maximum measuring range
- Device with 40 mm (1.5 in) antenna: 8 m (26.25 ft) 3)
- Device installed with 40 mm (1.5 in) antenna and "flooding protection tube" accessory: 12 m (39.37 ft) 4) Installation requirements
- recommended tank height > 1.5 m (5 ft)
- Open channel minimum width 0.5 m (1.6 ft)
- Calm surfaces
- No agitators
- No buildup
- Relative dielectric constant εr > 4 Contact Endress+Hauser for lower εr values Usable measuring range The usable measuring range depends on the antenna size, the medium's reflective properties, the installation position and any possible interference reflections. Media groups
- εr = 4 to 10 e.g. concentrated acid, organic solvents, ester, aniline, alcohol, acetone.
- εr > 10 e.g. conductive liquids, aqueous solutions, diluted acids and bases Reduction of the maximum possible measuring range by:
- Media with bad reflective properties (= low εr value)
- Formation of buildup, particularly of moist products
- Strong condensation
- Foam generation
- Freezing of sensor Operating frequency K-band (~ 26 GHz) Transmission power Mean power density in the direction of the beam
- At a distance of 1 m (3.3 ft): < 12 nW/cm2
- At a distance of 5 m (16 ft): < 0.4 nW/cm2 Output Output signal 4 to 20 mA An 4 to 20 mA interface is used for measured value output and to power to the device. Digital output Bluetooth® wireless technology The device has a Bluetooth® wireless technology interface and can be operated and configured via this interface using the SmartBlue app.
- The range under reference conditions is 25 m (82 ft)
- Incorrect operation by unauthorized persons is prevented by means of encrypted communication and password encryption
- The Bluetooth® wireless technology interface can be deactivated 3) order code 010 (approval) "GR": 5 m (16.4 ft) 4) order code 010 (approval) "GR": 8 m (26.2 ft)
8 Endress+Hauser
Signal on alarm Depending on the interface, failure information is displayed as follows:
- Current output Alarm current: 22.5 mA (in accordance with NAMUR recommendation NE 43)
- SmartBlue (app)
- Status signal (as per NAMUR Recommendation NE 107)
- Plain text display with remedial action Linearization The linearization function of the device allows the conversion of the measured value into any unit of length, weight, flow or volume. When operating via SmartBlue (app), up to 32 value pairs can be entered manually into the linearization table.
-+1 2 A0028954 2 Cable assignment
1 Plus, brown wire
2 Minus, blue wire
Supply voltage 10.5 to 30 VDC An external power supply is necessary. R [ ]/c87 U0 [V]10 10.5 21.75 20 30 500 A0029226 3 Maximum load R, depending on supply voltage U 0 of power supply unit Battery operation The sensor's Bluetooth® wireless technology communication can be disabled to increase the operating life of the battery. Potential equalization No special measures for potential equalization are required. Various power supply units can be ordered as an accessory from Endress+Hauser. Power consumption Maximum input power: 675 mW Current consumption • Maximum input current: <25 mA
- Maximum start-up current: 3.6 mA Starting time First stable measured value after 20 s (with supply voltage = 24 VDC)
10 Endress+Hauser
Power supply failure The configuration remains stored in the sensor. Connecting the device Y + + - -I mA A0028907 4 FMR10 block diagram
1 Micropilot FMR10, 4 to 20 mA
2 Power supply
Cable specification Unshielded cable, wire cross-section 0.75 mm2
- Resistant to UV and weather conditions as per ISO 4892-2
- Flame resistance according to IEC 60332-1-2 As per IEC/EN 60079-11 section 10.9, the cable is designed for a tensile strength of 30 N (6.74 lbf) (over a period of 1 h). The device is supplied with 10 m (33 ft) cable length as standard. Overvoltage protection The device is equipped with integrated overvoltage protection. Performance characteristics Reference operating conditions
- Temperature = +24 °C (+75 °F) ±5 °C (±9 °F)
- Pressure = 960 mbar abs. (14 psia) ±100 mbar (±1.45 psi)
- Humidity = 60 % ±15 %
- Reflector: metal plate with diameter ≥ 1 m (40 in)
- No major interference reflections inside the signal beam Maximum measured error Typical data under reference operating conditions: DIN EN 61298-2, percentage values in relation to the span. Output, digital (HART, SmartBlue (app))
- Sum of non-linearity, non-repeatability and hysteresis: ±5 mm (±0.2 in)
- Offset/zero point: ±4 mm (±0.16 in) Output, analog Only relevant for 4-20mA current output; add error of the analog value to the digital value
- Sum of non-linearity, non-repeatability and hysteresis: ±0.02 %
- Offset/zero point: ±0.03 %
Differing values in near-range applications [mm (in)] 5 (0.2) 10 (0.39) -20 (-0.79) 20 (0.79) -5 (-0.2) -10 (-0.39) R 0.1 (0.33)R A0033273 5 Maximum measured error in near-range applications ∆ Maximum measured error R Reference point of the distance measurement D Distance from reference point of antenna Measured value resolution Dead band as per EN61298-2:
- Digital: 1 mm (0.04 in)
- Analog: 4 µA Response time The response time can be configured. The following step response times apply (in accordance with DIN EN 61298-2) when damping is switched off: Tank height <5 m (16 ft) Sampling rate 1 s-1 Response time <3 s In accordance with DIN EN 61298-2, the step response time is the time following an abrupt change in the input signal up until the changed output signal has adopted 90% of the steady- state value for the first time. Influence of ambient temperature The measurements are carried out in accordance with EN 61298-3.
