ATV212HU30M3X SCHNEIDER

Document overview

  • PDF pages: 12

Technical content

Page 1

Specifications

variable speed drive ATV212 - 3kW

PDF page 1 diagram

- 240V - 3ph - wo EMC - IP21

Discontinued on: 14 February 2023

To be discontinued

Main

ATV212

Device short name

Asynchronous motors

Product destination

3 phases

Network number of phases

3 kW

Motor power kW

4 hp

Motor power hp

170…264 V

Supply voltage limits

50...60 Hz - 5...5 %

Supply frequency

10 A at 240 V

Line current

11.9 A at 200 V

Altivar 212

Range of product

Variable speed drive

Product or component type

Pumps and fans in HVAC

Product specific application

Modbus

Communication port protocol

LonWorks METASYS N2 BACnet APOGEE FLN

200...240 V - 15...10 %

[Us] rated supply voltage

Without EMC filter

EMC filter

IP21

IP degree of protection

Complementary

5.2 kVA at 240 V

Apparent power

13.7 A at 230 V

Continuous output current

15.1 A for 60 s

Maximum transient current

0.5…200 Hz

Speed drive output frequency

1…10

Speed range

+/- 10 % of nominal slip 0.2 Tn to Tn

Speed accuracy

1 LED (red) for DC bus energized

Local signalling

<= power supply voltage

Output voltage

Electrical between power and control

Isolation

PDF page 1 diagram

Page 2

Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR

Type of cable

Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC

VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14

Electrical connection

L1/R, L2/S, L3/T: terminal 6 mm² / AWG 10

1.3 N.m, 11.5 lb.in (L1/R, L2/S, L3/T)

Tightening torque

0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)

Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type:

Supply

overload and short-circuit protection Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection

2 ms +/- 0.5 ms F discrete

Sampling duration

2 ms +/- 0.5 ms R discrete 2 ms +/- 0.5 ms RES discrete 3.5 ms +/- 0.5 ms VIA analog 22 ms +/- 0.5 ms VIB analog

FM 2 ms, tolerance +/- 0.5 ms for analog output(s)

Response time

FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)

+/- 0.6 % (VIA) for a temperature variation 60 °C

Accuracy

+/- 0.6 % (VIB) for a temperature variation 60 °C +/- 1 % (FM) for a temperature variation 60 °C

VIA: +/- 0.15 % of maximum value for input

Linearity error

VIB: +/- 0.15 % of maximum value for input FM: +/- 0.2 % for output

FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits

Analogue output type

FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits

Configurable relay logic: (FLA, FLC) NO - 100000 cycles

Discrete output type

Configurable relay logic: (FLB, FLC) NC - 100000 cycles Configurable relay logic: (RY, RC) NO - 100000 cycles

3 mA at 24 V DC for configurable relay logic

Minimum switching current

5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)

Maximum switching current

5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R) 2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) 2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)

F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm

Discrete input type

R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm

Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)

Discrete input logic

Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1)

2830 V DC between earth and power terminals

Dielectric strength

4230 V DC between control and power terminals

= 1 mOhm 500 V DC for 1 minute

Insulation resistance

Display unit: 0.1 Hz

Frequency resolution

Analog input: 0.024/50 Hz

Time out setting from 0.1 to 100 s

Communication service

Read device identification (43) Monitoring inhibitable Read holding registers (03) 2 words maximum Write single register (06) Write multiple registers (16) 2 words maximum

Communication card for LonWorks

Option card

146 W

Power dissipation in W

50 m3/h

Air flow

HVAC

Specific application

Variable speed drive application Compressor for scroll Building - HVAC

Fan Building - HVAC

selection

Pump Building - HVAC

2.2…3 kW at 200…240 V 3 phases

Motor power range AC-3

Variable speed drive

Motor starter type

Discrete output number

Analogue input number

VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits

Analogue input type

Page 3

VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits

1

Analogue output number

2-wire RS 485

Physical interface

1 RJ45

Connector type

1 open style

9600 bps or 19200 bps

Transmission rate

RTU

Transmission frame

1…247

Number of addresses

8 bits, 1 stop, odd even or no configurable parity

Data format

No impedance

Type of polarization

Voltage/frequency ratio, 5 points

Asynchronous motor control

Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)

profile

Voltage/frequency ratio, 2 points Flux vector control without sensor, standard Voltage/frequency ratio - Energy Saving, quadratic U/f

