Page 1
Characteristics

Main
type
phases
limits
Complementary
Apparent power Prospective line Isc
5 kA
Continuous output current Maximum transient current Speed drive output frequency Nominal switching frequency
12 kHz
Switching frequency
Speed range
1...10
Speed accuracy Torque accuracy Transient overtorque Asynchronous motor control profile
Regulation loop Motor slip compensation
Local signalling Output voltage Isolation Type of cable for external connection
Electrical connection
5 груд 2012
variable speed drive ATV212 - 2.2kW - 3hp -
480V - 3ph - EMC - IP21
Range of product
Altivar 212
Product or component
Variable speed drive
Device short name
ATV212
Product destination
Asynchronous motors
Product specific
Pumps and fans in HVAC
application Assembly style
With heat sink
Network number of
3 phases
Motor power kW
2.2 kW
Motor power hp
3 hp
Power supply voltage
380...480 V (- 15...10 %)
Power supply voltage
323...528 V
Supply frequency
50...60 Hz (- 5...5 %)
Network frequency
47.5...63 Hz
EMC filter
Class C2 EMC filter integrated
Line current
3.6 A for 480 V 4.6 A for 380 V
3.9 kVA for 380 V
5.1 A at 380/460 V 5.6 A for 60 s 0.5...200 Hz
6...16 kHz adjustable 12...16 kHz with derating factor
+/- 10 % of nominal slip for 0.2 Tn to Tn torque variation +/- 15 % 120 % of nominal motor torque for 60 s Voltage/Frequency ratio, 2 points Voltage/Frequency ratio, 5 points Flux vector control without sensor, standard Voltage/Frequency ratio - Energy Saving, quadratic U/f Voltage/Frequency ratio, automatic IR compensation (U/f + automatic Uo) Adjustable PI regulator Adjustable Automatic whatever the load Not available in voltage/frequency ratio motor control 1 LED - red - DC bus energized <= power supply voltage Electrical between power and control IEC cable without mounting kit: 1 wire(s) - 45 °C, copper 90 °C / XLPE/EPR IEC cable without mounting kit: 1 wire(s) - 45 °C, copper 70 °C / PVC
UL 508 cable with UL Type 1 kit: 3 wire(s) - 40 °C, copper 75 °C / PVC Terminal 2.5 mm² / AWG 14 (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES) Terminal 6 mm² / AWG 10 (L1/R, L2/S, L3/T)
Page 2
0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
Tightening torque
1.3 N.m - 11.5 lb.in (L1/R, L2/S, L3/T) Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC, +/- 5 % -
Supply
<= 10 A with overload and short-circuit protection Internal supply: 24 V (21...27 V) DC - <= 200 A with overload and short-circuit protection
Analogue input number
2 Configurable PTC probe: (VIB) 0...6 probes - 1500 Ohm
Analogue input type
Switch-configurable voltage: (VIA) 0...10 V DC - 24 V max - 30000 Ohm - resolution: 10 bits Switch-configurable current: (VIA) 0...20 mA - 250 Ohm - resolution: 10 bits Configurable voltage: (VIB) 0...10 V DC - 24 V max - 30000 Ohm - resolution: 10 bits 2 ms +/- 0.5 ms (F) - discrete input(s)
Sampling duration
2 ms +/- 0.5 ms (R) - discrete input(s) 2 ms +/- 0.5 ms (RES) - discrete input(s) 3.5 ms +/- 0.5 ms (VIA) - analog input(s) 22 ms +/- 0.5 ms (VIB) - analog input(s) 2 ms +/- 0.5 ms (FM) - analog output(s)
Response time
7 ms +/- 0.5 ms (FLA, FLC) - discrete output(s) 7 ms +/- 0.5 ms (FLB, FLC) - discrete output(s) 7 ms +/- 0.5 ms (RY, RC) - discrete output(s) +/- 0.6 % (VIA) for a temperature variation 60 °C
Accuracy
+/- 0.6 % (VIB) for a temperature variation 60 °C +/- 1 % (FM) for a temperature variation 60 °C +/- 0.15 % of maximum value for input (VIA)
Linearity error
+/- 0.15 % of maximum value for input (VIB) +/- 0.2 % for output (FM)
Analogue output number
1 Switch-configurable voltage: (FM) 0...10 V DC - 7620 Ohm - resolution: 10 bits
Analogue output type
Switch-configurable current: (FM) 0...20 mA - 970 Ohm - resolution: 10 bits
Discrete output number
2 Configurable relay logic: (FLA, FLC) NO - 100000 cycles
Discrete output type
Configurable relay logic: (FLB, FLC) NC - 100000 cycles Configurable relay logic: (RY, RC) NO - 100000 cycles 3 mA at 24 V DC (configurable relay logic)
Minimum switching current
5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
Maximum switching current