- Digital (Bluetooth® wireless technology): Standard version: average TC = ±3 mm (±0.12 in)/10 K
- Analog (current output):
- Zero point (4 mA): average TK = 0.02 %/10 K
- Span (20 mA): average TK = 0.05 %/10 K
12 Endress+Hauser
Installation conditions Installation types B CA E F D A0028892 6 Wall, ceiling or nozzle installation A Wall or ceiling mount, adjustable B Mounted at front thread C Mounted at rear thread D Ceiling installation with counter nut (included in delivery) E Horizontal installation in cramped spaces (wastewater shaft), 40 mm (1.5 in) antenna with flooding protection tube (accessory) recommended F Shaft wall mounting Caution!
- The sensor cables are not designed as supporting cables. Do not use them for suspension purposes.
- Always operate the device in a vertical position in free-space applications. Nozzle mounting The antenna should project out of the nozzle for optimum measurement. The interior of the nozzle must be smooth and may not contain any edges or welded joints. The edge of the nozzle should be rounded if possible. L D L D A0028843 7 Nozzle mounting L Nozzle length D Nozzle diameter The maximum length of the nozzle L depends on the nozzle diameter D. Please note the limits for the diameter and length of the nozzle.
Mounting outside the nozzle
- D: min. 40 mm (1.5 in)
- L: max. D × 1.5 Mounting inside the nozzle
- D: min. 80 mm (3 in)
- L: max. 140 mm (5.5 in) + D × 1.5 Position for installation on a vessel A BD D A0028410 8 Installation position on a vessel
- If possible install the sensor so that its lower edge projects into the vessel.
- Recommended distance A wall - nozzle outer edge: ~ ¹⁄₆ of the vessel diameter D. Under no circumstances should the device be mounted closer than 15 cm (5.91 in) to the vessel wall.
- Do not install the sensor in the middle of the vessel.
- Avoid measurements through the filling curtain.
- Avoid equipment such as limit switches, temperature sensors, baffles, heating coils etc.
- No signals are evaluated within the Blocking distance (BD). It can therefore be used to suppress interference signals (e.g. the effects of condensate) in the vicinity of the antenna. An automatic Blocking distance of at least 0.1 m (0.33 ft) is configured as standard. However, this can be overwritten manually (0 m (0 ft) is also permitted). Automatic calculation: Blocking distance = Empty calibration - Full calibration - 0.2 m (0.656 ft). Each time a new entry is made in the Empty calibration parameter or Full calibration parameter, the Blocking distance parameter is recalculated automatically using this formula. If the result of the calculation is a value < 0.1 m (0.33 ft), the Blocking distance of 0.1 m (0.33 ft) will continue to be used. Device alignment for installation on a vessel
- Align the antenna vertically to the product surface.
- Align the eyelet with lug towards the vessel wall as well as possible.
