BMXDRC0805 SCHNEIDER
Document overview
- PDF pages: 5
Technical content
Page 1
Specifications
discrete module X80 - 8 NO/NC

Type C - Isolated relays - 125 V
DC/250 V AC
BMXDRC0805
Main
Modicon X80
Range of product
Relay discrete output module
Product or component type
8 conforming to EN/IEC 61131-2
Discrete output number
Positive or negative
Discrete output logic
5...125 V 5...150 V DC
Discrete output voltage
24...240 V 19...264 V AC
Complementary
40 ways terminal block
Electrical connection
50/60 Hz
Network frequency
47…63 Hz
Network frequency limits
5...150 V
Sensor power supply
19...264 V
4 A 40 °C
[Ith] conventional free air
3 A 50 °C
thermal current
2 A 60 °C
10 MOhm 500 V DC
Insulation resistance
3.6 W
Power dissipation in W
<= 10 ms activation
Response time on output
<= 13 ms deactivation
40 mA at 3.3 V DC
Typical current consumption
101 mA at 24 V DC
2683411 H
MTBF reliability
External short-circuit protection
Protection type
External overload protection External overvoltage protection, inductive AC network External overvoltage protection, inductive DC network
Use 1 fast blow fuse per channel or group of channel
Output overload protection
Use discharge diode on each output DC
Output overvoltage protection
Use RC circuit on each output AC Use ZNO surge limiter on each output AC
Use 1 fast blow fuse per channel or group of channel
Output short-circuit protection
10 mA 5 V DC
Minimum switching current
AC-12: 200000 cycles at 48 VA 24 V at 0…60 °C
Electrical durability
AC-12: 300000 cycles at 48 VA 48 V at 0…60 °C AC-12: 150000 cycles at 96 VA 48 V at 0…60 °C AC-12: 300000 cycles at 110 VA 100...120 V at 0…60 °C AC-12: 150000 cycles at 220 VA 100...120 V at 0…60 °C

Page 2
AC-12: 300000 cycles at 220 VA 200...250 V at 0…60 °C AC-12: 150000 cycles at 500 VA 200...250 V at 0…60 °C AC-15: 700000 cycles at 10 VA 24 V at 0…60 °C (load factor 0.4) AC-15: 500000 cycles at 24 VA 24 V at 0…60 °C (load factor 0.4) AC-15: 200000 cycles at 48 VA 24 V at 0…60 °C (load factor 0.4) AC-15: 700000 cycles at 10 VA 48 V at 0…60 °C (load factor 0.4) AC-15: 500000 cycles at 24 VA 48 V at 0…60 °C (load factor 0.4) AC-15: 300000 cycles at 48 VA 48 V at 0…60 °C (load factor 0.4) AC-15: 100000 cycles at 96 VA 48 V at 0…60 °C (load factor 0.4) AC-15: 1000000 cycles at 10 VA 100...120 V at 0…60 °C (load factor 0.4) AC-15: 300000 cycles at 50 VA 100...120 V at 0…60 °C (load factor 0.4)
AC-15: 200000 cycles at 110 VA 100...120 V at 0…60 °C (load factor 0.4) AC-15: 70000 cycles at 220 VA 100...120 V at 0…60 °C (load factor 0.4) AC-15: 1000000 cycles at 10 VA 200...250 V at 0…60 °C (load factor 0.4) AC-15: 500000 cycles at 50 VA 200...250 V at 0…60 °C (load factor 0.4) AC-15: 200000 cycles at 110 VA 200...250 V at 0…60 °C (load factor 0.4) AC-15: 150000 cycles at 220 VA 200...250 V at 0…60 °C (load factor 0.4) DC-12: 200000 cycles at 24 W 24 V at 0…60 °C DC-12: 150000 cycles at 48 W 24 V at 0…60 °C DC-12: 150000 cycles at 40 W 48...60 V at 0…60 °C DC-12: 100000 cycles at 45 W 100...125 V at 0…60 °C DC-13: 100000 cycles at 10 W 24 V at 0…60 °C
DC-13: 60000 cycles at 24 W 24 V at 0…60 °C DC-13: 40000 cycles at 48 W 24 V at 0…60 °C DC-13: 40000 cycles at 40 W 48...60 V at 0…60 °C DC-13: 100000 cycles at 15 W 100...125 V at 0…60 °C
1 LED (green)RUN
Status LED
1 LED per channel (green)channel diagnostic 1 LED (red)ERR 1 LED (red)I/O
0.189 kg
Net weight
Environment
IP20
IP degree of protection
1780 V AC at 50/60 Hz 1 min
Dielectric strength
3 gn
Vibration resistance
30 gn
Shock resistance
0…95 % at 0…60 °C without condensation
Relative humidity
0...2000 m
Operating altitude
2000...5000 m with derating factor
Packing Units
PCE
Unit Type of Package 1
1
Number of Units in Package 1
332.0 g
Package 1 Weight
5.5 cm
Package 1 Height
18 cm
Package 1 width
26 cm
Package 1 Length
S03
Unit Type of Package 2
8
Number of Units in Package 2
2.656 kg
Package 2 Weight
30 cm
Package 2 Height
30 cm
Package 2 width
40 cm
Package 2 Length
Offer Sustainability
Green Premium product
Sustainable offer status
REACh Regulation
REACh Declaration
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Directive
EU RoHS Declaration
Page 3
Yes
Mercury free
RoHS exemption information
Yes
China RoHS Regulation
China RoHS declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End of Life Information
The product must be disposed on European Union markets following specific waste collection and
WEEE
never end up in rubbish bins
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is
California proposition 65
known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Page 4
BMXDRC0805
Dimensions Drawings
Dimensions

(1) Front view (2) Right view (3) Top view
Page 5
BMXDRC0805
Connections and Schema
Connecting the Module
Output Circuit Diagram

(1) Module (2) Output (3) Command (4) Pre-actuator (5) Power supply NO : Normally open output NC : Normally closed output
Module Connection

(1) Pre-actuator (2) Power supply : 24...125 Vdc or 24...240 Vac (3) Fuse : Use appropriate fast-blow fuse for each relay (4) We recommend installing this type of protection on the terminals of each pre-actuator N/C : Not connected