ATV212HU22N4_V01 SCHNEIDER
Document overview
- PDF pages: 12
Technical content
Page 1
Product data sheet
Characteristics

Main
Phase
Rating
Type
voltage
Complementary
Apparent power Continuous output current
Maximum transient current Speed drive output frequency Speed range
1…10
Speed accuracy Local signalling Output voltage Isolation Type of cable
Electrical connection
Tightening torque
Supply
Sampling duration
Jan 13, 2022
ATV212HU22N4
variable speed drive ATV212 - 2.2kW - 3hp -
480V - 3ph - EMC - IP21
Device short name
ATV212
Product destination
Asynchronous motors 3 phase
Motor power kW
2.2 kW
Maximum Horse Power
3 hp
Supply voltage limits
323…528 V
Supply frequency
50...60 Hz - 5...5 %
Line current
3.6 A 480 V 4.6 A 380 V
Range of Product
Altivar 212
Product or Component
Variable speed drive
Product Specific
Pumps and fans in HVAC
Application Communication Port
BACnet
Protocol
LonWorks Modbus METASYS N2 APOGEE FLN
[Us] rated supply
380...480 V - 15...10 %
EMC filter
Class C2 EMC filter integrated
IP degree of protection
IP21
3.9 kVA 380 V 5.1 A 380 V 5.1 A 460 V 5.6 A 60 s 0.5…200 Hz
+/- 10 % of nominal slip 0.2 Tn to Tn For DC bus energized 1 LED (red) <= power supply voltage Electrical between power and control Without mounting kit 1 IEC cable 113 °F (45 °C), copper 90 °C / XLPE/EPR Without mounting kit 1 IEC cable 113 °F (45 °C), copper 70 °C / PVC With UL Type 1 kit 3 UL 508 cable 104 °F (40 °C), copper 75 °C / PVC VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES terminal 0.00 in² (2.5 mm²) / AWG 14 L1/R, L2/S, L3/T terminal 0.01 in² (6 mm²) / AWG 10 11.51 Lbf.In (1.3 N.m), 11.5 lb.in L1/R, L2/S, L3/T) 5.31 lbf.in (0.6 N.m) VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES) Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %,
<10 A overload and short-circuit protection Internal supply 24 V DC 21…27 V), <200 A overload and short-circuit protection 2 Ms +/- 0.5 ms F discrete 2 Ms +/- 0.5 ms R discrete 2 Ms +/- 0.5 ms RES discrete 3.5 Ms +/- 0.5 ms VIA analog 22 ms +/- 0.5 ms VIB analog
Page 2
FM 2 ms +/- 0.5 ms analog
Response time
FLA, FLC 7 ms +/- 0.5 ms discrete FLB, FLC 7 ms +/- 0.5 ms discrete RY, RC 7 ms +/- 0.5 ms discrete +/- 0.6 % VIA) for a temperature variation 60 °C
Accuracy
+/- 0.6 % VIB) for a temperature variation 60 °C +/- 1 % FM) for a temperature variation 60 °C VIA +/- 0.15 % of maximum value input
Linearity error
VIB +/- 0.15 % of maximum value input FM +/- 0.2 % output FM switch-configurable voltage 0...10 V DC 7620 Ohm 10 bits
Analogue output type
FM switch-configurable current 0...20 mA 970 Ohm 10 bits Configurable relay logic FLA, FLC) NO - 100000 cycles
Discrete output type
Configurable relay logic FLB, FLC) NC - 100000 cycles Configurable relay logic RY, RC) NO - 100000 cycles 3 mA 24 V DC configurable relay logic
Minimum switching current
5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R)
Maximum switching current
5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R) 2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R) 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R) F programmable 24 V DC level 1 PLC 4700 Ohm
Discrete input type