14 Endress+Hauser
90° 90° 90° 90° 90° A0028927 9 Device alignment for installation on a vessel Beam angle αW = 2 × D × tan α D W A0033201 10 Relationship between beam angle α, distance D and beamwidth diameter W The beam angle is defined as the angle α at which the power density of the radar waves reaches half the value of the maximum power density (3 dB width). Microwaves are also emitted outside the signal beam and can be reflected off interfering installations. Beam diameter W as a function of beam angle α and distance D. 40 mm (1.5 in) antenna, α 30 ° W = D × 0.54 40 mm (1.5 in) antenna with flooding protection tube, α 12 ° W = D × 0.21
Measurement in plastic vessels A0029540 11 Measurement in a plastic vessel with a metallic, interfering installation outside of the vessel
1 Pipe, tubing
2 Ladder
3 Grate, railing
If the outer wall of the vessel is made of a non-conductive material (e.g. GFR), microwaves can also be reflected by interfering installations outside of the vessel. Please ensure there are no interfering installations made of a conductive material in the signal beam (see the beam angle section for information on calculating the beamwidth diameter). Please contact the manufacturer for further information. Weather protection cover For outdoor use, a weather protection cover is recommended. The weather protection cover is available as an accessory. A0031277 12 Weather protection cover with 40 mm (1.5 in) antenna The sensor is not completely covered by the protection cover.
16 Endress+Hauser
Use of flooding protection tube The flooding protection tube ensures the sensor measures the maximum level even if it is completely flooded. In free-field installations and/or in applications where there is a risk of flooding, the flooding protection tube must be used. The flooding protection tube can be ordered as an accessory or together with the device via the product structure "Accessory enclosed". A0030394 13 Function of flooding protection tube
1 Air pocket
2 O-ring (EPDM) seal
3 Blocking distance
4 Max. level The tube is screwed directly onto the sensor and seals off the system by means of an O-ring making it air-tight. In the event of flooding, the air pocket that forms in the tube ensures the measurement of the maximum level at the end of the tube. Due to the fact that the Blocking distance is inside the tube, multiple echoes are not analyzed. Installation with mounting bracket, adjustable The mounting bracket is available as an accessory. A0040057 14 Installation with mounting bracket, adjustable
- Wall or ceiling installation is possible.
- Using the mounting bracket, position the antenna so that it is perpendicular to the product surface.
There is no conductive connection between the mounting bracket and transmitter housing. Electrostatic charging possible. ‣ Integrate the mounting bracket in the local potential equalization system. Cantilever installation, with pivot The cantilever, wall bracket and mounting frame are available as accessories. A B C A0028412 15 Cantilever installation, with pivot A Cantilever with wall bracket B Cantilever with mounting frame C Cantilever can be turned (e.g., in order to position the device over the center of the flume) Installation of horizontal mounting bracket for sewer shafts The horizontal mounting bracket for sewer shafts is available as an accessory. A0037747 16 Horizontal installation, mounting bracket, wastewater shaft, 40 mm (1.5 in) antenna with flooding protection tube (accessory) recommended Mounting in a shaft The pivoted mounting bracket is available as an accessory. A B A0037748 17 Mounting in a shaft, pivotable and adjustable A Arm with wall bracket B Pivotable and adjustable arm (e.g. to align the device with the center of a channel)
18 Endress+Hauser
Ambient temperature range Measuring device: –40 to +60 °C (–40 to +140 °F) For outdoor operation in strong sunlight:
- Mount the device in the shade.
- Avoid direct sunlight, particularly in warm climatic regions.
- Use a weather protection cover. Storage temperature –40 to +80 °C (–40 to +176 °F) Climate class DIN EN 60068-2-38 (test Z/AD) Operating altitude as per IEC 61010-1 Ed.3 Generally up to 2 000 m (6 600 ft) above sea level. Degree of protection Tested acc. to:
- IP66, NEMA 4X
- IP68, NEMA 6P (24 h at 1.83 m (6.00 ft)1.83 m under water) Vibration resistance DIN EN 60068-2-64/IEC 60068-2-64: 20 to 2 000 Hz, 1 (m/s2)2/Hz Electromagnetic compatibility (EMC) Electromagnetic compatibility in accordance with all of the relevant requirements outlined in the EN 61000 series and NAMUR Recommendation EMC (NE 21). Details are provided in the Declaration of Conformity (www.endress.com/downloads).
