ATV212HU15N4_V01 SCHNEIDER

Document overview

  • PDF pages: 12

Technical content

Page 1

Product data sheet

Characteristics

PDF page 1 diagram

Main

Phase

Rating

Type

voltage

Complementary

Apparent power Continuous output current

Maximum transient current Speed drive output frequency Speed range

1…10

Speed accuracy Local signalling Output voltage Isolation Type of cable

Electrical connection

Tightening torque

Supply

Sampling duration

Jan 13, 2022

ATV212HU15N4

variable speed drive ATV212 - 1.5kW - 2hp -

480V - 3ph - EMC - IP21

Device short name

ATV212

Product destination

Asynchronous motors 3 phase

Motor power kW

1.5 kW

Maximum Horse Power

2 hp

Supply voltage limits

323…528 V

Supply frequency

50...60 Hz - 5...5 %

Line current

2.5 A 480 V 3.2 A 380 V

Range of Product

Altivar 212

Product or Component

Variable speed drive

Product Specific

Pumps and fans in HVAC

Application Communication Port

APOGEE FLN

Protocol

BACnet Modbus LonWorks METASYS N2

[Us] rated supply

380...480 V - 15...10 %

EMC filter

Class C2 EMC filter integrated

IP degree of protection

IP21

2.8 kVA 380 V 3.7 A 380 V 3.7 A 460 V 4 A 60 s 0.5…200 Hz

+/- 10 % of nominal slip 0.2 Tn to Tn For DC bus energized 1 LED (red) <= power supply voltage Electrical between power and control Without mounting kit 1 IEC cable 113 °F (45 °C), copper 90 °C / XLPE/EPR Without mounting kit 1 IEC cable 113 °F (45 °C), copper 70 °C / PVC With UL Type 1 kit 3 UL 508 cable 104 °F (40 °C), copper 75 °C / PVC VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES terminal 0.00 in² (2.5 mm²) / AWG 14 L1/R, L2/S, L3/T terminal 0.01 in² (6 mm²) / AWG 10 11.51 Lbf.In (1.3 N.m), 11.5 lb.in L1/R, L2/S, L3/T) 5.31 lbf.in (0.6 N.m) VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES) Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %,

<10 A overload and short-circuit protection Internal supply 24 V DC 21…27 V), <200 A overload and short-circuit protection 2 Ms +/- 0.5 ms F discrete 2 Ms +/- 0.5 ms R discrete 2 Ms +/- 0.5 ms RES discrete 3.5 Ms +/- 0.5 ms VIA analog 22 ms +/- 0.5 ms VIB analog

Page 2

FM 2 ms +/- 0.5 ms analog

Response time

FLA, FLC 7 ms +/- 0.5 ms discrete FLB, FLC 7 ms +/- 0.5 ms discrete RY, RC 7 ms +/- 0.5 ms discrete +/- 0.6 % VIA) for a temperature variation 60 °C

Accuracy

+/- 0.6 % VIB) for a temperature variation 60 °C +/- 1 % FM) for a temperature variation 60 °C VIA +/- 0.15 % of maximum value input

Linearity error

VIB +/- 0.15 % of maximum value input FM +/- 0.2 % output FM switch-configurable voltage 0...10 V DC 7620 Ohm 10 bits

Analogue output type

FM switch-configurable current 0...20 mA 970 Ohm 10 bits Configurable relay logic FLA, FLC) NO - 100000 cycles

Discrete output type

Configurable relay logic FLB, FLC) NC - 100000 cycles Configurable relay logic RY, RC) NO - 100000 cycles 3 mA 24 V DC configurable relay logic

Minimum switching current

5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R)

Maximum switching current

5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R) 2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R) 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R) F programmable 24 V DC level 1 PLC 4700 Ohm

Discrete input type

R programmable 24 V DC level 1 PLC 4700 Ohm RES programmable 24 V DC level 1 PLC 4700 Ohm Positive logic (source) F, R, RES), <= 5 V, >= 11 V

