ATV212HD30N4 SCHNEIDER
Document overview
- PDF pages: 11
Technical content
Page 1
Characteristics

Main
type
tion
age
Complementary
Apparent power Prospective line Isc Continuous output current
Maximum transient current Speed drive output frequency Nominal switching frequency Switching frequency
Speed range Speed accuracy Torque accuracy Transient overtorque Asynchronous motor control profile
Regulation loop Motor slip compensation
Local signalling Output voltage Isolation Type of cable
Aug 9, 2019
variable speed drive ATV212 - 30kW - 40hp -
480V - 3ph - EMC - IP21
Product availability: Stock - Normally stocked in distribution facility
Range of product
Altivar 212
Product or component
Variable speed drive
Device short name
ATV212
Product destination
Asynchronous motors
Product specific applica-
Pumps and fans in HVAC
Assembly style
With heat sink
Phase
3 phases
Motor power kW
30 kW
Motor power hp
40 hp
[Us] rated supply volt-
380...480 V - 15...10 %
Supply voltage limits
323...528 V
Supply frequency
50...60 Hz - 5...5 %
Network frequency
47.5...63 Hz
EMC filter
Class C2 EMC filter integrated
Line current
44.7 A 480 V 56.7 A 380 V
44.6 kVA 380 V 22 kA 58.5 A 380 V 58.5 A 460 V 64.4 A 60 s 0.5...200 Hz 8 kHz 6...16 kHz adjustable 8...16 kHz with derating factor 1...10 +/- 10 % of nominal slip 0.2 Tn to Tn +/- 15 % 120 % of nominal motor torque +/- 10 % 60 s Voltage/Frequency ratio, 2 points Voltage/Frequency ratio, 5 points Flux vector control without sensor, standard Voltage/Frequency ratio - Energy Saving, quadratic U/f Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) Adjustable PI regulator Adjustable Automatic whatever the load Not available in voltage/frequency ratio motor control 1 LED red DC bus energized <= power supply voltage Electrical between power and control
IEC cable without mounting kit 1 113 °F (45 °C) copper 90 °C XLPE/EPR IEC cable without mounting kit 1 45 °C copper 70 °C PVC UL 508 cable with UL Type 1 kit 3 40 °C copper 75 °C PVC
Page 2
Terminal 0 in² (2.5 mm²) AWG 14 VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R,
Electrical connection
RES Terminal 50 mm² AWG 1/0 L1/R, L2/S, L3/T 212.39 lbf.in (24 N.m) 212 lb.in L1/R, L2/S, L3/T
Tightening torque
0.6 N.m VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 % <=
Supply
10 A overload and short-circuit protection Internal supply 24 V DC 21...27 V <= 200 A overload and short-circuit protection
Analogue input number
2 Switch-configurable voltage VIA 0...10 V DC 24 V max 30000 Ohm 10 bits
Analogue input type
Configurable voltage VIB 0...10 V DC 24 V max 30000 Ohm 10 bits Configurable PTC probe VIB 0...6 probes 1500 Ohm Switch-configurable current VIA 0...20 mA 250 Ohm 10 bits 2 ms +/- 0.5 ms F discrete
Sampling duration
2 ms +/- 0.5 ms R discrete 2 ms +/- 0.5 ms RES discrete 3.5 ms +/- 0.5 ms VIA analog 22 ms +/- 0.5 ms VIB analog 2 ms +/- 0.5 ms FM analog
Response time
7 ms +/- 0.5 ms FLA, FLC discrete 7 ms +/- 0.5 ms FLB, FLC discrete 7 ms +/- 0.5 ms RY, RC discrete +/- 0.6 % VIA for a temperature variation 60 °C
Accuracy
+/- 0.6 % VIB for a temperature variation 60 °C +/- 1 % FM for a temperature variation 60 °C +/- 0.15 % of maximum value input VIA
Linearity error
+/- 0.15 % of maximum value input VIB +/- 0.2 % output FM
Analogue output number
1 Switch-configurable voltage FM 0...10 V DC 7620 Ohm 10 bits
Analogue output type
Switch-configurable current FM 0...20 mA 970 Ohm 10 bits
Discrete output number
2 Configurable relay logic FLA, FLC NO 100000 cycles
Discrete output type
Configurable relay logic FLB, FLC NC 100000 cycles Configurable relay logic RY, RC NO 100000 cycles 3 mA 24 V DC configurable relay logic
Minimum switching current
5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R
Maximum switching current
5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R 2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R Programmable F 24 V DC level 1 PLC 4700 Ohm
Discrete input type
Programmable R 24 V DC level 1 PLC 4700 Ohm Programmable RES 24 V DC level 1 PLC 4700 Ohm Positive logic (source) F, R, RES <= 5 V >= 11 V
Discrete input logic
Negative logic (sink) F, R, RES >= 16 V <= 10 V Automatic based on the load
Acceleration and deceleration ramps
Linear adjustable separately from 0.01 to 3200 s
Braking to standstill
By DC injection Motor phase break motor
Protection type
Break on the control circuit drive Thermal power stage drive Overvoltages on the DC bus drive Against exceeding limit speed drive Against input phase loss drive With PTC probes motor Input phase breaks drive Line supply overvoltage and undervoltage drive Line supply undervoltage drive Overcurrent between output phases and earth drive Overheating protection drive Short-circuit between motor phases drive Thermal protection motor 3535 V DC between earth and power terminals