5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R) 2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) 2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) Programmable (F) 24 V DC, with level 1 PLC - 4700 Ohm
Discrete input type
Programmable (R) 24 V DC, with level 1 PLC - 4700 Ohm Programmable (RES) 24 V DC, with level 1 PLC - 4700 Ohm Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)
Discrete input logic
Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1) Automatic based on the load
Acceleration and deceleration ramps
Linear adjustable separately from 0.01 to 3200 s
Braking to standstill
By DC injection Overheating protection for drive
Protection type
Thermal power stage for drive Short-circuit between motor phases for drive Input phase breaks for drive Overcurrent between output phases and earth for drive Overvoltages on the DC bus for drive Break on the control circuit for drive Against exceeding limit speed for drive Line supply overvoltage and undervoltage for drive Line supply undervoltage for drive Against input phase loss for drive Thermal protection for motor Motor phase break for motor With PTC probes for motor 3535 V DC between earth and power terminals
Dielectric strength
5092 V DC between control and power terminals >= 1 MOhm at 500 V DC for 1 minute
Insulation resistance
0.1 Hz for display unit
Frequency resolution
0.024/50 Hz for analog input
Page 3
Communication port protocol
APOGEE FLN BACnet LonWorks METASYS N2 Modbus
Connector type
1 RJ45 1 open style
Physical interface
2-wire RS 485
Transmission frame
RTU 9600 bps or 19200 bps
Transmission rate
8 bits, 1 stop, odd even or no configurable parity
Data format Type of polarization
No impedance
Number of addresses
1...247 Monitoring inhibitable
Communication service
Read device identification (43) Read holding registers (03) 2 words maximum Time out setting from 0.1 to 100 s Write multiple registers (16) 2 words maximum Write single register (06) Communication card for LonWorks
Option card
Vertical +/- 10 degree
Operating position Width
107 mm
Height
143 mm
Depth
150 mm
Product weight
2 kg
Power dissipation in W
103 W
Fan flow rate
35 m3/h
Environment
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Electromagnetic compatibility
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Pollution degree
3 IEC 61800-5-1 IP21 conforming to EN/IEC 61800-5-1
IP degree of protection
IP21 conforming to EN/IEC 60529 IP41 on upper part conforming to EN/IEC 61800-5-1 IP41 on upper part conforming to EN/IEC 60529 IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1 IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529 1.5 mm (f = 3...13 Hz) conforming to EN/IEC 60068-2-6
Vibration resistance
1 gn (f = 13...200 Hz) conforming to EN/IEC 60068-2-8 15 gn for 11 ms conforming to IEC 60068-2-27
Shock resistance
Classes 3C1 conforming to IEC 60721-3-3
Environmental characteristic
Classes 3S2 conforming to IEC 60721-3-3 51 dB conforming to 86/188/EEC
Noise level
5...95 % without condensation conforming to IEC 60068-2-3
Relative humidity
5...95 % without dripping water conforming to IEC 60068-2-3 <= 1000 m without derating
Operating altitude
1000...3000 m (limited to 2000 m for the Corner Grounded distribution network) with current derating 1 % per 100 m -10...40 °C without derating
Ambient air temperature for operation
40...50 °C with derating factor
Ambient air temperature for storage
-25...70 °C
Page 4
EN 55011 class A group 1
Standards
EN 61800-3 EN 61800-3 category C2 EN 61800-3 category C3 EN 61800-3 environments 1 category C1 EN 61800-3 environments 1 category C2 EN 61800-3 environments 1 category C3 EN 61800-3 environments 2 category C1 EN 61800-3 environments 2 category C2 EN 61800-3 environments 2 category C3 EN 61800-5-1 IEC 61800-3 IEC 61800-3 category C2 IEC 61800-3 category C3 IEC 61800-3 environments 1 category C1 IEC 61800-3 environments 1 category C2 IEC 61800-3 environments 1 category C3 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 2 category C2 IEC 61800-3 environments 2 category C3 IEC 61800-5-1 UL Type 1
Product certifications
CSA C-Tick NOM 117 UL
Marking
CE
Page 5
Dimensions Drawings
Dimensions

