ATV212HU55N4 ETC2

Document overview

  • PDF pages: 11

Technical content

Page 1

Characteristics

PDF page 1 diagram

Main

type

phases

limits

Complementary

Apparent power Prospective line Isc

22 kA

Continuous output current Maximum transient current Speed drive output frequency Nominal switching frequency

12 kHz

Switching frequency

Speed range

1...10

Speed accuracy Torque accuracy Transient overtorque Asynchronous motor control profile

Regulation loop Motor slip compensation

Local signalling Output voltage Isolation Type of cable for external connection

Electrical connection

5 груд 2012

variable speed drive ATV212 - 5.5kW - 7.5hp -

480V - 3ph - EMC - IP21

Range of product

Altivar 212

Product or component

Variable speed drive

Device short name

ATV212

Product destination

Asynchronous motors

Product specific

Pumps and fans in HVAC

application Assembly style

With heat sink

Network number of

3 phases

Motor power kW

5.5 kW

Motor power hp

7.5 hp

Power supply voltage

380...480 V (- 15...10 %)

Power supply voltage

323...528 V

Supply frequency

50...60 Hz (- 5...5 %)

Network frequency

47.5...63 Hz

EMC filter

Class C2 EMC filter integrated

Line current

10.9 A for 380 V 8.6 A for 480 V

9.1 kVA for 380 V

12 A at 380/460 V 13.2 A for 60 s 0.5...200 Hz

6...16 kHz adjustable 12...16 kHz with derating factor

+/- 10 % of nominal slip for 0.2 Tn to Tn torque variation +/- 15 % 120 % of nominal motor torque for 60 s Voltage/Frequency ratio, 2 points Voltage/Frequency ratio, 5 points Flux vector control without sensor, standard Voltage/Frequency ratio - Energy Saving, quadratic U/f Voltage/Frequency ratio, automatic IR compensation (U/f + automatic Uo) Adjustable PI regulator Adjustable Automatic whatever the load Not available in voltage/frequency ratio motor control 1 LED - red - DC bus energized <= power supply voltage Electrical between power and control IEC cable without mounting kit: 1 wire(s) - 45 °C, copper 90 °C / XLPE/EPR IEC cable without mounting kit: 1 wire(s) - 45 °C, copper 70 °C / PVC

UL 508 cable with UL Type 1 kit: 3 wire(s) - 40 °C, copper 75 °C / PVC Terminal 2.5 mm² / AWG 14 (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES) Terminal 6 mm² / AWG 10 (L1/R, L2/S, L3/T)

Page 2

0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)

Tightening torque

1.3 N.m - 11.5 lb.in (L1/R, L2/S, L3/T) Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC, +/- 5 % -

Supply

<= 10 A with overload and short-circuit protection Internal supply: 24 V (21...27 V) DC - <= 200 A with overload and short-circuit protection

Analogue input number

2 Configurable PTC probe: (VIB) 0...6 probes - 1500 Ohm

Analogue input type

Switch-configurable voltage: (VIA) 0...10 V DC - 24 V max - 30000 Ohm - resolution: 10 bits Switch-configurable current: (VIA) 0...20 mA - 250 Ohm - resolution: 10 bits Configurable voltage: (VIB) 0...10 V DC - 24 V max - 30000 Ohm - resolution: 10 bits 2 ms +/- 0.5 ms (F) - discrete input(s)

Sampling duration

2 ms +/- 0.5 ms (R) - discrete input(s) 2 ms +/- 0.5 ms (RES) - discrete input(s) 3.5 ms +/- 0.5 ms (VIA) - analog input(s) 22 ms +/- 0.5 ms (VIB) - analog input(s) 2 ms +/- 0.5 ms (FM) - analog output(s)

Response time

7 ms +/- 0.5 ms (FLA, FLC) - discrete output(s) 7 ms +/- 0.5 ms (FLB, FLC) - discrete output(s) 7 ms +/- 0.5 ms (RY, RC) - discrete output(s) +/- 0.6 % (VIA) for a temperature variation 60 °C

Accuracy

+/- 0.6 % (VIB) for a temperature variation 60 °C +/- 1 % (FM) for a temperature variation 60 °C +/- 0.15 % of maximum value for input (VIA)

Linearity error

+/- 0.15 % of maximum value for input (VIB) +/- 0.2 % for output (FM)

Analogue output number

1 Switch-configurable voltage: (FM) 0...10 V DC - 7620 Ohm - resolution: 10 bits

Analogue output type

Switch-configurable current: (FM) 0...20 mA - 970 Ohm - resolution: 10 bits

Discrete output number

2 Configurable relay logic: (FLA, FLC) NO - 100000 cycles

Discrete output type

Configurable relay logic: (FLB, FLC) NC - 100000 cycles Configurable relay logic: (RY, RC) NO - 100000 cycles 3 mA at 24 V DC (configurable relay logic)