Discrete input logic

Negative logic (sink) F, R, RES), >= 16 V, <= 10 V 3535 V DC between earth and power terminals

Dielectric strength

5092 V DC between control and power terminals >= 1 mOhm 500 V DC for 1 minute

Insulation resistance Frequency resolution

Display unit 0.1 Hz Analog input 0.024/50 Hz Read device identification (43)

Communication Service

Time out setting from 0.1 to 100 s Monitoring inhibitable Write single register (06) Read holding registers (03) 2 words maximum Write multiple registers (16) 2 words maximum Communication card LonWorks

Option card Power dissipation in W

78 W 7132.77 Gal/hr(US) (27 m3/h)

Air flow Functionality

Mid

Specific application

HVAC Compressor for scroll Building - HVAC

Variable speed drive application selection

Fan Building - HVAC Pump Building - HVAC 1.1…2 KW 380…440 V 3 phase

Motor power range AC-3

1.1…2 kW 480…500 V 3 phase

Motor starter type

Variable speed drive

Discrete output number

2

Analogue input number

2 VIA switch-configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits

Analogue input type

VIB configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits VIB configurable PTC probe 0...6 probes 1500 Ohm VIA switch-configurable current 0...20 mA 250 Ohm 10 bits

Analogue output number

1

Physical interface

2-wire RS 485

Connector type

1 open style 1 RJ45 9600 bps or 19200 bps

Transmission Rate Transmission frame

RTU

Number of addresses

1…247 8 bits, 1 stop, odd even or no configurable parity

Data format Type of polarization

No impedance

Page 3

Voltage/Frequency ratio - Energy Saving, quadratic U/f

Asynchronous motor control profile

Voltage/Frequency ratio, 5 points Voltage/Frequency ratio, automatic IR compensation (U/f + automatic Uo) Voltage/Frequency ratio, 2 points Flux vector control without sensor, standard

Torque accuracy

+/- 15 % 120 % of nominal motor torque +/- 10 % 60 s

Transient overtorque

Linear adjustable separately from 0.01 to 3200 s

Acceleration and deceleration ramps

Automatic based on the load

Motor slip compensation

Adjustable Not available in voltage/frequency ratio motor control Automatic whatever the load 6...16 kHz adjustable

Switching frequency

12...16 kHz with derating factor

Nominal switching frequency

12 kHz

Braking to standstill

By DC injection

Network Frequency

47.5...63 Hz

Prospective line Isc

5 kA Overheating protection drive

Protection type

Thermal power stage drive Short-circuit between motor phases drive Input phase breaks drive Overcurrent between output phases and earth drive Overvoltages on the DC bus drive Break on the control circuit drive Against exceeding limit speed drive Line supply overvoltage and undervoltage drive Line supply undervoltage drive Against input phase loss drive Thermal protection motor Motor phase break motor With PTC probes motor

Width

4.21 in (107 mm)

Height

5.63 in (143 mm)

Depth

5.91 in (150 mm) 4.41 lb(US) (2 kg)

Net Weight

Environment

Pollution degree

2 IEC 61800-5-1 IP20 on upper part without blanking plate on cover EN/IEC 61800-5-1

IP degree of protection

IP20 on upper part without blanking plate on cover EN/IEC 60529 IP21 EN/IEC 61800-5-1 IP21 EN/IEC 60529 IP41 on upper part EN/IEC 61800-5-1 IP41 on upper part EN/IEC 60529 1.5 mm 3…13 Hz)EN/IEC 60068-2-6

Vibration resistance

1 gn 13…200 Hz)EN/IEC 60068-2-8 15 gn 11 ms IEC 60068-2-27

Shock resistance

Classes 3C1 IEC 60721-3-3

Environmental characteristic

Classes 3S2 IEC 60721-3-3 51 dB 86/188/EEC

Noise level

3280.84...9842.52 ft (1000...3000 m) limited to 2000 m for the Corner Grounded

Operating altitude

distribution network with current derating 1 % per 100 m <= 3280.84 ft (1000 m) without derating 5…95 % without condensation IEC 60068-2-3