Process temperature, process pressure p Tp [ °F ]°C ( ) -1( )-14.5 bar 3 (43.5) A0030443-EN 18 FMR10: Permitted range for process temperature and process pressure Process temperature range Process pressure range
- prel = –1 to 3 bar (–14.5 to 43.5 psi)
- pabs < 4 bar (58 psi) Dielectric constant For liquids
- εr ≥ 4
- Contact Endress+Hauser for lower εr values For dielectric constants (DC values) of many media commonly used in various industries refer to:
- the Endress+Hauser DC manual (CP01076F)
- the Endress+Hauser "DC Values App" (available for Android and iOS) Mechanical construction Dimensions 40 mm (1.5 in) antenna G 1 1/2" 20 (0.79) G 1" NPT 1" 26 (1.02) ø75 (2.95) 28 (1.1) 140 (5.5) 112 (4.4) NPT 1 1/2" A B A0028805 19 Dimensions of G 1-1/2" or MNPT 1-1/2" process connection thread, engineering unit: mm (in) A Cable gland B FNPT 1/2“ conduit
20 Endress+Hauser
40 mm (1.5 in) antenna with flooding protection tube /UNI230089 (3.5) 264 (10.4) /UNI230075 (2.95) A0030266 20 Dimensions of 40 mm (1.5 in) antenna mounted with flooding protection tube, engineering unit: mm (in) The flooding protection tube, metalized PBT-PC, can be ordered together with the device via the product structure "Accessory enclosed". Counter nut for process connection, rear side 8 (0.31) G 1"1 2 (0.08) 41 mm 2 (0.08) A0028419 21 Dimensions of counter nut for process connection, rear side, engineering unit: mm (in)
1 Seal
- The counter nut with seal (EPDM) is included in the scope of supply.
- Material: PA66 Weight Weight (including 10 m (32.8 ft) cable): approx. 3.0 kg (6.6 lb)
22 Overview of materials
1 Sensor housing; PVDF
2 Seal; EPDM
3 Process connection, rear side; PVDF
4 Cable gland; PA
5 Conduit adapter; CuZn nickel-plated
6 O-ring; EPDM
7 Counter nut; PA6.6
8 Design ring; PBT-PC
9 Process connection, front side; PVDF
Connecting cable Standard length: 10 m (33 ft) If longer cable lengths are required, an extension cable must be used. In this case, the total cable length (sensor cable + extension cable) must not exceed 300 m (984 ft). Material : PVC Operability Operating concept • 4 to 20 mA
- SmartBlue (app) via Bluetooth® wireless technology Operation via Bluetooth® wireless technology 1 2 3 A0028895 23 Possibilities for remote operation via Bluetooth® wireless technology
1 Transmitter power supply unit
2 Smartphone/tablet with SmartBlue (app)
3 Transmitter with Bluetooth® wireless technology
22 Endress+Hauser
Certificates and approvals The availability of approvals and certificates can be called up daily via the Product Configurator. CE mark The measuring system meets the legal requirements of the applicable EU Directives. These are listed in the corresponding EU Declaration of Conformity along with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. RoHS The measuring system complies with the substance restrictions of the Restriction on Hazardous Substances Directive 2011/65/EU (RoHS 2). EAC conformity The measuring system meets the legal requirements of the applicable EAC guidelines. These are listed in the corresponding EAC Declaration of Conformity together with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the EAC mark. RCM-Tick marking The supplied product or measuring system meets the ACMA (Australian Communications and Media Authority) requirements for network integrity, interoperability, performance characteristics as well as health and safety regulations. Here, especially the regulatory arrangements for electromagnetic compatibility are met. The products are labelled with the RCM- Tick marking on the name plate. A0029561 Approvals • Non-hazardous area
- CSA C/US General Purpose
- Non-hazardous area + EAC mark Pressure equipment with allowable pressure ≤ 200 bar (2 900 psi) Pressure instruments with a flange and threaded boss that do not have a pressurized housing do not fall within the scope of the Pressure Equipment Directive, irrespective of the maximum allowable pressure. Reasons: According to Article 2, point 5 of EU Directive 2014/68/EU, pressure accessories are defined as "devices with an operational function and having pressure-bearing housings". If a pressure instrument does not have a pressure-bearing housing (no identifiable pressure chamber of its own), there is no pressure accessory present within the meaning of the Directive. EN 302729-1/2 radio standard The devices comply with the LPR (Level Probing Radar) radio standard EN 302729-1/2 and are approved for unrestricted use inside and outside of closed vessels in countries of the EU and EFTA. As a prerequisite, the countries in question must have already implemented this standard. The following countries are those that have currently implemented the standard: Belgium, Bulgaria, Germany, Denmark, Estonia, France, Greece, UK, Ireland, Iceland, Italy, Liechtenstein, Lithuania, Latvia, Malta, The Netherlands, Norway, Austria, Poland, Portugal, Romania, Sweden, Switzerland, Slovakia, Spain, Czech Republic and Cyprus. Implementation is still underway in all of the countries not listed. Please note the following for operation of the devices outside of closed vessels: 1. The device must be mounted in accordance with the instructions in the "Installation" section. 2. Installation must be carried out by properly trained, expert staff. 3. The device antenna must be installed in a fixed location pointing vertically downwards. 4. The installation site must be located at a distance of 4 km from the astronomy stations listed below or otherwise approval must be provided by the relevant authority. If the device is installed at a distance of 4 to 40 km from one of the listed stations, it must not be installed at a height of more than 15 m (49 ft) above the ground.