R programmable 24 V DC level 1 PLC 4700 Ohm RES programmable 24 V DC level 1 PLC 4700 Ohm Positive logic (source) F, R, RES), <= 5 V, >= 11 V
Discrete input logic
Negative logic (sink) F, R, RES), >= 16 V, <= 10 V 3535 V DC between earth and power terminals
Dielectric strength
5092 V DC between control and power terminals >= 1 mOhm 500 V DC for 1 minute
Insulation resistance Frequency resolution
Display unit 0.1 Hz Analog input 0.024/50 Hz Write single register (06)
Communication Service
Read device identification (43) Time out setting from 0.1 to 100 s Read holding registers (03) 2 words maximum Write multiple registers (16) 2 words maximum Monitoring inhibitable Communication card LonWorks
Option card Power dissipation in W
103 W 9246.19 Gal/hr(US) (35 m3/h)
Air flow Functionality
Mid
Specific application
HVAC Building - HVAC Compressor for scroll
Variable speed drive application selection
Building - HVAC Fan Building - HVAC Pump 2.2…3 KW 380…440 V 3 phase
Motor power range AC-3
2.2…3 kW 480…500 V 3 phase
Motor starter type
Variable speed drive
Discrete output number
2
Analogue input number
2 VIA switch-configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits
Analogue input type
VIB configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits VIB configurable PTC probe 0...6 probes 1500 Ohm VIA switch-configurable current 0...20 mA 250 Ohm 10 bits
Analogue output number
1
Physical interface
2-wire RS 485
Connector type
1 open style 1 RJ45 9600 bps or 19200 bps
Transmission Rate Transmission frame
RTU
Number of addresses
1…247 8 bits, 1 stop, odd even or no configurable parity
Data format Type of polarization
No impedance
Page 3
Voltage/Frequency ratio, automatic IR compensation (U/f + automatic Uo)
Asynchronous motor control profile
Voltage/Frequency ratio, 5 points Flux vector control without sensor, standard Voltage/Frequency ratio - Energy Saving, quadratic U/f Voltage/frequency ratio, 2 points
Torque accuracy
+/- 15 % 120 % of nominal motor torque +/- 10 % 60 s
Transient overtorque
Automatic based on the load
Acceleration and deceleration ramps
Linear adjustable separately from 0.01 to 3200 s Not available in voltage/frequency ratio motor control
Motor slip compensation
Adjustable Automatic whatever the load 6...16 kHz adjustable
Switching frequency
12...16 kHz with derating factor
Nominal switching frequency
12 kHz
Braking to standstill
By DC injection
Network Frequency
47.5...63 Hz
Prospective line Isc
5 kA Overheating protection drive
Protection type
Thermal power stage drive Short-circuit between motor phases drive Input phase breaks drive Overcurrent between output phases and earth drive Overvoltages on the DC bus drive Break on the control circuit drive Against exceeding limit speed drive Line supply overvoltage and undervoltage drive Line supply undervoltage drive Against input phase loss drive Thermal protection motor Motor phase break motor With PTC probes motor
Width
4.21 in (107 mm)
Height
5.63 in (143 mm)
Depth
5.91 in (150 mm) 4.41 lb(US) (2 kg)
Net Weight
Environment
Pollution degree
3 IEC 61800-5-1 IP20 on upper part without blanking plate on cover EN/IEC 61800-5-1
IP degree of protection