Dielectric strength
5092 V DC between control and power terminals >= 1 MOhm 500 V DC for 1 minute
Insulation resistance
0.024/50 Hz analog input
Frequency resolution
0.1 Hz display unit
Page 3
Communication port protocol
APOGEE FLN BACnet LonWorks METASYS N2 Modbus
Connector type
1 RJ45 1 open style
Physical interface
2-wire RS 485
Transmission frame
RTU 9600 bps or 19200 bps
Transmission rate
8 bits, 1 stop, odd even or no configurable parity
Data format Type of polarization
No impedance
Number of addresses
1...247 Monitoring inhibitable
Communication service
Read device identification (43) Read holding registers (03) 2 words maximum Time out setting from 0.1 to 100 s Write multiple registers (16) 2 words maximum Write single register (06) Communication card LonWorks
Option card
Vertical +/- 10 degree
Operating position Width
9.45 in (240 mm) 16.54 in (420 mm)
Height Depth
8.43 in (214 mm) 58.2 lb(US) (26.4 kg)
Product weight Power dissipation in W
847 W 76611.27 Gal/hr(US) (290 m3/h)
Air flow Functionality
Mid
Specific application
HVAC
IP degree of protection
IP21 Building - HVAC : compressor for scroll
Variable speed drive application selection
Building - HVAC : fan Building - HVAC : pump 30...50 kW at 380...440 V 3 phases
Motor power range AC-3
30...50 kW at 480...500 V 3 phases Variable speed drive
Motor starter type
Environment
Conducted radio-frequency immunity test level 3 IEC 61000-4-6
Electromagnetic compatibility
Voltage dips and interruptions immunity test IEC 61000-4-11 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 Electrical fast transient/burst immunity test level 4 IEC 61000-4-4 Electrostatic discharge immunity test level 3 IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3
Pollution degree
3 IEC 61800-5-1 IP20 on upper part without blanking plate on cover EN/IEC 61800-5-1
IP degree of protection
IP20 on upper part without blanking plate on cover EN/IEC 60529 IP21 EN/IEC 61800-5-1 IP21 EN/IEC 60529 IP41 on upper part EN/IEC 61800-5-1 IP41 on upper part EN/IEC 60529 1 gn 13...200 Hz EN/IEC 60068-2-8
Vibration resistance
1.5 mm 3...13 Hz EN/IEC 60068-2-6 15 gn 11 ms IEC 60068-2-27
Shock resistance
Classes 3C1 IEC 60721-3-3
Environmental characteristic
Classes 3S2 IEC 60721-3-3 59.9 dB 86/188/EEC
Noise level
3280.84...9842.52 ft (1000...3000 m) limited to 2000 m for the Corner Grounded
Operating altitude
distribution network with current derating 1 % per 100 m <= 3280.84 ft (1000 m) without derating 5...95 % without condensation IEC 60068-2-3
Relative humidity
5...95 % without dripping water IEC 60068-2-3 14...104 °F (-10...40 °C) without derating
Ambient air temperature for operation
104...122 °F (> 40...50 °C) with derating factor
Page 4
-13...158 °F (-25...70 °C)
Ambient air temperature for storage
EN 55011 class A group 1
Standards
EN 61800-3 EN 61800-3 category C2 EN 61800-3 category C3 EN 61800-3 environments 1 category C1 EN 61800-3 environments 1 category C2 EN 61800-3 environments 1 category C3 EN 61800-3 environments 2 category C1 EN 61800-3 environments 2 category C2 EN 61800-3 environments 2 category C3 EN 61800-5-1 IEC 61800-3 IEC 61800-3 category C2 IEC 61800-3 category C3 IEC 61800-3 environments 1 category C1 IEC 61800-3 environments 1 category C2 IEC 61800-3 environments 1 category C3 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 2 category C2 IEC 61800-3 environments 2 category C3 IEC 61800-5-1 UL Type 1
Product certifications
CSA C-Tick NOM 117 UL
Marking
CE
Ordering and shipping details
22158 - ATV212 30 - 100 HP 460 VOLT
Category Discount Schedule
CP4D
GTIN
00785901921554
Nbr. of units in pkg.
1 68.200000000000003
Package weight(Lbs) Returnability
Y
Country of origin
CN
Offer Sustainability
Green Premium product
Sustainable offer status RoHS (date code: YYWW)
Compliant - since 1050 - Schneider Electric declaration of conformity
Schnei-
der Electric declaration of conformity Reference not containing SVHC above the threshold
REACh Product environmental profile
Available
Product end of life instructions
Available WARNING: This product can expose you to chemicals including:
California proposition 65
Lead and lead compounds, which is known to the State of California to cause can-
- - - - - - - Substance 1
cer and birth defects or other reproductive harm. Bisphenol A (BPA), which is known to the State of California to cause birth defects
- - - - - - - Substance 2
or other reproductive harm. For more information go to www.p65warnings.ca.gov
- - - - - - - More information
Contractual warranty
Warranty period
18 months
Page 5
Dimensions Drawings
Dimensions

