ATV212HU30M3X SCHNEIDER
Document overview
- PDF pages: 12
Technical content
Page 1
Specifications
variable speed drive ATV212 - 3kW

- 240V - 3ph - wo EMC - IP21
Discontinued on: 14 February 2023
To be discontinued
Main
ATV212
Device short name
Asynchronous motors
Product destination
3 phases
Network number of phases
3 kW
Motor power kW
4 hp
Motor power hp
170…264 V
Supply voltage limits
50...60 Hz - 5...5 %
Supply frequency
10 A at 240 V
Line current
11.9 A at 200 V
Altivar 212
Range of product
Variable speed drive
Product or component type
Pumps and fans in HVAC
Product specific application
Modbus
Communication port protocol
LonWorks METASYS N2 BACnet APOGEE FLN
200...240 V - 15...10 %
[Us] rated supply voltage
Without EMC filter
EMC filter
IP21
IP degree of protection
Complementary
5.2 kVA at 240 V
Apparent power
13.7 A at 230 V
Continuous output current
15.1 A for 60 s
Maximum transient current
0.5…200 Hz
Speed drive output frequency
1…10
Speed range
+/- 10 % of nominal slip 0.2 Tn to Tn
Speed accuracy
1 LED (red) for DC bus energized
Local signalling
<= power supply voltage
Output voltage
Electrical between power and control
Isolation

