AS168X SCHURTER

Document overview

  • Manufacturer or author: Provided By digicamel.com
  • PDF pages: 9

Technical content

Features

  • Excellent short circuit performance (up to 10 kA)
  • High limits of discrimination (due to energy limitation)
  • Wide choice of characteristics (Adaptability)
  • Availability of AC and DC in the same frame size
  • Compact, «finger safe» design
  • Ease installation (on DIN rail)

Applications

  • Industrial machines
  • Automation
  • Aircondition, ventilation
  • Transformers
  • Power supplies
  • Telecom systems
  • Computer systems
  • Test systems
  • Medical equipments MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERÄTESCHUTZSCHALTER AS168X

www.schurter.com124 Beispiel DC-Version: Nennstrom bei +23°C 10 A Umgebungstemperatur +50°C Korrekturfaktor 1,2 Gewählter Nennstrom bei +50°C Umgebungstemperatur

10 A x 1,2 = 12 A

Umgebungs- Korrekturfaktor temperatur [°C] AC-Version DC-Version –20 0,78 0,80 –5 0,82 0,87 0 0,83 0,90 +10 0,87 0,95 +23 0,91 1,00 +30 0,95 1,05 +40 1,00 1,10 +50 1,05 1,20 +60 1,11 1,30 Einfluss der Umgebungstemperatur AC-Schalter sind für eine Umgebungs- temperatur von +40°C geeicht, DC-Schalter für +23°C. Zur Bestimmung des Nennstromes für eine tiefere oder höhere Umgebungs- temperatur ist ein Korrekturfaktor gemäss untenstehender Tabelle zu verwenden: Example DC version: Rated current at +23°C 10 A Ambient temperature +50°C Correction factor 1,2 Chosen rated current at +50°C ambient temperature Auslösekennlinie F Tripping characteristic G Auslösekennlinie G Tripping characteristic H Auslösekennlinie H Ambient Correction factor temperature [°C] AC version DC version –20 0,78 0,80 –5 0,82 0,87 0 0,83 0,90 +10 0,87 0,95 +23 0,91 1,00 +30 0,95 1,05 +40 1,00 1,10 +50 1,05 1,20 +60 1,11 1,30 Effect of ambient temperature AC-breakers are calibrated for an ambient temperature of +40°C, DC-breakers for +23°C. To determine the rated current for a lower or higher ambient temperature, use a correction factor from the table below: Multiple of rated current (x In) Nennstrom-Vielfaches (x In) 1 10 100 1000 x I n 0,1ms 1ms 10ms 0,1s 10s 100s 1000s 1hr Tripping time / Auslösezeit Multiple of rated current (x In) Nennstrom-Vielfaches (x In) 1 10 100 1000 x I n 0,1ms 1ms 10ms 0,1s 10s 100s 1000s 1hr Tripping time / Auslösezeit Multiple of rated current (x In) Nennstrom-Vielfaches (x In) 1 10 100 1000 x I n 0,1ms 1ms 10ms 0,1s 10s 100s 1000s 1hr Tripping time / Auslösezeit MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERÄTESCHUTZSCHALTER AS168X

www.schurter.com 125 MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERÄTESCHUTZSCHALTER AS168X Technical data / Technische Daten Pole / Pole: Rated voltage Ue AC versions / AC Versionen F; G; H AC 480/277 V; DC 65 V Nennspannung Ue DC versions / DC Versionen DF; DG; DH DC 180 V 1 pole / 1polig DC 360 V 2 – 3 pole / 2 – 3polig Note: The connection polarity must be strictly observed. An application with a DC Type AS168X in an AC network is not allowed. Hinweis: Die Anschlusspolarität muss unbedingt beachtet werden. Eine Anwendung von DC Versionen in AC Netzen ist nicht zulässig. Rated current In See approvals, page 126 AC/DC 0,5 – 52 A Nennstrom In Siehe Approbationen Seite 126 AC/DC 0,5 – 52 A Endurance Number of cycles at In 6000 Lebensdauer Anzahl Schaltspiele bei In 6000 Type of tripping • Thermal magnetic / thermisch-magnetisch TM Auslöseart • Positively trip-free / positive Freiauslösung Type of actuation / Betätigungsart Manual ON/OFF / Manuell EIN/AUS S-type / S-Typ Permissible wire cross section 1,5 – 25 mm 2 /AWG #16...4 Zulässiger Leiterquerschnitt 1,5 – 25 mm2 /AWG #16...4 Switched neutral / Schaltbarer, neutraler Pol: Rated voltage Ue / Nennspannung Ue AC 277 V Rated current In / Nennstrom In AC/DC 65 A Function The switched neutral closes with manual closure of the poles and opens automatically with thermal magnetic tripping of the poles. Tripping characteristic DF Auslösekennlinie DF Tripping characteristic DG Auslösekennlinie DG Tripping characteristic DH Auslösekennlinie DH Multiple of rated current (x In) Nennstrom-Vielfaches (x In) 1 10 100 1000 x I n 0,1ms 1ms 10ms 0,1s 10s 100s 1000s 1hr Tripping time / Auslösezeit Multiple of rated current (x In) Nennstrom-Vielfaches (x In) 1 10 100 1000 x I n 0,1ms 1ms 10ms 0,1s 10s 100s 1000s 1hr Tripping time / Auslösezeit Multiple of rated current (x In) Nennstrom-Vielfaches (x In) 1 10 100 1000 x I n 0,1ms 1ms 10ms 0,1s 10s 100s 1000s 1hr Tripping time / Auslösezeit

www.schurter.com126 Technical data (continued) / Technische Daten (Fortsetzung) Funktion Der Neutralleitertrenner schliesst bei manueller Einschaltung der Pole und öffnet automatisch bei thermisch- magnetischer Auslösung der Pole. Add-on modules / Zusatzmodule: Rated voltage Ue / Nennspannung Ue Rated current In / Nennstrom In Auxiliary contact H1 & H2 and Signal contact S1 & S2 AC 277 V 6 A Hilfskontakt H1 & H2 und DC 125 V 1 A Signalkontakt S1 & S2 DC 50 V 6 A Functional auxiliary contact module Type H1 (assumes the same contact position) Actuation of the contact is determined Type H2 (assumes the opposite position) by the condition of the handle position of the adjacent poles. Funktion Hilfskontakt Typ H1 (gleichschaltend) Hilfskontakte schalten bei thermisch- Typ H2 (gegenschaltend) magnetischer Auslösung sowie Handbetätigung synchron mit den geschützten Polen. Functional signal contact Type S1 (assumes the same contact position) The signal contact operates due to a Type S2 (assumes the opposite position) thermal magnetic tripping and must be reset by hand. Funktion Signalkontakt Typ S1 (gleichschaltend) Signalkontakte schalten nur bei Typ S2 (gegenschaltend) thermisch-magnetischer Auslösung und sind von Hand zurückzustellen. Relay trip module Type Voltage range AC/DC Impedance at 50 Hz Fremdauslösung Typ Arbeitsbereich AC/DC Impedanz bei 50 Hz A1 5 – 12 V 1.1 Ω A2 10 – 24 V 4.7 Ω A3 20 – 48 V 16 Ω A4 40 – 110 V 63 Ω A5 90 – 240 V 395 Ω Function of relay trip module When voltage is applied across the terminals, remote tripping takes place by a self interrupting magnetic system. Trip delay time 8 - 16 ms. Funktion Fremdauslösung Beim Anlegen der Klemmenspannung erfolgt die Auslösung durch ein selbstunterbrechendes Magnetsystem. Ausschaltverzögerung 8 – 16 ms. General data / Allgemeine Daten: Dielectric strength AC 2000 V Spannungsfestigkeit AC 2000 V Vibration resistance IEC 60068-2-6, Test Fc 0,75 mm amplitude, 10 – 57 Hz Schwingungsfestigkeit 0,75 mm Amplitude, 10 – 57 Hz Shock resistance / Stossfestigkeit IEC 60068-2-27, Test Ea 25 g / 10 ms Halfsinus Protection against electric shock Finger safe per IEC 529 IP20 Berührungsschutz Fingerschutz nach IEC 529 IP20 Permissible ambient temperature -20°C to +60°C Zul. Umgebungstemperatur -20°C bis +60°C Weight / Gewichte 1 pole / 1-Pol ca. 130 g Switched neutral / Schaltbarer neutraler Pol ca. 130 g Auxiliary contact / Hilfskontakt ca. 100 g Signal contact / Signalkontakt ca. 100 g Relay trip module / Fremdauslösung ca. 120 g MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERÄTESCHUTZSCHALTER AS168X

MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERÄTESCHUTZSCHALTER AS168X Approvals / Approbationen www.schurter.com 127 VDE UL UL EN 60934 * UL 1077 CSA 22.2 235 UL 508 ** CSA 22.2 14 Poles Characteristic/ Nennstrom [A] Volt AC Volt DC Icn [A] Volt AC Volt DC Icn [A] Volt AC Icn [A]

1 F / G / H

420/240 65 4500 277 65 5000 277 5000 F / G 0.5 - 25 420/240 65 4500 277 240 65 5000 10000 277 5000 H 0.5 - 40 420/240 65 4500 277 65 5000 277 5000 F / G 27 - 40 420/240 65 4500 277 240 65 5000 10000 277 5000

2 F / G / H

420 65 4500 480 65 5000 480 5000 F / G 0.5 - 25 420 65 4500 480 65 10000 480 5000 H 0.5 - 40 420 65 4500 480 65 5000 480 5000 F / G 27 - 40 420 65 4500 480 65 10000 480 5000

3 F / G / H

420 65 4500 480Y/277 65 5000 480 5000 F / G 0.5 - 25 420 65 4500 480Y/277 65 10000 480 5000 H 0.5 - 40 420 65 4500 480Y/277 65 5000 480 5000 F / G 27 - 40 420 65 4500 480Y/277 65 10000 480 5000

4 F / G / H

0.5 - 52 420/240 65 4500 480Y/277 65 5000 480Y/277 5000 VDE * UL EN 60934 UL 1077 CSA 22.2 235 Poles Characteristic/ Nennstrom [A] Volt DC Icn [A] Volt DC Icn [A]

1 DF / DG

0.5 - 50 120 4500 180 2000 DH 6 - 50 120 4500 180 2000

2 DF / DG

0.5 - 50 240 4500 360 2000 DH 6 - 50 240 4500 360 2000

3 DF / DG

0.5 - 40 360 4500 360 10000 DF / DG 45 - 50 360 4500 360 5000 DH 6 - 50 360 4500 360 5000

4 DF / DG

0.5 - 40 360 4500 360 10000 DF / DG 45 - 50 360 4500 360 5000 DH 6 - 50 360 4500 360 5000 AC versions / AC-Versionen DC versions / DC-Versionen * VDE approval pending / VDE Zulassung pendent ** Rated currents 32–52 A available approx. March 2003 / Nennwerte 32–52 A ca. ab März 2003 lieferbar EVD EVD

www.schurter.com128 MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERÄTESCHUTZSCHALTER AS168X Conversion table Ampere rating – Horsepower rating / Umrechnungstabelle Ampère – Horsepower HORSEPOWER (FLA & LRC RATINGS APPLY WHERE NO HP RATING IS GIVEN) NOMINAL CIRCUIT VOLTAGE, VacAS168X-CB MOTOR NAMEPLATE 110- 120 200 208 220- 240 265 277 380- 415 440- 480 Rated Current (See Note #1) FLA Rating Starting/ LRC Rating pole 2 pole 0.5A 0.5A 3 ° 1A 1A 6 ° 1/10 1.5A 1.5A 9 ° 1/10 1/10 1/10 1/6 2A 2A 12A 1/8 1/6 1/6 1/4 3A 3A 18A 1/10 1/6 1/6 1/4 1/4 1/3 1/3 1/2 4A 4A 24A 1/8 1/4 1/3 1/3 1/3 1/3 1/2 1 5A 5A 30A 1/6 1/3 1/3 1/2 1/2 1/2 3/4 1 1/2 6A 6A 36A 1/4 1/2 1/2 1/2 3/4 3/4 1 2 7A 7A 42A 1/4 1/2 1/2 3/4 1 1 1 1/2 2 8A 8A 48A 1/3 3/4 3/4 1 1 1 2 2 9A 9A 54A 1/3 3/4 1 1 1 _ 1 1/2 2 3 10A 10A 60A 1/2 1 1 1 1/2 1 1/2 2 2 3 12A 12A 72A 1/2 1 1/2 1 1/2 2 2 2 3 3 13A 13A 78A 1/2 1 1/2 1 1/2 2 2 2 3 3 15A 15A 90A 3/4 2 2 2 3 3 3 5 16A 16A 96A 1 2 2 2 3 3 3 5 18A 18A 108A 1 2 2 3 3 3 5 5 20A 20A 120A 1 1/2 3 3 3 3 3 5 5 23A 23A 138A 1 1/2 3 3 3 3 3 5 7 1/2 25A 25A 150A 2 3 3 3 5 5 5 7 1/2 27A 27A 162A 2 3 3 3 5 5 7 1/2 10 30A 30A 180A 2 3 3 5 5 5 7 1/2 10 HORSEPOWER (FLA & LRC RATINGS APPLY WHERE NO HP RATING IS GIVEN)AS168X-CB MOTOR NAMEPLATE NOMINAL CIRCUIT VOLTAGE, VAC 110-120 200 208 220-240 380-415 440-480 Rated Current (See Note #1) FLA Rating Starting/ LRC Rating 3 pole 0.5A 0.5A 1A 1A 1.5A 1.5A 10A 1/2 1/2 2A 2A 12.5A 3/4 3/4 3A 3A 20A 1/2 1/2 1/2 1 1 1/2 4A 4A 25A 3/4 3/4 3/4 1 1/2 2 5A 5A 32A 1/2 1 1 1 2 3 6A 6A 32A 1/2 1 1 1 1/2 2 3 7A 7A 32A 3/4 1 1/2 1 1/2 2 3 3 8A 8A 46A 3/4 2 2 2 3 5 9A 9A 46A 1 2 2 2 3 5 10A 10A 46A 1 2 2 3 5 5 12A 12A 63.5A 1 1/2 3 3 3 5 7 1/2 13A 13A 63.5A 1 1/2 3 3 3 5 7 1/2 15A 15A 81A 2 3 3 3 7 1/2 10 16A 16A 81A 2 3 3 5 7 1/2 10 18A 18A 81A 2 5 5 5 10 10 20A 20A 81A 3 5 5 5 10 10 23A 23A 116A 3 5 5 7 1/2 10 15 25A 25A 116A 3 5 7 1/2 7 1/2 10 15 27A 27A 145A 3 7 1/2 7 1/2 7 1/2 15 20 30A 30A 145A 3 7 1/2 7 1/2 10 15 20 HP-Rating: 1 phase (1 pole & 2 pole): Note #1: For AC motor circuit nameplate FLA loads, AC general-use loads, AC resistance loads Voltage Rating: One pole: AC 277 V, 1 phase Two pole: AC 480Y/277 V, 1 phase Three pole: AC 480Y/277 V, 3 phase HP-Rating: 3 phase (3 pole):