Dimensions in mm
| ATV212H | a | b | c | G | H | K | Ø |
| D22M3X D22N4, D30N4 | 240 | 420 | 214 | 206 | 403 | 10 | 6 |
| D37N4, D45N4 | 240 | 550 | 244 | 206 | 529 | 10 | 6 |
Dimensions in in.
| ATV212H | a | b | c | G | H | K | Ø |
| D22M3X D22N4, D30N4 | 9.45 | 16.54 | 8.43 | 8.11 | 15.87 | 0.39 | 0.24 |
| D37N4, D45N4 | 9.45 | 21.65 | 9.60 | 8.11 | 20.83 | 0.39 | 0.24 |
EMC mounting plate (supplied with drive)

Dimensions in mm
| ATV212H | b1 | c1 |
| D22M3X D22N4, D30N4 | 122 | 120 |
| D37N4, D45N4 | 113 | 127 |
Dimensions in in.
| ATV212H | b1 | c1 |
| D22M3X D22N4, D30N4 | 4.80 | 4.72 |
| D37N4, D45N4 | 4.45 | 5.00 |
Page 6
Mounting and Clearance
Mounting Recommendations
Clearance
Depending on the conditions in which the drive is to be used, its installation will require certain precautions and the use of appropriate accessories. Install the unit vertically:
- Do not place it close to heating elements.
- Leave sufficient free space to ensure that the air required for cooling purposes can circulate from bottom to the top of the unit.

Mounting Types
Type A mounting

Type B mounting

Type C mounting

By removing the protective blanking cover from the top of the drive, the degree of protection for the drive becomes IP21. The protective blanking cover may vary according to the drive model, see opposite.
Specific Recommendations for Mounting in an Enclosure
To help ensure proper air circulation in the drive:
- Fit ventilation grilles.
- Check that there is sufficient ventilation. If there is not, install a forced ventilation unit with a filter. The openings and/or fans must provide
a flow rate at least equal to that of the drive fans (refer to the product characteristics).
- Use special filters with UL Type 12/IP54 protection.
- Remove the blanking cover from the top of the drive.
Page 7
Sealed Metal Enclosure (IP54 Degree of Protection) The drive must be mounted in a dust and damp proof enclosure in certain environmental conditions, such as dust, corrosive gases, high humidity with risk of condensation and dripping water, splashing liquid, etc.This enables the drive to be used in an enclosure where the maximum internal temperature reaches 50°C.
Page 8
Connections and Schema
Recommended Wiring Diagram
3-Phase Power Supply

A1: ATV 212 drive KM1: Contactor Q1: Circuit breaker Q2: GV2 L rated at twice the nominal primary current of T1 Q3: GB2CB05 S1, XB4 B or XB5 A pushbuttons S2: T1: 100 VA transformer 220 V secondary (1) Fault relay contacts for remote signalling of the drive status (2) Connection of the common for the logic inputs depends on the positioning of the switch (Source, PLC, Sink) (3) Reference potentiometer SZ1RV1202 NOTE: All terminals are located at the bottom of the drive. Install interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.
Switches (Factory Settings)
Voltage/current selection for analog I/O (VIA and VIB)
Voltage/current selection for analog I/O (FM)
Selection of logic type
(1) negative logic (2) positive logic
Other Possible Wiring Diagrams
Page 9
Logic Inputs According to the Position of the Logic Type Switch
“Source” position

“Sink” position

| “PLC” position with PLC transistor outputs | |
| (1) PLC | (1) PLC |
2-wire control

F: Forward R: Preset speed (2) ATV 212 control terminals
3-wire control
F: Forward R: Stop RES: Reverse (2) ATV 212 control terminals
PTC probe

(2) ATV 212 control terminals (3) Motor
Analog Inputs
Voltage analog inputs
| External +10 V | |
| (2) ATV 212 control terminals (4) Speed reference potentiometer 2.2 to 10 kΩ | (2) ATV 212 control terminals |
Page 10
Analog input configured for current: 0-20 mA, 4-20 mA, X-Y mA

(2) ATV 212 control terminals (5) Source 0-20 mA, 4-20 mA, X-Y mA
Analog input VIA configured as positive logic input (“Source” position)
(2) ATV 212 control terminals
Analog input VIA configured as negative logic input (“Sink” position)

(2) ATV 212 control terminals
Page 11
Performance Curves
Derating Curves
The derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type (A, B or C). For intermediate temperatures (45°C for example), interpolate between 2 curves.

X Switching frequency