Page 2
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
Type of cable
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC
VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14
Electrical connection
L1/R, L2/S, L3/T: terminal 6 mm² / AWG 10
1.3 N.m, 11.5 lb.in (L1/R, L2/S, L3/T)
Tightening torque
0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type:
Supply
overload and short-circuit protection Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection
2 ms +/- 0.5 ms F discrete
Sampling duration
2 ms +/- 0.5 ms R discrete 2 ms +/- 0.5 ms RES discrete 3.5 ms +/- 0.5 ms VIA analog 22 ms +/- 0.5 ms VIB analog
FM 2 ms, tolerance +/- 0.5 ms for analog output(s)
Response time
FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
+/- 0.6 % (VIA) for a temperature variation 60 °C
Accuracy
+/- 0.6 % (VIB) for a temperature variation 60 °C +/- 1 % (FM) for a temperature variation 60 °C
VIA: +/- 0.15 % of maximum value for input
Linearity error
VIB: +/- 0.15 % of maximum value for input FM: +/- 0.2 % for output
FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits
Analogue output type
FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits
Configurable relay logic: (FLA, FLC) NO - 100000 cycles
Discrete output type
Configurable relay logic: (FLB, FLC) NC - 100000 cycles Configurable relay logic: (RY, RC) NO - 100000 cycles
3 mA at 24 V DC for configurable relay logic
Minimum switching current
5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
Maximum switching current
5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R) 2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) 2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)
F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
Discrete input type
R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)
Discrete input logic
Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1)
2830 V DC between earth and power terminals
Dielectric strength
4230 V DC between control and power terminals
= 1 mOhm 500 V DC for 1 minute
Insulation resistance
Display unit: 0.1 Hz
Frequency resolution
Analog input: 0.024/50 Hz
Time out setting from 0.1 to 100 s
Communication service
Read device identification (43) Monitoring inhibitable Read holding registers (03) 2 words maximum Write single register (06) Write multiple registers (16) 2 words maximum
Communication card for LonWorks
Option card
146 W
Power dissipation in W
50 m3/h
Air flow
HVAC
Specific application
Variable speed drive application Compressor for scroll Building - HVAC
Fan Building - HVAC
selection
Pump Building - HVAC
2.2…3 kW at 200…240 V 3 phases
Motor power range AC-3
Variable speed drive
Motor starter type
Discrete output number
Analogue input number
VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
Analogue input type
Page 3
VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits
1
Analogue output number
2-wire RS 485
Physical interface
1 RJ45
Connector type
1 open style
9600 bps or 19200 bps
Transmission rate
RTU
Transmission frame
1…247
Number of addresses
8 bits, 1 stop, odd even or no configurable parity
Data format
No impedance
Type of polarization
Voltage/frequency ratio, 5 points
Asynchronous motor control
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)
profile
Voltage/frequency ratio, 2 points Flux vector control without sensor, standard Voltage/frequency ratio - Energy Saving, quadratic U/f
+/- 15 %
Torque accuracy
120 % of nominal motor torque +/- 10 % for 60 s
Transient overtorque
Automatic based on the load
Acceleration and deceleration
Linear adjustable separately from 0.01 to 3200 s
ramps
Not available in voltage/frequency ratio motor control
Motor slip compensation
Automatic whatever the load Adjustable
6...16 kHz adjustable
Switching frequency
12...16 kHz with derating factor
12 kHz
Nominal switching frequency
By DC injection
Braking to standstill
47.5...63 Hz
Network frequency
5 kA
Prospective line Isc
Overheating protection: drive
Protection type
Thermal power stage: drive Short-circuit between motor phases: drive Input phase breaks: drive Overcurrent between output phases and earth: drive Overvoltages on the DC bus: drive Break on the control circuit: drive Against exceeding limit speed: drive Line supply overvoltage and undervoltage: drive Line supply undervoltage: drive Against input phase loss: drive Thermal protection: motor Motor phase break: motor With PTC probes: motor
142 mm
Width
184 mm
Height
150 mm
Depth
3.05 kg
Net weight
Environment
3 conforming to IEC 61800-5-1
Pollution degree
IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1 IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529 IP21 conforming to EN/IEC 61800-5-1 IP21 conforming to EN/IEC 60529 IP41 on upper part conforming to EN/IEC 61800-5-1 IP41 on upper part conforming to EN/IEC 60529
1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6
Vibration resistance
1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-8
15 gn for 11 ms conforming to IEC 60068-2-27
Shock resistance
Page 4
Classes 3C1 conforming to IEC 60721-3-3
Environmental characteristic
Classes 3S2 conforming to IEC 60721-3-3
51 dB conforming to 86/188/EEC
Noise level
1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 %
Operating altitude
per 100 m <= 1000 m without derating
5…95 % without condensation conforming to IEC 60068-2-3
Relative humidity
5…95 % without dripping water conforming to IEC 60068-2-3
-10…40 °C (without derating)
Ambient air temperature for
40…50 °C (with derating factor)
operation
Vertical +/- 10 degree
Operating position
NOM 117
Product certifications
C-Tick UL CSA
CE
Marking
IEC 61800-3 environments 1 category C2
Standards
EN 61800-3 environments 1 category C3 IEC 61800-3 environments 2 category C1 EN 61800-3 environments 2 category C3 EN 61800-3 environments 2 category C2 IEC 61800-3 environments 2 category C2 EN 61800-3 IEC 61800-3 environments 1 category C3 IEC 61800-3 EN 61800-5-1 EN 61800-3 environments 1 category C1 IEC 61800-3 environments 2 category C3 IEC 61800-5-1 IEC 61800-3 environments 1 category C1 UL Type 1 EN 61800-3 environments 1 category C2 EN 61800-3 environments 2 category C1
With heat sink
Assembly style
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Electromagnetic compatibility
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Adjustable PI regulator
Regulation loop
-25…70 °C
Ambient air temperature for storage
Packing Units
PCE
Unit Type of Package 1
1
Number of Units in Package 1
24 cm
Package 1 Height
24.5 cm
Package 1 Width
24.5 cm
Package 1 Length
2.797 kg
Package 1 Weight
P06
Unit Type of Package 2
12
Number of Units in Package 2
75 cm
Package 2 Height
60 cm
Package 2 Width
80 cm
Package 2 Length
46.564 kg
Package 2 Weight
Offer Sustainability
Green Premium product
Sustainable offer status
Page 5
REACh Regulation
REACh Declaration
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Directive
EU RoHS Declaration
Yes
Mercury free
China RoHS Regulation
China RoHS declaration
RoHS exemption information
Yes
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End of Life Information
The product must be disposed on European Union markets following specific waste collection and
WEEE
never end up in rubbish bins
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is
California proposition 65
known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Contractual warranty
18 months
Warranty
Page 6
Dimensions Drawings
Dimensions

Dimensions in mm
| ATV212H | a | b | G | H | J | K | Ø |
| 075M3X...U22M3X 075N4...U22N4 | 107 | 143 | 93 | 121.5 | 5 | 16.5 | 2 x Ø5 |
| U30M3X, U40M3X U30N4...U55N4 | 142 | 184 | 126 | 157 | 6.5 | 20.5 | 4 x Ø5 |
Dimensions in in.
| ATV212H | a | b | G | H | J | K | Ø |
| 075M3X...U22M3X 075N4...U22N4 | 4.21 | 5.63 | 3.66 | 4.78 | 0.20 | 0.65 | 2 x Ø0.20 |
| U30M3X, U40M3X U30N4...U55N4 | 5.59 | 7.24 | 4.96 | 6.18 | 0.26 | 0.81 | 4 x Ø0.20 |
Plate for EMC mounting (supplied with the drive)