Minimum switching current

5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)

Maximum switching current

5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R) 2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) 2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) Programmable (F) 24 V DC, with level 1 PLC - 4700 Ohm

Discrete input type

Programmable (R) 24 V DC, with level 1 PLC - 4700 Ohm Programmable (RES) 24 V DC, with level 1 PLC - 4700 Ohm Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)

Discrete input logic

Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1) Automatic based on the load

Acceleration and deceleration ramps

Linear adjustable separately from 0.01 to 3200 s

Braking to standstill

By DC injection Overheating protection for drive

Protection type

Thermal power stage for drive Short-circuit between motor phases for drive Input phase breaks for drive Overcurrent between output phases and earth for drive Overvoltages on the DC bus for drive Break on the control circuit for drive Against exceeding limit speed for drive Line supply overvoltage and undervoltage for drive Line supply undervoltage for drive Against input phase loss for drive Thermal protection for motor Motor phase break for motor With PTC probes for motor 3535 V DC between earth and power terminals

Dielectric strength

5092 V DC between control and power terminals >= 1 MOhm at 500 V DC for 1 minute

Insulation resistance

0.1 Hz for display unit

Frequency resolution

0.024/50 Hz for analog input

Page 3

Communication port protocol

APOGEE FLN BACnet LonWorks METASYS N2 Modbus

Connector type

1 RJ45 1 open style

Physical interface

2-wire RS 485

Transmission frame

RTU 9600 bps or 19200 bps

Transmission rate

8 bits, 1 stop, odd even or no configurable parity

Data format Type of polarization

No impedance

Number of addresses

1...247 Monitoring inhibitable

Communication service

Read device identification (43) Read holding registers (03) 2 words maximum Time out setting from 0.1 to 100 s Write multiple registers (16) 2 words maximum Write single register (06) Communication card for LonWorks

Option card

Vertical +/- 10 degree

Operating position Width

142 mm

Height

184 mm

Depth

150 mm

Product weight

3.35 kg

Power dissipation in W

215 W

Fan flow rate

74 m3/h

Environment

Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2

Electromagnetic compatibility

Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11

Pollution degree

3 IEC 61800-5-1 IP21 conforming to EN/IEC 61800-5-1

IP degree of protection

IP21 conforming to EN/IEC 60529 IP41 on upper part conforming to EN/IEC 61800-5-1 IP41 on upper part conforming to EN/IEC 60529 IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1 IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529 1.5 mm (f = 3...13 Hz) conforming to EN/IEC 60068-2-6

Vibration resistance

1 gn (f = 13...200 Hz) conforming to EN/IEC 60068-2-8 15 gn for 11 ms conforming to IEC 60068-2-27

Shock resistance

Classes 3C1 conforming to IEC 60721-3-3

Environmental characteristic

Classes 3S2 conforming to IEC 60721-3-3 51 dB conforming to 86/188/EEC

Noise level

5...95 % without condensation conforming to IEC 60068-2-3

Relative humidity

5...95 % without dripping water conforming to IEC 60068-2-3 <= 1000 m without derating

Operating altitude

1000...3000 m (limited to 2000 m for the Corner Grounded distribution network) with current derating 1 % per 100 m -10...40 °C without derating

Ambient air temperature for operation

40...50 °C with derating factor

Ambient air temperature for storage

-25...70 °C

Page 4

EN 55011 class A group 1

Standards

EN 61800-3 EN 61800-3 category C2 EN 61800-3 category C3 EN 61800-3 environments 1 category C1 EN 61800-3 environments 1 category C2 EN 61800-3 environments 1 category C3 EN 61800-3 environments 2 category C1 EN 61800-3 environments 2 category C2 EN 61800-3 environments 2 category C3 EN 61800-5-1 IEC 61800-3 IEC 61800-3 category C2 IEC 61800-3 category C3 IEC 61800-3 environments 1 category C1 IEC 61800-3 environments 1 category C2 IEC 61800-3 environments 1 category C3 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 2 category C2 IEC 61800-3 environments 2 category C3 IEC 61800-5-1 UL Type 1

Product certifications

CSA C-Tick NOM 117 UL

Marking

CE

Page 5

Dimensions Drawings

Dimensions

PDF page 5 diagram

Dimensions in mm

ATV212H a b G H J K Ø
075M3X...U22M3X 075N4...U22N4 107 143 93 121.5 5 16.5 2 x Ø5
U30M3X, U40M3X U30N4...U55N4 142 184 126 157 6.5 20.5 4 x Ø5

Dimensions in in.

ATV212H a b G H J K Ø
075M3X...U22M3X 075N4...U22N4 4.21 5.63 3.66 4.78 0.20 0.65 2 x Ø0.20
U30M3X, U40M3X U30N4...U55N4 5.59 7.24 4.96 6.18 0.26 0.81 4 x Ø0.20

Plate for EMC mounting (supplied with the drive)

PDF page 5 diagram

(1) 2 x M5 screws Dimensions in mm

ATV212H b1 c
075M3X...U22M3X 075N4...U22N4 49 67.3
U30M3X, U40M3X U30N4...U55N4 48 88.8

Dimensions in in.

ATV212H b1 c
075M3X...U22M3X 075N4...U22N4 1.93 2.65
U30M3X, U40M3X U30N4...U55N4 1.89 3.50

Page 6

Mounting and Clearance

Mounting Recommendations

Clearance

Depending on the conditions in which the drive is to be used, its installation will require certain precautions and the use of appropriate accessories. Install the unit vertically:

  • Do not place it close to heating elements.
  • Leave sufficient free space to ensure that the air required for cooling purposes can circulate from bottom to the top of the unit.
PDF page 6 diagram

Mounting Types

Type A mounting

PDF page 6 diagram

Type B mounting

PDF page 6 diagram

Type C mounting

PDF page 6 diagram

By removing the protective blanking cover from the top of the drive, the degree of protection for the drive becomes IP21. The protective blanking cover may vary according to the drive model, see opposite.

Specific Recommendations for Mounting in an Enclosure

To help ensure proper air circulation in the drive:

  • Fit ventilation grilles.
  • Check that there is sufficient ventilation. If there is not, install a forced ventilation unit with a filter. The openings and/or fans must
PDF page 6 diagram

provide a flow rate at least equal to that of the drive fans (refer to the product characteristics).

  • Use special filters with UL Type 12/IP54 protection.
  • Remove the blanking cover from the top of the drive.

Page 7

Sealed Metal Enclosure (IP54 Degree of Protection) The drive must be mounted in a dust and damp proof enclosure in certain environmental conditions, such as dust, corrosive gases, high humidity with risk of condensation and dripping water, splashing liquid, etc.This enables the drive to be used in an enclosure where the maximum internal temperature reaches 50°C.

Page 8

Connections and Schema

Recommended Wiring Diagram

3-Phase Power Supply

PDF page 8 diagram

A1: ATV 212 drive KM1: Contactor Q1: Circuit breaker Q2: GV2 L rated at twice the nominal primary current of T1 Q3: GB2CB05 S1, XB4 B or XB5 A pushbuttons S2: T1: 100 VA transformer 220 V secondary (1) Fault relay contacts for remote signalling of the drive status (2) Connection of the common for the logic inputs depends on the positioning of the switch (Source, PLC, Sink) (3) Reference potentiometer SZ1RV1202 All terminals are located at the bottom of the drive. Install interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.

Switches (Factory Settings)

Voltage/current selection for analog I/O (VIA and VIB)

Voltage/current selection for analog I/O (FM)

Selection of logic type

(1) negative logic (2) positive logic

Other Possible Wiring Diagrams

Page 9

Logic Inputs According to the Position of the Logic Type Switch

“Source” position

PDF page 9 diagram

“Sink” position

PDF page 9 diagram
“PLC” position with PLC transistor outputs
(1) PLC (1) PLC

2-wire control

PDF page 9 diagram

F: Forward R: Preset speed (2) ATV 212 control terminals

3-wire control

F: Forward R: Stop RES: Reverse (2) ATV 212 control terminals

PTC probe

PDF page 9 diagram

(2) ATV 212 control terminals (3) Motor

Analog Inputs

Voltage analog inputs

External +10 V
(2) ATV 212 control terminals (4) Speed reference potentiometer 2.2 to 10 kΩ (2) ATV 212 control terminals

Page 10

Analog input configured for current: 0-20 mA, 4-20 mA, X-Y mA

PDF page 10 diagram

(2) ATV 212 control terminals (5) Source 0-20 mA, 4-20 mA, X-Y mA

Analog input VIA configured as positive logic input (“Source” position)

(2) ATV 212 control terminals

Analog input VIA configured as negative logic input (“Sink” position)

PDF page 10 diagram

(2) ATV 212 control terminals

Page 11

Performance Curves

Derating Curves

The derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type (A, B or C). For intermediate temperatures (45°C for example), interpolate between 2 curves.

PDF page 11 diagram

X Switching frequency