Country Name of the station Latitude Longitude Germany Effelsberg 50°31'32" North 06°53'00" East Finland Metsähovi 60°13'04" North 24°23'37" East Tuorla 60°24'56" North 24°26'31" East France Plateau de Bure 44°38'01" North 05°54'26" East Floirac 44°50'10" North 00°31'37" West Great Britain Cambridge 52°09'59" North 00°02'20" East Damhall 53°09'22" North 02°32'03" West Jodrell Bank 53°14'10" North 02°18'26" West Knockin 52°47'24" North 02°59'45" West Pickmere 53°17'18" North 02°26'38" West Italy Medicina 44°31'14" North 11°38'49" East Noto 36°52'34" North 14°59'21" East Sardinia 39°29'50" North 09°14'40" East Poland Fort Skala Krakow 50°03'18" North 19°49'36" East Russia Dmitrov 56°26'00" North 37°27'00" East Kalyazin 57°13'22" North 37°54'01" East Pushchino 54°49'00" North 37°40'00" East Zelenchukskaya 43°49'53" North 41°35'32" East Sweden Onsala 57°23'45" North 11°55'35" East Switzerland Bleien 47°20'26" North 08°06'44" East Spain Yebes 40°31'27" North 03°05'22" West Robledo 40°25'38" North 04°14'57" West Hungary Penc 47°47'22" North 19°16'53" East As a general rule, the requirements outlined in EN 302729-1/2 must be observed. FCC / Industry Canada This device complies with Part 15 of the FCC Rules [and with Industry Canada license-exempt RSS standard(s)]. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes: (1) l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.
24 Endress+Hauser
[Any] Changes or modifications made to this equipment not expressly approved by Endress+Hauser may void the FCC authorization to operate this equipment. This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna
- Increase the separation between the equipment and receiver
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected
- Consult the dealer or an experienced radio/TV technician for help
- The installation of the LPR/TLPR device shall be done by trained installers, in strict compliance with the manufacturer’s instructions.
- The use of this device is on a “no-interference, no-protection” basis. That is, the user shall accept operations of high-powered radar in the same frequency band which may interfere with or damage this device. However, devices found to interfere with primary licensing operations will be required to be removed at the user’s expense.
- Only for usage without the accessory “flooding protection tube”, i.e. NOT in the free-field: This device shall be installed and operated in a completely enclosed container to prevent RF emissions, which can otherwise interfere with aeronautical navigation. FCC / Industry Canada IDs Tank level-probing radar
- HVIN: FMR10
- FCC ID: LCGFMR2XK
- Industry Canada ID: 2519A-2K
- HVIN: FMR10X
- FCC ID: LCGFMR2XKT
- Industry Canada ID: 2519A-2KT Level-probing radar:
- HVIN: FMR10+R7
- FCC ID: LCGFMR2XKF
- Industry Canada ID: 2519A-2KF
- HVIN: FMR10+R7X
- FCC ID: LCGFMR2XKL
- Industry Canada ID: 2519A-2KL Japanese Radio Law and Japanese Telecommunications Business Law Compliance This device is granted pursuant to the Japanese Radio Law (電波法) and the Japanese Telecommunications Business Law (電気通信事業法). This device should not be modified (otherwise the granted designation number will become invalid). Certified No.: 202-LSF004 The products are labelled with the Technical Conformity Mark (GITEKI) from Japanese Ministry of Internal Affairs and Communications (MIC) on the name plate. 202-LSF004R A0032960 Mexico El funcionamiento de este equipo está sujeto a las dos condiciones siguientes:
- (1) Este equipo o aparato no puede causar interferencias perjudiciales.
- (2) Este equipo o aparato debe aceptar todas las interferencias, incluyendo las que puedan causar un funcionamiento indeseado del equipo o aparato.
