Technical content

Features

– Two relay outputs – Floating connections for 2 actuators – Nominal current of each output: 2 A – Total current of the terminal: 4 A – Segment voltage U S connected – Diagnostic and status indicators – Can be used under extreme ambient conditions – Extended temperature range of -40°C ... +70°C (see “Tested successfully: use under extreme ambient conditions”) –P a i n t e d P C B s WARNING: Undefined system state By default, the position of the relay contacts on the module is not defined. To prevent undesired system states, perform a complete cycle (on/off) before connecting the segment voltage. This data sheet is only valid in association with the IL SYS INST UM E user manual. Make sure you always use the latest documentation. It can be downloaded from the product at phoenixcontact.net/products. 8463_en_01 2015-08-12

IB IL 24/48 DOR 2/W-XC-PAC 8463_en_01 PHOENIX CONTACT 2 2T a b l e o f c o n t e n t s

IB IL 24/48 DOR 2/W-XC-PAC 8463_en_01 PHOENIX CONTACT 3 Description Type Order No. Pcs./Pkt. Inline digital output terminal, version for extreme conditions, complete with accessories (connector plug and labeling field), 2 relay PDTs, gold con- tact, 5 - 48 V DC, 2 A IB IL 24/48 DOR 2/W-XC-PAC 2701214 1 3O r d e r i n g d a t a Accessories Type Order No. Pcs./Pkt. Labeling field, width: 12.2 mm (Marking) IB IL FIELD 2 2727501 10 Insert strip, Sheet, white, unlabeled, can be labeled with: Office printing systems, Plotter: Laser printer, Mounting type: Insert, Lettering field: 62 x 10 mm (Marking) ESL 62X10 0809492 1 Connector, for digital 1, 2 or 8-channel Inline terminals (Connector/ Adapter) IB IL SCN-8 2726337 10 Zack Marker strip, flat, Strip, white, unlabeled, can be labeled with: Plotter, Mounting type: Snap into flat marker groove, for terminal block width: 6.2 mm, Lettering field: 5.15 x 6.15 mm (Marking) ZBF 6:UNBEDRUCKT 0808710 10 Zack Marker strip, flat, white, for terminal block width: 6.2 mm (Marking) ZBF 6:SO/CMS 0808778 1 Flat zack marker sheet, white, for terminal block width: 6.2 mm (Marking) ZBFM 6:SO/CMS 0803650 1 Flat zack marker sheet, Sheet, white, unlabeled, can be labeled with: Plot- ter, Mounting type: Snap into flat marker groove, for terminal block width: 6.2 mm, Lettering field: 5 x 5.5 mm (Marking) ZBFM 6/WH:UNBEDRUCKT 0803618 10 Inline distance terminal, complete with accessories IB IL DOR LV-SET-PAC 2861645 1 Documentation Type Order No. Pcs./Pkt. Application note, English, The safety-related segment circuit AH EN IL SAFE - - Data sheet, English, INTERBUS addressing DB GB IBS SYS ADDRESS - - Application note, English, Using distance terminal blocks and interference suppression measures on inductive loads AH EN IB IL DOR - - Dimensions (nominal sizes in mm) Width 12.2 mm Height 119.8 mm Depth 71.5 mm Note on dimensions Housing dimensions

4 Technical data

140,5 119,8 71,5

IB IL 24/48 DOR 2/W-XC-PAC 8463_en_01 PHOENIX CONTACT 4 General data Color green Weight 63 g (with connector) Operating mode Process data mode with 2 bits Ambient temperature (operation) -25 °C ... 55 °C (Standard) -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) Ambient temperature (storage/transport) -40 °C ... 85 °C Permissible humidity (operation) 10 % ... 95 % (according to DIN EN 61131-2) Permissible humidity (storage/transport) 10 % ... 95 % (according to DIN EN 61131-2) Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level) Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level) Degree of protection IP20 Protection class III, IEC 61140, EN 61140, VDE 0140-1 Connection data Designation Inline connector Connection method Spring-cage connection Conductor cross section [AWG] 28 ... 16 Stripping length 8 mm Interface Inline local bus Connection method Inline data jumper Transmission speed 500 kBit/s Power consumption Communications power UL 7.5 V DC Current consumption from UL max. 30 mA Power consumption 0.23 W (at U L) Relay output Number of outputs 2 Connection method Spring-cage connection Connection method Floating SPDT relay contact Nominal output voltage 48 V DC Output voltage range 5 V AC ... 30 V AC 5 V DC ... 60 V DC Maximum output current per channel 2 A Contact type 2 floating PDT contacts Contact material AgSnO2, hard gold-plated Contact resistance 75 m Ω Switching voltage min. 10 mV (DC) max. 30 V AC (PELV (EN 61131)) max. 60 V DC (PELV (EN 61131)) Switching current min. 10 µA