+/- 15 %

Torque accuracy

120 % of nominal motor torque +/- 10 % for 60 s

Transient overtorque

Automatic based on the load

Acceleration and deceleration

Linear adjustable separately from 0.01 to 3200 s

ramps

Not available in voltage/frequency ratio motor control

Motor slip compensation

Automatic whatever the load Adjustable

6...16 kHz adjustable

Switching frequency

12...16 kHz with derating factor

12 kHz

Nominal switching frequency

By DC injection

Braking to standstill

47.5...63 Hz

Network frequency

5 kA

Prospective line Isc

Overheating protection: drive

Protection type

Thermal power stage: drive Short-circuit between motor phases: drive Input phase breaks: drive Overcurrent between output phases and earth: drive Overvoltages on the DC bus: drive Break on the control circuit: drive Against exceeding limit speed: drive Line supply overvoltage and undervoltage: drive Line supply undervoltage: drive Against input phase loss: drive Thermal protection: motor Motor phase break: motor With PTC probes: motor

142 mm

Width

184 mm

Height

150 mm

Depth

3.05 kg

Net weight

Environment

3 conforming to IEC 61800-5-1

Pollution degree

IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1 IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529 IP21 conforming to EN/IEC 61800-5-1 IP21 conforming to EN/IEC 60529 IP41 on upper part conforming to EN/IEC 61800-5-1 IP41 on upper part conforming to EN/IEC 60529

1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6

Vibration resistance

1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-8

15 gn for 11 ms conforming to IEC 60068-2-27

Shock resistance

Page 4

Classes 3C1 conforming to IEC 60721-3-3

Environmental characteristic

Classes 3S2 conforming to IEC 60721-3-3

51 dB conforming to 86/188/EEC

Noise level

1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 %

Operating altitude

per 100 m <= 1000 m without derating

5…95 % without condensation conforming to IEC 60068-2-3

Relative humidity

5…95 % without dripping water conforming to IEC 60068-2-3

-10…40 °C (without derating)

Ambient air temperature for

40…50 °C (with derating factor)

operation

Vertical +/- 10 degree

Operating position

NOM 117

Product certifications

C-Tick UL CSA

CE

Marking

IEC 61800-3 environments 1 category C2

Standards

EN 61800-3 environments 1 category C3 IEC 61800-3 environments 2 category C1 EN 61800-3 environments 2 category C3 EN 61800-3 environments 2 category C2 IEC 61800-3 environments 2 category C2 EN 61800-3 IEC 61800-3 environments 1 category C3 IEC 61800-3 EN 61800-5-1 EN 61800-3 environments 1 category C1 IEC 61800-3 environments 2 category C3 IEC 61800-5-1 IEC 61800-3 environments 1 category C1 UL Type 1 EN 61800-3 environments 1 category C2 EN 61800-3 environments 2 category C1

With heat sink

Assembly style

Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2

Electromagnetic compatibility

Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11

Adjustable PI regulator

Regulation loop

-25…70 °C

Ambient air temperature for storage

Packing Units

PCE

Unit Type of Package 1

1

Number of Units in Package 1

24 cm

Package 1 Height

24.5 cm

Package 1 Width

24.5 cm

Package 1 Length

2.797 kg

Package 1 Weight

P06

Unit Type of Package 2

12

Number of Units in Package 2

75 cm

Package 2 Height

60 cm

Package 2 Width

80 cm

Package 2 Length

46.564 kg

Package 2 Weight

Offer Sustainability

Green Premium product

Sustainable offer status

Page 5

REACh Regulation

REACh Declaration

Pro-active compliance (Product out of EU RoHS legal scope)

EU RoHS Directive

EU RoHS Declaration

Yes

Mercury free

China RoHS Regulation

China RoHS declaration

RoHS exemption information

Yes

Environmental Disclosure

Product Environmental Profile

Circularity Profile

End of Life Information

The product must be disposed on European Union markets following specific waste collection and

WEEE

never end up in rubbish bins

WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is

California proposition 65

known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Contractual warranty

18 months

Warranty

Page 6

Dimensions Drawings

Dimensions

PDF page 6 diagram

Dimensions in mm

ATV212H a b G H J K Ø
075M3X...U22M3X 075N4...U22N4 107 143 93 121.5 5 16.5 2 x Ø5
U30M3X, U40M3X U30N4...U55N4 142 184 126 157 6.5 20.5 4 x Ø5

Dimensions in in.