Este producto contiene un módulo inalámbrico Marca: Endress+Hauser Modelo: FMR10 A0034100 Other standards and guidelines
- IEC/EN 61010-1 Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory Procedures
- IEC/EN 55011 "EMC Emission, RF Emission for Class B". Industrial, scientific and medical equipment – Electromagnetic disturbance characteristics - Limits and methods of measurement
- IEC/EN 61000-4-2 EMC Immunity, ESD (Performance Criteria A). Electromagnetic compatibility (EMC): Testing and measurement techniques - Electrostatic discharge immunity test (ESD)
- IEC/EN 61000-4-3 EMC Immunity, RF field susceptibility (Performance Criteria A). Electromagnetic compatibility (EMC): Testing and measurement techniques - Radiated, radio-frequency, electromagnetic field immunity test
- IEC/EN 61000-4-4 EMC Immunity, bursts (Performance Criteria B). Electromagnetic compatibility (EMC): Testing and measurement techniques - Electrical fast transient/burst immunity test
- IEC/EN 61000-4-5 EMC Immunity, surge (Performance Criteria B). Electromagnetic compatibility (EMC): Testing and measurement techniques - Surge immunity test
- IEC/EN 61000-4-6 EMC Immunity, conducted RF (Performance Criteria A). Electromagnetic compatibility (EMC): Testing and measurement techniques - Immunity to conducted disturbances induced by radio- frequency fields
- IEC/EN 61000-4-8 EMC Immunity, magnetic fields 50 Hz. Electromagnetic compatibility (EMC): Testing and measurement techniques - Power frequency magnetic field immunity test
- EN 61000-6-3 EMC Emission, conducted RF. EMC: Radiated interference - Residential, commercial and light industry environment
- NAMUR NE 21 Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment
- NAMUR NE 43 Standardization of the signal level for the breakdown information of digital transmitters with analog output signal.
- NAMUR NE 107 Status classification as per NE107
- NAMUR NE 131 Requirements for field devices for standard applications
- IEEE 802.15.1 Requirements for the Bluetooth® wireless technology interface
Ordering information
Detailed ordering information is available for your nearest sales organization 1. Click Corporate 2. Select the country 3. Click Products 4. Select the product using the filters and search field
26 Endress+Hauser
- Open the product page The Configuration button to the right of the product image opens the Product Configurator. Product Configurator - the tool for individual product configuration
- Up-to-the-minute configuration data
- Depending on the device: Direct input of measuring point-specific information such as measuring range or operating language
- Automatic verification of exclusion criteria
- Automatic creation of the order code and its breakdown in PDF or Excel output format
- Ability to order directly in the Endress+Hauser Online Shop Accessories Device-specific accessories Protective cover 90 (3.54) Ø 98 (3.86) A0028181 24 Dimensions of protective cover, engineering unit: mm (in) Material PVDF Order number 52025686 The sensor is not completely covered. Securing nut G 1-1/2" Suitable for devices with G 1-1/2" and MNPT 1-1/2" process connection.
G1 1/2" DIN ISO 228 60 mm 10 (0.39) A0028849 25 Dimensions of securing nut, engineering unit: mm (in) Material PC Order number 52014146
28 Endress+Hauser
Flooding protection tube 40 mm (1.5 in) Suitable for use with devices with a 40 mm (1.5 in) antenna and G 1-1/2" process connection on front. The flooding protection tube can be ordered together with the device via the product structure "Accessory enclosed". /UNI230089 (3.5) 152 (5.98) G 1-1/2" A0028418 26 Dimensions of 40 mm (1.5 in) flooding protection tube, engineering unit: mm (in) Material PBT-PC, metalized Order number 71325090
Mounting bracket, adjustable 117.5 (4.63) 92.5 (3.64) 70 (2.76) /UNI23009 (0.35) 12 (0.47) 9 (0.35) 12 (0.47)9 (0.35) 35 (1.38) A0028861 27 Dimensions of mounting bracket, engineering unit: mm (in) Consists of:
- 1 × mounting bracket, 316L (1.4404)
- 1 × angle bracket, 316L (1.4404)
- 3 × screws, A4
- 3 × securing disks, A4 Order number 71325079
30 Endress+Hauser
FAX50 screw-in flange The FAX50 screw-in flange is a universal flange which can be used for three standards (DIN - ASME - JIS) owing to its min./max. dimensions. D b L B A0029185 28 Dimensions of the UNI flange FAX50 L Bore diameter K1, Diameter of pitch circle D Flange diameter b Total flange thickness B Slotted hole (width) Order number FAX50-#### For available materials and dimensions, see TI00426F