2 A (30 V DC)

1 A (60 V DC)

Limiting continuous current 2 A (at maximum ambient temperature) Switching capacity 60 W

62.5 VA (ohmic)

Switching frequency 1 Hz (without load) ; 1 Hz (with load) Nominal power consumption 200 mW

IB IL 24/48 DOR 2/W-XC-PAC 8463_en_01 PHOENIX CONTACT 5 Coil resistance 178 Ω ±10 % (at 20 °C) Typical response time typ. 20 ms Bouncing time 4 ms (for on and off) Typical release time typ. 20 ms Service life, electrical 108 cycles Mechanical service life 2x 10 5 cycles Common potentials all contacts floating Relay output Programming data (INTERBUS, local bus) ID code (hex) BD ID code (dec.) 189 Length code (hex) 2C Length code (dec.) 44 Process data channel 2 Bit Input address area 0 Bit Output address area 2 Bit Parameter channel (PCP) 0 Bit Register length (bus) 2 Bit For the programming data/configuration data of other bus systems, please refer to the corresponding electronic device data sheet (e.g., GSD, EDS). Configuration and parameter data in a PROFIBUS system Required parameter data 3 Byte Need for configuration data 4 Byte Error messages to the higher level control or computer system None Electrical isolation/isolation of the voltage areas Test section Test voltage Relay contact / Bus logics 1.5 kV, 50 Hz, 1 min Contact/contact 1 kV, 50 Hz, 1 min Contact / PE 1 kV, 50 Hz, 1 min To achieve electrical isolation between the logic level and the I/O area, supply these areas from separate power supply units. Interconnection of the power supply units in the 24 V area is not permitted (see also user manual). Approvals For the latest approvals, please visit phoenixcontact.net/products.

IB IL 24/48 DOR 2/W-XC-PAC 8463_en_01 PHOENIX CONTACT 6

5 Additional tables

5.1 Maximum switching current for ohmic load de-

pending on the switching voltage Load current IL as a function of the switching voltage US Figure 1 Load current I L as a function of the switching voltage US

1 DC, ohmic load

2 AC, ohmic load

Number of operations N as a function of the load cur- rent IL Figure 2 Number of operations N as a function of the load current IL 1 30 V DC, ohmic load 2 125 V AC, ohmic load

5.2 Power dissipation

Formula for calculating the power dissipation of the electronics Power dissipation of the housing Switching voltage (V DC) Switching current (A) 10 2.0 20 2.0 30 2.0 60 1.0 0,1 1,0 2,0 10 100 200 3,0 IL A US V30 0,3 100 1,0 2,0 N IL A x10 Where: PEL Total power dissipation in the terminal i Continuous index n Number of set outputs (n = 1 ... 2) m Number of relays with controlled coil I Li Load current of output i PHOU = 1.2 W -25°C ≤ TA < +25°C PHOU = 1.2 W - [(TA - 25°C) x 0.02 W/°C] +25°C < TA ≤ +55°C Where: PHOU Power dissipation of the housing TA Ambient temperature P = 0,23 W + m x 0,14W + (I x 0,075)EL Li ∑ nn i = 1i = 1

IB IL 24/48 DOR 2/W-XC-PAC 8463_en_01 PHOENIX CONTACT 7

5.3 Limitation of simultaneity, derating

5.4 Air clearances and creepage distances

Derating when using the N/O contact Ambient temperature Tamb Power dissipation of the housing Maximum load current 100 % simultaneity 50 % simultaneity ≤ 40°C 0.9 W 2.0 A 2.0 A ≤ 55 °C 0.6 W 1.0 A 2.0 A Air clearances and creepage distances (according to EN 50178, VDE 0109, VDE 0110) Isolating distance Clearance Creepage distance Test voltage Relay contact/bus logic ≥ 1.5 mm ≥ 1.5 mm 1.5 kV, 50 Hz, 1 min. Contact/contact ≥ 1.5 mm ≥ 1.5 mm 1.0 kV, 50 Hz, 1 min. Contact/PE ≥ 3.1 mm ≥ 3.1 mm 1.5 kV, 50 Hz, 1 min. Relay/relay None

IB IL 24/48 DOR 2/W-XC-PAC 8463_en_01 PHOENIX CONTACT 8

6 Tested successfully: Use under ex-

XC terminals have been tested successfully over 250 tem- perature change cycles in accordance with IEC 61131-2 in the range from -40°C to +70°C. The following conditions were observed: – The Inline devices for all connecting cables were con- nected with a minimum conductor cross section of 0.5 mm² – The Inline station was a ssembled on a wall-mounted horizontal DIN rail – Fans were used to ensure continuous movement of air in the control cabinet – The Inline station was not exposed to vibration or shock – The Inline station was oper ated with a maximum of

