DB3031981 LAPP
Document overview
- Manufacturer or author: Provided By www.digicamel.com(free datasheet download site)
- PDF pages: 1
Technical content
U.I. Lapp GmbH DATA SHEET HEAT 180 1x2x0,64 DB3031981 valid from: 25.03.2013 Originator: RAWE/PDC approved: HAPF/PDC Document: DB3031981 page 1 of 1 All rights reserved acc. to DIN ISO 16016. PD 0019/2.2_11.10DE Application High temperature PROFIBUS data-cable for fixed installation up to 180 °C. The cable is oil and sunlight resistant. Design Conductor bare copper wire, ca. 0.64 mm ∅ Insulation foamed flouroethylene, core ∅ ca. 2.55 mm Core identification code a-core red, b-core green Stranding 2 cores stranded together with fillers Screening aluminized foil on top: braid of tinned copper wires, coverage ca. 60 % Outer sheath perfluoroethylenepropylene (FEP), violet, outer ∅: ca. 7.2 mm Electrical properties at 20° C Resistance (loop) max. 110 Ω/km Insulation resistance min. 16 GΩxkm Mutual capacitance ca. 28 nF/km Characteristic impedance 9.6 kHz: 270 Ω ± 27 Ω 38.4 kHz: 185 Ω ± 18.5 Ω 3 up to 20 Mhz: 150 Ω ± 15 Ω Line attenuation 9.6 kHz: max. 0.25 dB/100 m 38.4 kHz: max. 0.4 dB/100 m 4 MHz: max. 2.2 dB/100 m 16 MHz: max. 4.2 dB/100 m Operating voltage (rms-value) max. 250 V Test voltage (DC, 3 sec) 3600 V Mechanical and thermal properties Minimum bending radius repeated: 7 x outer diameter single: 5 x outer diameter Permissible temperature range -50 °C up to +180 °C General requirements Dangerous and forbidden substances acc. to RoHS directive 2011/65/EU regarding Restriction of the use of certain hazardous substances (RoHS) are not allowed to the manufacturing.