120(4.72) 30 (1.2) 250 (9.84) G ø16 (0.6) 3 (0.12) A0019346 29 Dimensions of angle bracket. Unit of measurement mm (in) G Sensor connection in accordance with product structure "Process connection on front" Weight 3.4 kg (7.5 lb) Material 316L (1.4404) Order number for G 1-1/2" process connection 71452324 Also suitable for MNPT 1-1/2"
32 Endress+Hauser
Cantilever with pivot Installation type sensor process connection rear side A B A0028885 30 Installation type sensor process connection rear side A Installation with cantilever and wall bracket B Installation with cantilever and mounting frame
1 Cantilever
2 Wall bracket
3 Mounting frame
Cantilever (short) with pivot, sensor process connection on rear 585 (23) 200 (7.87) 35 (1.4) 50(2.0) 20 (0.8) 105 (4.1) 100 (3.9) 25(1.0) 20 (0.8) 75 (2.9) (0.08) 2 (0.08) A0037806 31 Dimensions of cantilever (short) with pivot for sensor process connection on rear. Unit of measurement mm (in) Weight: 2.1 kg (4.63 lb) Material 316L (1.4404) Order number 71452315
- 35 mm (1.38 in) openings for all G 1" or MNPT 1" connections on rear
- 22 mm (0.87 in) opening can be used for an additional sensor
- Retaining screws are included in delivery
Cantilever (long) with pivot, sensor process connection on rear 1085 (42.7) 300 (11.8) 35 (1.4) 50(2.0) 20 (0.8) 105 (4.1) 100 (3.9) 25(1.0) 20 (0.8) 75 (2.9) (0.12) 3 (0.12) A0037807 32 Dimensions of cantilever (long) with pivot for sensor process connection on rear. Unit of measurement mm (in) Weight: 4.5 kg (9.92 lb) Material 316L (1.4404) Order number 71452316
- 35 mm (1.38 in) openings for all G 1" or MNPT 1" connections on rear
- 22 mm (0.87 in) opening can be used for an additional sensor
- Retaining screws are included in delivery Installation type sensor process connection front side A B A0028886 33 Installation type sensor process connection front side A Installation with cantilever and wall bracket B Installation with cantilever and mounting frame
34 Endress+Hauser
Cantilever (short) with pivot, G 1-½" sensor process connection on front 585 (23) 200 (7.87) 35 (1.4) 50 (2.0) 20 (0.8) 105 (4.1) 100 (3.9) 25 (1.0) 20 (0.8) 75 (2.9) 2 (0.08) A0037802 34 Dimensions of cantilever (short) with pivot for G 1-½" sensor process connection on front. Unit of measurement mm (in) Weight: 1.9 kg (4.19 lb) Material 316L (1.4404) Order number 71452318
- 50 mm (2.17 in) openings for all G 1-½" (MNPT 1-½") connections on front
- 22 mm (0.87 in) opening can be used for an additional sensor
- Retaining screws are included in delivery Cantilever (long) with pivot, G 1-½" sensor process connection on front 1085 (42.7) 300 (11.8) 35 (1.4) 50 (2.0) 20 (0.8) 105 (4.1) 100 (3.9) 25 (1.0) 20 (0.8) 75 (2.9) 3 (0.12) A0037803 35 Dimensions of cantilever (long) with pivot for G 1-½" sensor process connection on front. Unit of measurement mm (in)
Weight: 4.4 kg (9.7 lb) Material 316L (1.4404) Order number 571452319
- 50 mm (2.17 in) openings for all G 1-½" (MNPT 1-½") connections on front
- 22 mm (0.87 in) opening can be used for an additional sensor
- Retaining screws are included in delivery Mounting frame (short) for cantilever with pivot 3.2 (0.13) 20 (0.8) 55 (2.17) 100 (3.94) 25 (0.98) 700 (27.6) 45 (1.77) 76(2.99) 13 (0.5) ø33.7 (1.3) 130 (5.12) 150 (5.91) 100 (3.94) 60 (2.36) 4 (0.16) 6.5 (0.3) 109 (4.29) 75 (2.95) A0037799 36 Dimensions of mounting frame (short). Unit of measurement mm (in) Weight: 3.2 kg (7.06 lb) Material 316L (1.4404) Order number 71452327
36 Endress+Hauser
Mounting frame (long) for cantilever with pivot 3.2 (0.13) 20 (0.8) 55 (2.17) 100 (3.94) 25 (0.98) 1400 (55.1) 45 (1.77) 76(2.99) 13 (0.5) ø33.7 (1.3) 130 (5.12) 150 (5.91) (3.94) 60 (2.36) 4 (0.16) 6.5 (0.3) 109 (4.29) 75 (2.95) 100 A0037800 37 Dimensions of mounting frame (long). Unit of measurement mm (in) Weight: 4.9 kg (10.08 lb) Material 316L (1.4404) Order number 71452326 Wall bracket for cantilever with pivot 110 (4.3) 25 (1.0) 4 (0.16) 6.5 (0.3) 150 (5.9) ø33.7 (1.3) 3.2 (0.1) 180 (7.1) 213 (8.4) 88 (3.5) A0019350 38 Dimensions of the wall bracket. Unit of measurement mm (in) Weight 1.4 kg (3.09 lb) Material 316L (1.4404) Order number 71452323
ø35 1210 ø5.6 155 1.5 100110±2 105 A0028891 39 Dimensions of ceiling mounting bracket. Unit of measurement mm (in) Material 316L (1.4404) Order number 71093130
38 Endress+Hauser
Pivoted mounting bracket for sewer channel The pivotable mounting bracket is used to install the device in a manhole over a sewer channel. 104 (4.09) 100 (3.94) 358 (14.1) 6.8 (0.27) 6.8 (0.27) 34 (1.34) 177 (6.97) A0038143 40 Dimensions of pivotable mounting bracket. Unit of measurement mm (in) Material 316L (1.4404) Order number 71429910
Horizontal mounting bracket for sewer shafts The horizontal mounting bracket for sewer shafts is used to install the device in confined spaces. 100(3.94) 100(3.94) 280 (11) 144 (5.67) /UNI23009 (0.35) Ø34 (1.34) 135° A0038142 41 Dimensions of horizontal mounting bracket for sewer shafts. Unit of measurement mm (in) Material 316L (1.4404) Order number 71429905
40 Endress+Hauser
Service-specific accessories Applicator Software for selecting and sizing Endress+Hauser measuring devices:
- Calculation of all the necessary data for identifying the optimum measuring device: e.g. pressure loss, accuracy or process connections.
- Graphic illustration of the calculation results Administration, documentation and access to all project-related data and parameters over the entire life cycle of a project. Applicator is available: https://portal.endress.com/webapp/applicator Configurator Product Configurator - the tool for individual product configuration
- Up-to-the-minute configuration data
- Depending on the device: Direct input of measuring point-specific information such as measuring range or operating language
- Automatic verification of exclusion criteria
- Automatic creation of the order code and its breakdown in PDF or Excel output format
- Ability to order directly in the Endress+Hauser Online Shop The Configurator is available on the Endress+Hauser website: www.endress.com -> Click "Corporate" -> Select your country -> Click "Products" -> Select the product using the filters and the search field -> Open the product page -> The "Configure" button to the right of the product image opens the Product Configurator. W@M Life cycle management for your plant W@M supports you with a wide range of software applications over the entire process: from planning and procurement, to the installation, commissioning and operation of the measuring devices. All the relevant device information, such as the device status, spare parts and device-specific documentation, is available for every device over the entire life cycle. The application already contains the data of your Endress+Hauser device. Endress+Hauser also takes care of maintaining and updating the data records. W@M is available: www.endress.com/lifecyclemanagement Supplementary documentation The following documentation types are available in the Downloads section of the Endress+Hauser website (www.endress.com/downloads): For an overview of the scope of the associated Technical Documentation, refer to the following:
- W@M Device Viewer (www.endress.com/deviceviewer): Enter the serial number from nameplate
- Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2D matrix code (QR code) on the nameplate Brief Operating Instructions (KA) Guide that takes you quickly to the 1st measured value The Brief Operating Instructions contain all the essential information from incoming acceptance to initial commissioning. Operating Instructions (BA) Your reference guide These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal. Safety Instructions (XA) Depending on the approval, the following Safety Instructions (XA) are supplied with the device. They are an integral part of the Operating Instructions. The nameplate indicates the Safety Instructions (XA) that are relevant to the device.
Apple® Apple, the Apple logo, iPhone, and iPod touch are trademarks of Apple Inc., registered in the U.S. and other countries. App Store is a service mark of Apple Inc. Android® Android, Google Play and the Google Play logo are trademarks of Google Inc. Bluetooth® The Bluetooth® word mark and logos are registered trademarks owned by the Bluetooth SIG, Inc. and any use of such marks by Endress+Hauser is under license. Other trademarks and trade names are those of their respective owners.