www.schurter.com 129 Order code / Bestellcode Basic type / Grundtyp Thermal magnetic high performance circuit breaker Thermisch-magnetischer Hochleistungs-Geräteschutzschalter Number of poles / Polzahl Tripping characteristics / Auslösekennlinien Thermal Magnetic Deliverable currents Thermisch Magnetisch Lieferbare Nennströme F 1.0 –1.25 xIn 3 – 5 xIn 0,5 – 52 A G 1.0 –1.25 xIn 6 – 10 xIn 0,5 – 52 A H 1.0 –1.25 xIn 12 – 20 xIn 0,5 – 52 A DF 1.05 –1.35 xIn 4,5 – 8 xIn 0,5 – 50 A DG 1.05 –1.35 xIn 9 – 16 xIn 0,5 – 50 A DH 1.05 –1.35 xIn 18 – 32 xIn 6,0 – 50 A Rated current / Nennstrom Switched neutral pole / Schaltbarer neutraler Pol N Auxiliary contact / Hilfskontakt H1 Assumes the same contact position as the protected poles Gleiche Kontaktposition wie die geschützten Pole (gleichschaltend) H2 Assumes the opposite contact position as the protected poles Entgegengesetzte Kontaktposition wie die geschützten Pole (gegenschaltend) Signal contact / Signalkontakt S1 Assumes the same contact position as the protected poles Gleiche Kontaktposition wie die geschützten Pole (gleichschaltend) S2 Assumes the opposite contact position as the protected poles Entgegengesetzte Kontaktposition wie die geschützten Pole (gegenschaltend) Relay trip module / Fremdauslösung A1 AC/DC 5 – 12 V A2 AC/DC 10 – 24 V A3 AC/DC 20 – 48 V A4 AC/DC 40 – 110 V A5 AC/DC 90 – 240 V Accessories / Zubehör Must be ordered separately / muss separat bestellt werden

2 DG 200 NAS168X – CB

S2AS168X – ACB Code I n (A) 060 6.0 070 7.0 080 8.0 090 9.0 100 10.0 120 12.0 150 15.0 Code I n (A) 005 0.5 010 1.0 015 1.5 020 2.0 030 3.0 040 4.0 050 5.0 Code I n (A) 160 16.0 180 18.0 200 20.0 230 23.0 250 25.0 270 27.0 300 30.0 Code I n (A) 320 32.0 350 35.0 400 40.0 450 45.0 500 50.0 520 52.0* Maximum combination Maximale Kombinationen

1 Add-on module +

1 Zusatzmodul +

N N 4 poles +

4 Pole +

2 Add-on modules +

2 Zusatzmodule +

N N 3 poles +

3 Pole +

MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERÄTESCHUTZSCHALTER AS168X * AC version only / Nur AC-Version

www.schurter.com130 MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERÄTESCHUTZSCHALTER AS168X DIN rail mounting / Hutschiene DIN-Befestigung AS168X-CB1… …N 1.9 44.4 61.6 68.4 5.1 26.6 17.5 +0.5 – 0.0 26.6 17.5 +0.5 – 0.0 35 mm DIN rail EN 50022 35 mm Hutschiene DIN-EN 50022 Wire crosssection Max. torque Drahtquerschnitt Max. Drehmoment 1.5…10 mm 2 2.5 Nm 16 …25 mm 2 3.1 Nm AWG #16...8 22 Ib–in AWG #6...4 28 Ib–in Max. torque Max. zulässiges Anzugsdrehmoment AS168X-ACBH. AS168X-ACBS. AS168X-ACBA. 17.5 +0.5 – 0.0 17.5 +0.5 – 0.0 17.5 +0.5 – 0.0

Accessories / Zubehör AS168X-ACBLOA Lockout attachment / Abschliessverriegelung Schematic diagrams / Schaltbilder AS168X-CB1… AS168X-ACBH2 AS168X-CB1… AS168X-ACBH1 AS168X-CB1…NAS168X-CB1… AS168X-CB1… AS168X-ACBS1 AS168X-CB1… AS168X-ACBS2 AS168X-CB1… AS168X-ACBA. MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERÄTESCHUTZSCHALTER AS168X www.schurter.com 131