ATV212H a b G H J K Ø
075M3X...U22M3X 075N4...U22N4 4.21 5.63 3.66 4.78 0.20 0.65 2 x Ø0.20
U30M3X, U40M3X U30N4...U55N4 5.59 7.24 4.96 6.18 0.26 0.81 4 x Ø0.20

Plate for EMC mounting (supplied with the drive)

PDF page 6 diagram

2 x M5 screws (1) Dimensions in mm

ATV212H b1 c
075M3X...U22M3X 075N4...U22N4 49 67.3
U30M3X, U40M3X U30N4...U55N4 48 88.8

Dimensions in in.

ATV212H b1 c
075M3X...U22M3X 075N4...U22N4 1.93 2.65
U30M3X, U40M3X U30N4...U55N4 1.89 3.50

Page 7

Mounting and Clearance

Mounting Recommendations

Clearance

Depending on the conditions in which the drive is to be used, its installation will require certain precautions and the use of appropriate accessories. Install the unit vertically:

  • Do not place it close to heating elements.
  • Leave sufficient free space to ensure that the air required for cooling purposes can circulate from bottom to the top of the unit.
PDF page 7 diagram

Mounting Types

Type A mounting

PDF page 7 diagram

Type B mounting

PDF page 7 diagram

Type C mounting

PDF page 7 diagram

By removing the protective blanking cover from the top of the drive, the degree of protection for the drive becomes IP21. The protective blanking cover may vary according to the drive model, see opposite.

Page 8

Mounting and Clearance

Specific Recommendations for Mounting in an Enclosure

To help ensure proper air circulation in the drive:

  • Fit ventilation grilles.
  • Check that there is sufficient ventilation. If there is not, install a forced ventilation unit with a filter. The openings and/or fans must provide a flow rate at
  • Use special filters with UL Type 12/IP54 protection.
  • Remove the blanking cover from the top of the drive.

Sealed Metal Enclosure (IP54 Degree of Protection)

The drive must be mounted in a dust and damp proof enclosure in certain environmental conditions, such as dust, corrosive gases, high humidity with risk of condensation and dripping water, splashing liquid, etc.This enables the drive to be used in an enclosure where the maximum internal temperature reaches 50°C.

Page 9

Connections and Schema

Recommended Wiring Diagram

3-Phase Power Supply

PDF page 9 diagram

ATV 212 drive A1: KM1: Contactor Circuit breaker Q1: GV2 L rated at twice the nominal primary current of T1 Q2: GB2CB05 Q3: S1, S2: XB4 B or XB5 A pushbuttons 100 VA transformer 220 V secondary T1: Fault relay contacts for remote signalling of the drive status (1) Connection of the common for the logic inputs depends on the positioning of the switch (Source, PLC, Sink) (2) Reference potentiometer SZ1RV1202 (3) NOTE: All terminals are located at the bottom of the drive. Install interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.

Switches (Factory Settings)

Voltage/current selection for analog I/O (VIA and VIB)

Voltage/current selection for analog I/O (FM)

Selection of logic type

negative logic (1) positive logic (2)

Page 10

Connections and Schema

Other Possible Wiring Diagrams

Logic Inputs According to the Position of the Logic Type Switch

“Source” position

PDF page 10 diagram

“Sink” position

PDF page 10 diagram
“PLC” position with PLC transistor outputs
(1) PLC (1) PLC

2-wire control

PDF page 10 diagram

Forward F: Preset speed R: ATV 212 control terminals (2)

3-wire control

Forward F: Stop R: Reverse RES: ATV 212 control terminals (2)

PTC probe

PDF page 10 diagram

ATV 212 control terminals (2) Motor (3)

Analog Inputs

Voltage analog inputs

External +10 V
(2) ATV 212 control terminals (4) Speed reference potentiometer 2.2 to 10 kΩ (2) ATV 212 control terminals

Analog input configured for current: 0-20 mA, 4-20 mA, X-Y mA

PDF page 10 diagram

ATV 212 control terminals (2) Source 0-20 mA, 4-20 mA, X-Y mA (5)

Page 11

Analog input VIA configured as positive logic input (“Source” position)

ATV 212 control terminals (2)

Analog input VIA configured as negative logic input (“Sink” position)

PDF page 11 diagram

ATV 212 control terminals (2)

Page 12

Performance Curves

Derating Curves

The derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type (A, B or C). For intermediate temperatures (45°C for example), interpolate between 2 curves.

PDF page 12 diagram

Switching frequency X

Recommended replacement(s)

ATV212HU30M3X is replaced by the following product range:

PDF page 12 diagram