IP20 on upper part without blanking plate on cover EN/IEC 60529 IP21 EN/IEC 61800-5-1 IP21 EN/IEC 60529 IP41 on upper part EN/IEC 61800-5-1 IP41 on upper part EN/IEC 60529 1.5 mm 3…13 Hz)EN/IEC 60068-2-6
Vibration resistance
1 gn 13…200 Hz)EN/IEC 60068-2-8 15 gn 11 ms IEC 60068-2-27
Shock resistance
Classes 3C1 IEC 60721-3-3
Environmental characteristic
Classes 3S2 IEC 60721-3-3 51 dB 86/188/EEC
Noise level
3280.84...9842.52 ft (1000...3000 m) limited to 2000 m for the Corner Grounded
Operating altitude
distribution network with current derating 1 % per 100 m <= 3280.84 ft (1000 m) without derating 5…95 % without condensation IEC 60068-2-3
Relative humidity
5…95 % without dripping water IEC 60068-2-3 14…104 °F (-10…40 °C) without derating)
Ambient air temperature for operation
104…122 °F (40…50 °C) with derating factor) Vertical +/- 10 degree
Operating position Product Certifications
CSA NOM 117 UL C-tick
Marking
CE
Page 4
Standards
IEC 61800-3 EN 61800-5-1 IEC 61800-3 environments 1 category C2 EN 61800-3 environments 1 category C2 EN 61800-3 EN 61800-3 environments 2 category C3 EN 61800-3 environments 1 category C1 IEC 61800-3 environments 1 category C3 IEC 61800-3 category C3 IEC 61800-3 environments 2 category C1 UL Type 1 EN 61800-3 category C3 EN 61800-3 environments 1 category C3 EN 61800-3 category C2 EN 61800-3 environments 2 category C2 IEC 61800-3 environments 2 category C3 EN 55011 class A group 1 IEC 61800-3 environments 2 category C2 EN 61800-3 environments 2 category C1 IEC 61800-5-1 IEC 61800-3 category C2 IEC 61800-3 environments 1 category C1
Assembly style
With heat sink Electrostatic discharge immunity test level 3 IEC 61000-4-2
Electromagnetic compatibility
Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 Conducted radio-frequency immunity test level 3 IEC 61000-4-6 Voltage dips and interruptions immunity test IEC 61000-4-11 Adjustable PI regulator
Regulation loop
-13…158 °F (-25…70 °C)
Ambient Air Temperature for Storage
Ordering and shipping details
22157 - ATV212 1 - 25 HP 460 VOLT
Category Discount Schedule
CP4D
GTIN
3606480322464
Nbr. of units in pkg.
1 4.30 lb(US) (1.95 kg)
Package weight(Lbs) Returnability
Yes
Country of origin
ID
Packing Units
Unit Type of Package 1
PCE
Package 1 Height
7.09 in (18 cm)
Package 1 width
7.28 in (18.5 cm)
Package 1 Length
8.35 in (21.2 cm)
Unit Type of Package 2
P06
Number of Units in Package 2
27 145.57 lb(US) (66.03 kg)
Package 2 Weight Package 2 Height
28.94 in (73.5 cm)
Package 2 width
23.62 in (60 cm)
Package 2 Length
31.50 in (80 cm)
Offer Sustainability
Green Premium product
Sustainable offer status
WARNING: This product can expose you to chemicals including: Lead and
California proposition 65
lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
REACh Regulation
REACh Declaration
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS
Declaration
Mercury free
Yes
Page 5
RoHS exemption information
Yes
China RoHS Regulation
China RoHS Declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End Of Life Information The product must be disposed on European Union markets following specific
WEEE
waste collection and never end up in rubbish bins.
Contractual warranty
Warranty
18 months
Page 6
ATV212HU22N4
Product data sheet
Dimensions Drawings
Dimensions