24.5 V (ensured by using regulated power supply units)

Figure 3 Temperature change cycle Temperature in the control cabinet/ambient temperature Cycle WARNING: The terminal is not approved for use in poten- tially explosive areas. The terminal is not approved for use in safety technology. 3 h + 30 min 3 h + 30 min (3 0,6) K/min+

3 K+Tmin

2 K+Tmax

IB IL 24/48 DOR 2/W-XC-PAC 8463_en_01 PHOENIX CONTACT 9

7 Internal circuit diagram

Figure 4 Internal wiring of the terminal points Key:

8 Special features of the terminal

8.1 Switching a voltage eq ual to the segment volt-

The potential US is available at terminal points 1.1 and 1.2. If you insert a jumper between 1.1 and 1.3 or 2.1 and 2.3, you connect the segment voltage potential to the main con- tact of the relevant relay and can therefore switch the con- nected load in a non-isolated manner. If you do not insert a jumper, you can switch the load in a floating manner.

8.2 Switching a voltage unequal to the segment

Distance terminals are not required. Only floating switching of the load is permitted. Do not, therefore, attach any jumpers to the connector. Switching an AC voltage within a DC segment circuit Place distance terminals in front of and behind the relay ter- minal block. The distance terminals interrupt the potential jumpers. As a result, no segment voltage is present at terminal points 1.1 and 2.1. It is only possible to switch the connected load in a floating manner. Protocol chip (Bus logic including voltage conditioning) LED Relay Electrically isolated area I/O area including relay contact isolated from the logic area including the relay coil Explanation for other used symbols has been provided in the IL SYS INST UM E user man- ual. /G4C /G6F /G63 /G61 /G6C /G20 /G62 /G75 /G73 /G55 /G4C /G4F /G50 /G43 /G36 /G38 /G35 /G30 /G31 /G30 /G30 /G33 /G55 /G4D /G55 /G53 OPC See also the information in the AH EN IB IL DOR application note. If the switch contact potentials and the seg- ment circuit potential are two different DC cir- cuits, Phoenix Contact recommends establishing a ground connection between the two power supply units.

IB IL 24/48 DOR 2/W-XC-PAC 8463_en_01 PHOENIX CONTACT 10

9 Local status and diagnostic indica-

Figure 5 Local status and diagnostic indicators Function identification Pink Housing/connector color Green housing Green, unprinted connector

10 Terminal point assignment

Figure 6 Terminal point assignment Designa- tion Color Meaning D Green Diagnostics (bus and logic volt- age) 1 ... 2 Yellow Status of the outputs (relay has picked up) D Terminal point Assignment 1.1 / 2.1 Segment voltage U S

1.2 Relay N/C contact Relay 1

1.3 Relay main contact Relay 1

1.4 Relay N/O contact Relay 1

2.2 Relay N/C contact Relay 2

2.3 Relay main contact Relay 2

2.4 Relay N/O contact Relay 2

1.1 2.1 1.2 2.2 1.3 2.3 1.4 2.4 1.1 1.2 1.3 1.4 2.1 2.3 2.4 2.2

IB IL 24/48 DOR 2/W-XC-PAC 8463_en_01 11PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany phoenixcontact.com

11 Connection notes and examples

Figure 7 Actuator connection; floating connection Figure 8 Actuator connection; non-isolated connection Figure 9 Output relay contacts

12 Process data

Assignment of the terminal points to the output pro- cess data The LED lights up if the corresponding N/O contact is closed. NOTE: Damage to the electronics Use the terminal within the PELV range (EN 61131) up to a maximum of 30 V AC or 60 V DC. 1.1 2.1 1.2 1.3 1.4 2.2 2.3 2.4 N/O contact N/C contact Main contact 1.1 2.1 1.2 1.3 1.4 2.2 2.3 2.4 1.2 1.4 1.3Hauptkontakt/ Main contact Öffnerkontakt/ N/C contact Schließerkontakt/ N/O contact (Byte.Bit) view 0.1 0.0 N/O contact 2 (contact 2.4) N/O contact 1 (contact 1.4) Possible bit combinations 0 0 open open 01o p e n c l o s e d 10c l o s e d o p e n 1 1 closed closed Status indicator LED 2 1 For the assignment of the illustrated (byte.bit) view to your INTERBUS control or computer system, please refer to the DB GB IBS SYS ADDRESS data sheet.