Relative humidity

5…95 % without dripping water IEC 60068-2-3 14…104 °F (-10…40 °C) without derating)

Ambient air temperature for operation

104…122 °F (40…50 °C) with derating factor) Vertical +/- 10 degree

Operating position Product Certifications

UL NOM 117 C-tick CSA

Marking

CE

Page 4

EN 55011 class A group 1

Standards

EN 61800-3 environments 2 category C1 EN 61800-3 category C3 IEC 61800-3 IEC 61800-3 environments 2 category C2 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 1 category C3 UL Type 1 IEC 61800-3 environments 2 category C3 IEC 61800-3 environments 1 category C2 EN 61800-3 environments 1 category C3 EN 61800-3 EN 61800-3 environments 1 category C2 EN 61800-3 environments 2 category C3 IEC 61800-3 environments 1 category C1 EN 61800-5-1 IEC 61800-3 category C3 IEC 61800-3 category C2 IEC 61800-5-1 EN 61800-3 category C2 EN 61800-3 environments 1 category C1 EN 61800-3 environments 2 category C2

Assembly style

With heat sink Electrostatic discharge immunity test level 3 IEC 61000-4-2

Electromagnetic compatibility

Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 Conducted radio-frequency immunity test level 3 IEC 61000-4-6 Voltage dips and interruptions immunity test IEC 61000-4-11 Adjustable PI regulator

Regulation loop

-13…158 °F (-25…70 °C)

Ambient Air Temperature for Storage

Ordering and shipping details

22157 - ATV212 1 - 25 HP 460 VOLT

Category Discount Schedule

CP4D

GTIN

3606480322457

Nbr. of units in pkg.

1 4.26 lb(US) (1.933 kg)

Package weight(Lbs) Returnability

Yes

Country of origin

ID

Packing Units

Unit Type of Package 1

PCE

Package 1 Height

7.68 in (19.5 cm)

Package 1 width

7.68 in (19.5 cm)

Package 1 Length

8.86 in (22.5 cm)

Unit Type of Package 2

P06

Number of Units in Package 2

27 143.72 lb(US) (65.19 kg)

Package 2 Weight Package 2 Height

28.94 in (73.5 cm)

Package 2 width

23.62 in (60 cm)

Package 2 Length

31.50 in (80 cm)

Offer Sustainability

Green Premium product

Sustainable offer status

WARNING: This product can expose you to chemicals including: Lead and

California proposition 65

lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

REACh Regulation

REACh Declaration

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

EU RoHS

Declaration

Mercury free

Yes

Page 5

RoHS exemption information

Yes

China RoHS Regulation

China RoHS Declaration

Environmental Disclosure

Product Environmental Profile

Circularity Profile

End Of Life Information The product must be disposed on European Union markets following specific

WEEE

waste collection and never end up in rubbish bins.

Contractual warranty

Warranty

18 months

Page 6

ATV212HU15N4

Product data sheet

Dimensions Drawings

Dimensions

PDF page 6 diagram

Dimensions in mm

ATV212H a b G H J K Ø
075M3X...U22M3X 075N4...U22N4 107 143 93 121.5 5 16.5 2 x Ø5
U30M3X, U40M3X U30N4...U55N4 142 184 126 157 6.5 20.5 4 x Ø5

Dimensions in in.

ATV212H a b G H J K Ø
075M3X...U22M3X 075N4...U22N4 4.21 5.63 3.66 4.78 0.20 0.65 2 x Ø0.20
U30M3X, U40M3X U30N4...U55N4 5.59 7.24 4.96 6.18 0.26 0.81 4 x Ø0.20

Plate for EMC mounting (supplied with the drive)

PDF page 6 diagram

(1) 2 x M5 screws Dimensions in mm

ATV212H b1 c
075M3X...U22M3X 075N4...U22N4 49 67.3
U30M3X, U40M3X U30N4...U55N4 48 88.8

Dimensions in in.

ATV212H b1 c
075M3X...U22M3X 075N4...U22N4 1.93 2.65
U30M3X, U40M3X U30N4...U55N4 1.89 3.50

Page 7

ATV212HU15N4

Product data sheet

Mounting and Clearance

Mounting Recommendations

Clearance

Depending on the conditions in which the drive is to be used, its installation will require certain precautions and the use of appropriate accessories. Install the unit vertically:

  • Do not place it close to heating elements.
  • Leave sufficient free space to ensure that the air required for cooling purposes can circulate from bottom to the top of the unit.
PDF page 7 diagram

Mounting Types

Type A mounting

PDF page 7 diagram

Type B mounting

PDF page 7 diagram

Type C mounting

PDF page 7 diagram

By removing the protective blanking cover from the top of the drive, the degree of protection for the drive becomes IP21. The protective blanking cover may vary according to the drive model, see opposite.

Specific Recommendations for Mounting in an Enclosure

To help ensure proper air circulation in the drive:

  • Fit ventilation grilles.
  • Check that there is sufficient ventilation. If there is not, install a forced ventilation unit with a filter. The openings and/or fans must provide

a flow rate at least equal to that of the drive fans (refer to the product characteristics).

  • Use special filters with UL Type 12/IP54 protection.
  • Remove the blanking cover from the top of the drive.

Page 8

Sealed Metal Enclosure (IP54 Degree of Protection) The drive must be mounted in a dust and damp proof enclosure in certain environmental conditions, such as dust, corrosive gases, high humidity with risk of condensation and dripping water, splashing liquid, etc.This enables the drive to be used in an enclosure where the maximum internal temperature reaches 50°C.

Page 9

ATV212HU15N4

Product data sheet

Connections and Schema

Recommended Wiring Diagram

3-Phase Power Supply

PDF page 9 diagram

A1: ATV 212 drive KM1: Contactor Q1: Circuit breaker Q2: GV2 L rated at twice the nominal primary current of T1 Q3: GB2CB05 S1, XB4 B or XB5 A pushbuttons S2: T1: 100 VA transformer 220 V secondary (1) Fault relay contacts for remote signalling of the drive status (2) Connection of the common for the logic inputs depends on the positioning of the switch (Source, PLC, Sink) (3) Reference potentiometer SZ1RV1202 NOTE: All terminals are located at the bottom of the drive. Install interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.

Switches (Factory Settings)

Voltage/current selection for analog I/O (VIA and VIB)

Voltage/current selection for analog I/O (FM)

Selection of logic type

(1) negative logic (2) positive logic

Other Possible Wiring Diagrams

Page 10

Logic Inputs According to the Position of the Logic Type Switch

“Source” position

PDF page 10 diagram

“Sink” position

PDF page 10 diagram
“PLC” position with PLC transistor outputs
(1) PLC (1) PLC

2-wire control

PDF page 10 diagram

F: Forward R: Preset speed (2) ATV 212 control terminals

3-wire control

F: Forward R: Stop RES: Reverse (2) ATV 212 control terminals

PTC probe

PDF page 10 diagram

(2) ATV 212 control terminals (3) Motor

Analog Inputs

Voltage analog inputs

External +10 V
(2) ATV 212 control terminals (4) Speed reference potentiometer 2.2 to 10 kΩ (2) ATV 212 control terminals

Page 11

Analog input configured for current: 0-20 mA, 4-20 mA, X-Y mA

PDF page 11 diagram

(2) ATV 212 control terminals (5) Source 0-20 mA, 4-20 mA, X-Y mA

Analog input VIA configured as positive logic input (“Source” position)

(2) ATV 212 control terminals

Analog input VIA configured as negative logic input (“Sink” position)

PDF page 11 diagram

(2) ATV 212 control terminals

Page 12

ATV212HU15N4

Product data sheet

Performance Curves

Derating Curves

The derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type (A, B or C). For intermediate temperatures (45°C for example), interpolate between 2 curves.

PDF page 12 diagram

X Switching frequency