Dimensions in mm
| ATV212H | a | b | G | H | J | K | Ø |
| 075M3X...U22M3X 075N4...U22N4 | 107 | 143 | 93 | 121.5 | 5 | 16.5 | 2 x Ø5 |
| U30M3X, U40M3X U30N4...U55N4 | 142 | 184 | 126 | 157 | 6.5 | 20.5 | 4 x Ø5 |
Dimensions in in.
| ATV212H | a | b | G | H | J | K | Ø |
| 075M3X...U22M3X 075N4...U22N4 | 4.21 | 5.63 | 3.66 | 4.78 | 0.20 | 0.65 | 2 x Ø0.20 |
| U30M3X, U40M3X U30N4...U55N4 | 5.59 | 7.24 | 4.96 | 6.18 | 0.26 | 0.81 | 4 x Ø0.20 |
Plate for EMC mounting (supplied with the drive)

(1) 2 x M5 screws Dimensions in mm
| ATV212H | b1 | c |
| 075M3X...U22M3X 075N4...U22N4 | 49 | 67.3 |
| U30M3X, U40M3X U30N4...U55N4 | 48 | 88.8 |
Dimensions in in.
| ATV212H | b1 | c |
| 075M3X...U22M3X 075N4...U22N4 | 1.93 | 2.65 |
| U30M3X, U40M3X U30N4...U55N4 | 1.89 | 3.50 |
Page 7
ATV212HU22N4
Product data sheet
Mounting and Clearance
Mounting Recommendations
Clearance
Depending on the conditions in which the drive is to be used, its installation will require certain precautions and the use of appropriate accessories. Install the unit vertically:
- Do not place it close to heating elements.
- Leave sufficient free space to ensure that the air required for cooling purposes can circulate from bottom to the top of the unit.

Mounting Types
Type A mounting

Type B mounting

Type C mounting

By removing the protective blanking cover from the top of the drive, the degree of protection for the drive becomes IP21. The protective blanking cover may vary according to the drive model, see opposite.
Specific Recommendations for Mounting in an Enclosure
To help ensure proper air circulation in the drive:
- Fit ventilation grilles.
- Check that there is sufficient ventilation. If there is not, install a forced ventilation unit with a filter. The openings and/or fans must provide
a flow rate at least equal to that of the drive fans (refer to the product characteristics).
- Use special filters with UL Type 12/IP54 protection.
- Remove the blanking cover from the top of the drive.
Page 8
Sealed Metal Enclosure (IP54 Degree of Protection) The drive must be mounted in a dust and damp proof enclosure in certain environmental conditions, such as dust, corrosive gases, high humidity with risk of condensation and dripping water, splashing liquid, etc.This enables the drive to be used in an enclosure where the maximum internal temperature reaches 50°C.
Page 9
ATV212HU22N4
Product data sheet
Connections and Schema
Recommended Wiring Diagram
3-Phase Power Supply

A1: ATV 212 drive KM1: Contactor Q1: Circuit breaker Q2: GV2 L rated at twice the nominal primary current of T1 Q3: GB2CB05 S1, XB4 B or XB5 A pushbuttons S2: T1: 100 VA transformer 220 V secondary (1) Fault relay contacts for remote signalling of the drive status (2) Connection of the common for the logic inputs depends on the positioning of the switch (Source, PLC, Sink) (3) Reference potentiometer SZ1RV1202 NOTE: All terminals are located at the bottom of the drive. Install interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.
Switches (Factory Settings)
Voltage/current selection for analog I/O (VIA and VIB)
Voltage/current selection for analog I/O (FM)
Selection of logic type
(1) negative logic (2) positive logic
Other Possible Wiring Diagrams
Page 10
Logic Inputs According to the Position of the Logic Type Switch
“Source” position

“Sink” position

| “PLC” position with PLC transistor outputs | |
| (1) PLC | (1) PLC |
2-wire control

F: Forward R: Preset speed (2) ATV 212 control terminals
3-wire control
F: Forward R: Stop RES: Reverse (2) ATV 212 control terminals
PTC probe

(2) ATV 212 control terminals (3) Motor
Analog Inputs
Voltage analog inputs
| External +10 V | |
| (2) ATV 212 control terminals (4) Speed reference potentiometer 2.2 to 10 kΩ | (2) ATV 212 control terminals |
Page 11
Analog input configured for current: 0-20 mA, 4-20 mA, X-Y mA

(2) ATV 212 control terminals (5) Source 0-20 mA, 4-20 mA, X-Y mA
Analog input VIA configured as positive logic input (“Source” position)
(2) ATV 212 control terminals
Analog input VIA configured as negative logic input (“Sink” position)

(2) ATV 212 control terminals
Page 12
ATV212HU22N4
Product data sheet
Performance Curves
Derating Curves
The derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type (A, B or C). For intermediate temperatures (45°C for example), interpolate between 2 curves.

X Switching frequency