Dimensions in mm
| ATV212H | a | b | G | H | J | K | Ø |
| 075M3X...U22M3X 075N4...U22N4 | 107 | 143 | 93 | 121.5 | 5 | 16.5 | 2 x Ø5 |
| U30M3X, U40M3X U30N4...U55N4 | 142 | 184 | 126 | 157 | 6.5 | 20.5 | 4 x Ø5 |
Dimensions in in.
| ATV212H | a | b | G | H | J | K | Ø |
| 075M3X...U22M3X 075N4...U22N4 | 4.21 | 5.63 | 3.66 | 4.78 | 0.20 | 0.65 | 2 x Ø0.20 |
| U30M3X, U40M3X U30N4...U55N4 | 5.59 | 7.24 | 4.96 | 6.18 | 0.26 | 0.81 | 4 x Ø0.20 |
Plate for EMC mounting (supplied with the drive)

(1) 2 x M5 screws Dimensions in mm
| ATV212H | b1 | c |
| 075M3X...U22M3X 075N4...U22N4 | 49 | 67.3 |
| U30M3X, U40M3X U30N4...U55N4 | 48 | 88.8 |
Dimensions in in.
| ATV212H | b1 | c |
| 075M3X...U22M3X 075N4...U22N4 | 1.93 | 2.65 |
| U30M3X, U40M3X U30N4...U55N4 | 1.89 | 3.50 |
Page 6
Mounting and Clearance
Mounting Recommendations
Clearance
Depending on the conditions in which the drive is to be used, its installation will require certain precautions and the use of appropriate accessories. Install the unit vertically:
- Do not place it close to heating elements.
- Leave sufficient free space to ensure that the air required for cooling purposes can circulate from bottom to the top of the unit.

Mounting Types
Type A mounting

Type B mounting

Type C mounting

By removing the protective blanking cover from the top of the drive, the degree of protection for the drive becomes IP21. The protective blanking cover may vary according to the drive model, see opposite.
Specific Recommendations for Mounting in an Enclosure
To help ensure proper air circulation in the drive:
- Fit ventilation grilles.
- Check that there is sufficient ventilation. If there is not, install a forced ventilation unit with a filter. The openings and/or fans must

provide a flow rate at least equal to that of the drive fans (refer to the product characteristics).
- Use special filters with UL Type 12/IP54 protection.
- Remove the blanking cover from the top of the drive.
Page 7
Sealed Metal Enclosure (IP54 Degree of Protection) The drive must be mounted in a dust and damp proof enclosure in certain environmental conditions, such as dust, corrosive gases, high humidity with risk of condensation and dripping water, splashing liquid, etc.This enables the drive to be used in an enclosure where the maximum internal temperature reaches 50°C.
Page 8
Connections and Schema
Recommended Wiring Diagram
3-Phase Power Supply

A1: ATV 212 drive KM1: Contactor Q1: Circuit breaker Q2: GV2 L rated at twice the nominal primary current of T1 Q3: GB2CB05 S1, XB4 B or XB5 A pushbuttons S2: T1: 100 VA transformer 220 V secondary (1) Fault relay contacts for remote signalling of the drive status (2) Connection of the common for the logic inputs depends on the positioning of the switch (Source, PLC, Sink) (3) Reference potentiometer SZ1RV1202 All terminals are located at the bottom of the drive. Install interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.
Switches (Factory Settings)
Voltage/current selection for analog I/O (VIA and VIB)
Voltage/current selection for analog I/O (FM)
Selection of logic type
(1) negative logic (2) positive logic
Other Possible Wiring Diagrams
Page 9
Logic Inputs According to the Position of the Logic Type Switch
“Source” position

“Sink” position

| “PLC” position with PLC transistor outputs | |
| (1) PLC | (1) PLC |
2-wire control

F: Forward R: Preset speed (2) ATV 212 control terminals
3-wire control
F: Forward R: Stop RES: Reverse (2) ATV 212 control terminals
PTC probe

(2) ATV 212 control terminals (3) Motor
Analog Inputs
Voltage analog inputs
| External +10 V | |
| (2) ATV 212 control terminals (4) Speed reference potentiometer 2.2 to 10 kΩ | (2) ATV 212 control terminals |
Page 10
Analog input configured for current: 0-20 mA, 4-20 mA, X-Y mA

(2) ATV 212 control terminals (5) Source 0-20 mA, 4-20 mA, X-Y mA
Analog input VIA configured as positive logic input (“Source” position)
(2) ATV 212 control terminals
Analog input VIA configured as negative logic input (“Sink” position)

(2) ATV 212 control terminals
Page 11
Performance Curves
Derating Curves
The derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type (A, B or C). For intermediate temperatures (45°C for example), interpolate between 2 curves.

X Switching frequency