2 x M5 screws (1) Dimensions in mm
| ATV212H | b1 | c |
| 075M3X...U22M3X 075N4...U22N4 | 49 | 67.3 |
| U30M3X, U40M3X U30N4...U55N4 | 48 | 88.8 |
Dimensions in in.
| ATV212H | b1 | c |
| 075M3X...U22M3X 075N4...U22N4 | 1.93 | 2.65 |
| U30M3X, U40M3X U30N4...U55N4 | 1.89 | 3.50 |
Page 7
Mounting and Clearance
Mounting Recommendations
Clearance
Depending on the conditions in which the drive is to be used, its installation will require certain precautions and the use of appropriate accessories. Install the unit vertically:
- Do not place it close to heating elements.
- Leave sufficient free space to ensure that the air required for cooling purposes can circulate from bottom to the top of the unit.

Mounting Types
Type A mounting

Type B mounting

Type C mounting

By removing the protective blanking cover from the top of the drive, the degree of protection for the drive becomes IP21. The protective blanking cover may vary according to the drive model, see opposite.
Page 8
Mounting and Clearance
Specific Recommendations for Mounting in an Enclosure
To help ensure proper air circulation in the drive:
- Fit ventilation grilles.
- Check that there is sufficient ventilation. If there is not, install a forced ventilation unit with a filter. The openings and/or fans must provide a flow rate at
- Use special filters with UL Type 12/IP54 protection.
- Remove the blanking cover from the top of the drive.
Sealed Metal Enclosure (IP54 Degree of Protection)
The drive must be mounted in a dust and damp proof enclosure in certain environmental conditions, such as dust, corrosive gases, high humidity with risk of condensation and dripping water, splashing liquid, etc.This enables the drive to be used in an enclosure where the maximum internal temperature reaches 50°C.
Page 9
Connections and Schema
Recommended Wiring Diagram
3-Phase Power Supply

ATV 212 drive A1: KM1: Contactor Circuit breaker Q1: GV2 L rated at twice the nominal primary current of T1 Q2: GB2CB05 Q3: S1, S2: XB4 B or XB5 A pushbuttons 100 VA transformer 220 V secondary T1: Fault relay contacts for remote signalling of the drive status (1) Connection of the common for the logic inputs depends on the positioning of the switch (Source, PLC, Sink) (2) Reference potentiometer SZ1RV1202 (3) NOTE: All terminals are located at the bottom of the drive. Install interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.
Switches (Factory Settings)
Voltage/current selection for analog I/O (VIA and VIB)
Voltage/current selection for analog I/O (FM)
Selection of logic type
negative logic (1) positive logic (2)
Page 10
Connections and Schema
Other Possible Wiring Diagrams
Logic Inputs According to the Position of the Logic Type Switch
“Source” position

“Sink” position

| “PLC” position with PLC transistor outputs | |
| (1) PLC | (1) PLC |
2-wire control

Forward F: Preset speed R: ATV 212 control terminals (2)
3-wire control
Forward F: Stop R: Reverse RES: ATV 212 control terminals (2)
PTC probe

ATV 212 control terminals (2) Motor (3)
Analog Inputs
Voltage analog inputs
| External +10 V | |
| (2) ATV 212 control terminals (4) Speed reference potentiometer 2.2 to 10 kΩ | (2) ATV 212 control terminals |
Analog input configured for current: 0-20 mA, 4-20 mA, X-Y mA

ATV 212 control terminals (2) Source 0-20 mA, 4-20 mA, X-Y mA (5)
Page 11
Analog input VIA configured as positive logic input (“Source” position)
ATV 212 control terminals (2)
Analog input VIA configured as negative logic input (“Sink” position)

ATV 212 control terminals (2)
Page 12
Performance Curves
Derating Curves
The derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type (A, B or C). For intermediate temperatures (45°C for example), interpolate between 2 curves.

Switching frequency X
Recommended replacement(s)
ATV212HU30M3X is replaced by the following product range: