Features
– Straight version – 1 IO-Link interface – 1 analog input for connecting resistance temperature detectors (RTDs) – Connection of the sensor in 3-wire technology – IO-Link and sensor connections via M12 connectors – FE connection for local connection to functional earth ground – Supply of the module electr onics and the sensor via the IO-Link interface of the IO-Link master – Diagnostic indicator Make sure you always use the latest documentation. It can be downloaded from the product at phoenixcontact.net/products. 8597_en_07 2015-04-28
8597_en_07 PHOENIX CONTACT 2 2T a b l e o f c o n t e n t s
8597_en_07 PHOENIX CONTACT 3 Description Type Order No. Pcs. / Pkt. Axioline E-IO-Link/analog converter for connecting a temperature mea- surement resistor, M12 fast connection technology, straight version AXL E IOL RTD1 M12 S 2700352 1 3O r d e r i n g d a t a Dimensions (nominal sizes in mm) Width 16.6 mm Height 29 mm Depth 79.5 mm
4 Technical data
50 16,5 79,5 2829 16,6 General data Weight 34 g Ambient temperature (operation) -25 °C ... 60 °C Ambient temperature (storage/transport) -25 °C ... 85 °C Permissible humidity (operation) 5 % ... 95 % Permissible humidity (storage/transport) 5 % ... 95 % Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level) Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level) Degree of protection IP65/67 Protection class III, IEC 61140, EN 61140, VDE 0140-1 Pollution degree 2 IO-Link Specification V1.1.1 Protection against polarity reversal Yes Transmission speed 230,4 kBit/s (COM3) Frame type 1 Cycle Time min. 2 ms Process data update 2 ms Amount of process data 16 Bit (Input data) IO-Link ports Number of ports 1 Connection method M12 connector, A-coded
8597_en_07 PHOENIX CONTACT 4 IO-Link port supply Typical current consumption 16.5 mA ±15% (at 24 V DC) Current consumption max. 25 mA Protection against polarity reversal Yes Short-circuit protection Yes Overload protection Yes I/O supply voltage 24 V DC This supply voltage is provided via the IO-Link interface of the IO-Link master. Analog RTD inputs Number of inputs 1 (for resistance temperature detectors) Connection method M12 connector, A-coded Connection method 3-wire (optionally 4-wire) Sensor types (RTD) that can be used Pt 100, Pt 1000 Resolution A/D 12 bit Data formats IB IL, S7-compatible Relative accuracy < 0.3 % (From the measuring range final value in the nominal range) Permissible cable length max. 30 m (Shielded cable) Protection against polarity reversal yes Short-circuit protection yes Overload protection yes Error messages to the higher level control or computer system Overrange or underrange Message in the diagnostic code (in the IB IL format) Measured value invalid/no valid measured value present Message in the diagnostic code (in the IB IL format) Configuration invalid Message in the diagnostic code (in the IB IL format) Module faulty Message in the diagnostic code (in the IB IL format) Mechanical tests Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 Operation: 2g Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 Storage/transport: 5g Shock in acc. with EN 60068-2-27/IEC 60068-2-27 Operation: 30g, 11 ms, three shocks in each space direction Shock in acc. with EN 60068-2-27/IEC 60068-2-27 Storage/transport: 50g, 11 ms, three shocks in each space direction Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g, 16 ms, 1000 shocks, in all space directions Approvals For the latest approvals, please visit phoenixcontact.net/products.
8597_en_07 PHOENIX CONTACT 5
5 Additional tables
The data is valid for nominal operation (supply volt- age = 24 V) in the default configuration. The tolerance values refer to the measuring range final value.
6 Internal circuit diagram
Figure 1 Internal wiring of connections Key: Tolerance and temperature response at TA = -25°C to +60°C Sensor type Measuring range Drift Lower limit Upper limit Typical Maxi- mum Pt 100 DIN -200 °C +850 °C ±5 ppm/K ±95 ppm/K Pt 1000 SAMA -200 °C +850 °C ±20 ppm/K ±95 ppm/K Linear resis- tor RLin 500 Ω (linear range 1) 0 Ω 500 Ω ±5 ppm/K ±95 ppm/K Linear resis- tor RLin 5000 Ω (linear range 2) 0 Ω 5000 Ω ±34 ppm/K ±95 ppm/K Tolerances influenced by electromagnetic interfer- ence Type of electro- magnetic inter- ference Standard Toler- ance Criterion Electromagnetic fields EN 61000-4-3/ IEC 61000-4-3 < ±1.5% A Fast transients (burst) EN 61000-4-4/ IEC 61000-4-4 < ±0.5% A Conducted interference EN 61000-4-6/ IEC 61000-4-6 < ±1.0% A Protective circuit IO-Link circuit Microprocessor Analog/digital converter Protection µC C/Q L- FE FE IO-Link IC Protection
3 AnalogIO-Link
µC
8597_en_07 PHOENIX CONTACT 6
7 Pin assignment
7.1 Connections on the device
Figure 2 Connections on the converter
7.2 Pin assignment of the IO-Link interface
Figure 3 Pin assignment of the I/O link interface (M12 A-coded, pin)
7.3 Pin assignment of the analog input
Figure 4 Pin assignment of the analog input (M12 A-coded, socket)
8 Connection notes
Always connect the analog sensors using shielded, twisted pair cables.
9 Connection example
Figure 5 Connection example No. Connection 1I O - L i n k i n t e r f a c e (indicated by IO-Link symbol)
2 Fixing options;
options for connection to functional earth ground
3 Analog input
1L + + 2 4 V supply voltage; from IO-Link master 2- N o t u s e d
3 L- GND, reference potential for L+
4 C/Q IO-Link data transmission channel
1 U+ RTD sensor +
2 I+ Constant current supply +
3 U- RTD sensor -
4 I- Constant current supply -
8597_en_07 PHOENIX CONTACT 7
10 Assembly
Figure 6 Connection of a sensor to an IO-Link master via the converter
- Connect the IO-Link interface of the converter to an IO- Link port of the higher-level IO-Link master using a stan- dardized 3-pos. cable.
- Connect the analog sensor directly to the analog con- verter input or using a shielded 4-pos. cable.
- Fasten each connection using the M12 connectors.
11 Local status indicator
Figure 7 Local status indicator In environments with high levels of interfer- ence, in particular, Phoenix Contact recom- mends connecting the converter to an appropriate functional earth ground point using an M4 screw. Desig- nation Color Mean- ing State Description COM Green Status of IO- Link de- vice ON Supply voltage OK Flashing Supply voltage OK, SDCI communica- tion active OFF No supply voltage, no communication COM
8597_en_07 PHOENIX CONTACT 8
12 Process data
The device occupies one word of IN process data and one word of OUT process data.
12.1 IN process data
The measured values are depicted in IB IL or S7-compatible format. A diagnostic code is mapped to the input data in the event of an error. IB IL format Values > 8000hex and < 8100hex indicate an error. S7-compatible format In the format S7-compatible exsist two diagnostic codes, see the following table. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 V Analog value V Sign bit (= 0, not relevant) By some formats bit 2 ... bit 0 are not relevant for the measured value. They are set to 0. Code (hex) Cause
8001 Overrange
8002 Wire break
8003 Short-circuit
8004 Measured value invalid/no valid measured
8040 Device faulty
8080 Underrange
Code (hex) Cause 7FFF Overrange
8000 Wire break/short-circuit/underrange
8597_en_07 PHOENIX CONTACT 9
12.2 OUT process data
The device can be configured via the process data output word. The following configurations are possible: – Selection of the sensor type – Selection of formats for re presenting measured values – Adjusting the resolution
12.3 Parameterization via OUT process data
Reparameterization can be carried out via the output pro- cess data, however this is not saved permanently on the de- vice. The following sequence applies regardless of the format ( IB IL or S7-compatible): – The master sends parameter data (OutputProcessData with bit 15 = 1) – The device interrupts the transmission of current pro- cess data and responds with the following diagnostic code in the process data: – If the diagnostic code is OK, the parameter data is ac- cepted immediately. The master can end parameteriza- tion (OutputProcessData with bit 15 = 0). The device returns to normal operation with cyclic process data transmission. – In the event of the ERROR di agnostic code, the master can abort parameterization without modified parameter data (OutputProcessData with bit 15 = 0) or transmit the modified parameterization (return to step 1).
12.4 Example
The example applies to the following changes: – Adjusting the resolution from 0.1 °C to 0.1 °F – Selection of formats S7-compatible (Default) to IB IL – Selection of the Sensor type Pt 100 DIN (Default) to Linear R 0 Ω ... 500 Ω 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Configuration Reserved Resolution Format Sensor type For the exact meaning of the individual bits, please refer to “Parameterization (80hex: ParaWord)”. Please operate the reparameterization only by the startup of the device! In order to start configuration, bit 15 of the out- put word must be set to 1. If bit 15 = 0, the de- fault configuration is active. Code (hex) Cause
8800 Parameter OK
8801 Parameter ERROR
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Configuration Reserved Resolution Format Sensor type
1 R e s e r v e d 10101110
8597_en_07 PHOENIX CONTACT 10
13 Significant values in various formats
13.1 IB IL format
13.2 S7-compatible format
Resolution 0.1 Ω 1 Ω 0.1 °C * 0.1 °F * hex dec Ω Ω °C °F
8003 Short-circuit no (0 Ω)n o ( 0 Ω)y e s y e s
8002 Wire break yes yes yes yes
8001 Overrange > 525 > 5250 > 850 >1562
1482 5250 525 5250 525 525 03E8 1000 100 1000 100 100 0032 50 5 50 5 5 0005 5 0.5 5 0.5 0.5 0001 1 0.1 1 - - 0000 0 0 0 0 0 FC18 -1000 - - -100 -100 F830 -2000 - - -200 -200 F330 -3280 - - - -328
8080 Underrange - - < -200 < -328
Resolution 0.17 Ω 1.7 Ω 0.1 °C * 0.1 °F * hex dec Ω Ω °C °F
8000 Short-circuit no (0 Ω)n o ( 0 Ω)y e s y e s
8000 Wire break yes yes yes yes
7FFF Overrange > 705.4 > 7054 > 850 > 1562 7EF8 32504 705.4 7054 - - 3D04 15620 339 3390 - 1562 2134 8500 184.5 1845 850 850 03E8 1000 21.7 217 100 100 0032 50 1.1 11 50 50 0008 8 0.17 1.7 - - 0005 5 - - 0.5 0.5 0000 0 0 0 0 0 FC18 -1000 - - -100 -100 F830 -2000 - - -200 -200
8000 Underrange - - < -200 < -328
- The format representation is based on 0.1 °C/F. The actual resolution is 0.5 °C/F. The measurement is thus always in 0.5 °C/F increments (steps).
8597_en_07 PHOENIX CONTACT 11
14 IO-Link objects
14.1 Overview of the objects
Index (hex) Object name Length in bytes Access Meaning Contents DPP ISDU Identification
07 Vendor ID 2 R Manufacturer identifica-
08 B0hex
09 Device ID 3 R Device ID 01 hex
10 VendorName Max. 64 R Manufacturer name Phoenix Contact 11 VendorText Max. 64 R Notes www.phoenixcontact.com 12 ProductName Max. 64 R Product designation AXL E IOL RTD1 M12 S 13 Product ID Max. 64 R Order No. 2700352 14 ProductText Max. 64 R Product text IO-Link/Analog-Converter Temperature RTD Input Straight 15 Serial number Max. 16 R Serial numb er Stored in the production pro- cess. 16 HardwareVersion Max. 64 R Hardware version E.g., 01 17 FirmwareVersion Max. 64 R Firmware version E.g., 001 Diagnostics
20 Error count 2 R Errors since power up Number of errors
28 InputProcessData 2 R Input process data Last current data
80 ParaWord 2 R/W Parameterization 0000
8597_en_07 12PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany phoenixcontact.com
14.2 Parameterization (80 hex: ParaWord)
Parameterize the device using this object. In the case of valid parameters, the parameterization is permanently stored on the device. After a reset, the device operates with the last permanently stored data. Upon delivery, the device operates with the default data (default settings). In the following tables the values in bold are default settings. Saving data to the device leads to a communication failure of around 30 ms. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Reserved Resolution for sensor type Format Sensor type Sensor type Code (bin) Meaning
0000 Pt 100 DIN
0001 Pt 1000 SAMA
1110 IB IL format:
Linear R 0 Ω ... 500 Ω S7-compatible format: Linear R 0 Ω ... 600 Ω
1111 IB IL format:
Linear R 0 Ω ... 5 kΩ S7-compatible format Linear R 0 Ω ... 6 kΩ Other Reserved Format Code (bin) Meaning
00 S7-compatible
10 IB IL
Resolution for sensor type 00 0.1 °C (0.5 °C increments) IB IL format: 0,1 Ω S7-compatible format: 0,17 Ω Format IB IL: 1,0 Ω Format S7-kompatibel: 1,7 Ω 10 0.1 °F (0.5 °F increments) Reserved Reserved Other Reserved