Technical content

Features

– Connections for eight digital actuators – Connection of actuators in 1-wire technology – Nominal current per output: 0.5 A – Total current of the terminal: 4 A – Short-circuit and overload protected outputs – Diagnostic and status indicators – Can be used under extreme ambient conditions –P a i n t e d P C B s – Extended temperature range T2 (-40°C  +55°C) This data sheet is only valid in association with the IL SYS INST UM E user manual. Make sure you always use the latest documentation. It can be downloaded from the product at www.phoenixcontact.net/catalog. 8462_en_00 2012-05-29

8462_en_00 PHOENIX CONTACT 2 2T a b l e o f c o n t e n t s

8462_en_00 PHOENIX CONTACT 3 Description Type Order No. Pcs. / Pkt. Inline digital output terminal, version for extreme conditions, complete with accessories (connector plug and labeling field), 8 outputs, 24 V DC, 500 mA, 1-wire connection technology IB IL 24 DO8/HD-XC-PAC 2701213 1 3O r d e r i n g d a t a Accessories Type Order No. Pcs. / Pkt. Connector, for digital 1, 2 or 8-channel Inline terminals ( Plug/Adapter ) IB IL SCN-8 2726337 10 Labeling field, width: 12.2 mm ( Marking ) IB IL FIELD 2 2727501 10 Documentation Type Order No. Pcs. / Pkt. User manual, English, Automation terminals of the Inline product range IL SYS INST UM E - - Data sheet, English, INTERBUS addressing DB GB IBS SYS ADDRESS - - Dimensions (nominal sizes in mm) Width 12.2 mm Height 119.8 mm Depth 71.5 mm Note on dimensions Housing dimensions

4 Technical data

140,5 119,8 71,5 General data Color green Weight 60 g ( With connector ) Operating mode Process data mode with one byte Ambient temperature (operation) -40 °C ... 55 °C (See also the "Tested successfully: Use under extreme ambient conditions" section of the data sheet.) Ambient temperature (operation) -40 °C ... 60 °C (At U S < 24.5 V; see also the "Tested successfully: Use under ex- treme ambient conditions" section of the data sheet.) Ambient temperature (storage/transport) -40 °C ... 85 °C Temperature class T2 (-40°C ... 55°C, EN 50155) Permissible humidity (operation) 10 % ... 95 % (according to DIN EN 61131-2) Permissible humidity (storage/transport) 10 % ... 95 % (according to DIN EN 61131-2) Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)

8462_en_00 PHOENIX CONTACT 4 Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level) Degree of protection IP20 Protection class III, IEC 61140, EN 61140, VDE 0140-1 General data Connection data Name Inline connectors Connection method Spring-cage connection Conductor cross section [AWG] 28 ... 16 Interface Inline local bus Connection method Inline data jumper Transmission speed 500 kBit/s Power consumption Segment supply voltage US 24 V DC (nominal value) Current consumption from US max. 4 A DC Communications power UL 7.5 V DC Current consumption from UL max. 45 mA Power loss max. 0.62 W Digital outputs Number of outputs 8 Connection method Spring-cage connection Connection method 1-wire Output voltage 24 V (US - 1 V) Maximum output current per channel 500 mA Maximum output current per device 4 A Nominal load, ohmic 12 W (48 Ω) Nominal load, inductive 12 VA (1.2 H; 50 Ω) Nominal load, lamp 12 W Signal delay when switching on an ohmic nominal load Typ. 500 µs Signal delay when switching on an inductive nominal load Typ. 100 ms (1.2 H; 50 Ω) Signal delay when switching on a lamp nominal load Typ. 100 ms Signal delay when switching off an ohmic nominal load Typ. 1 ms Signal delay when switching off an inductive nominal load Typ. 50 ms (1.2 H; 50 Ω) Signal delay when switching off a lamp nominal load Typ. 1 ms Maximum operating frequency with ohmic nominal load max. 300 Hz (this switching frequency is limited by the data rate selected, the number of bus devices, the structure of the bus, the software used and the control or computer system used) Maximum operating frequency with inductive nominal load max. 0.5 Hz Maximum operating frequency with lamp nominal load max. 8 Hz (this switching frequency is limited by the data rate selected, the num- ber of bus devices, the structure of the bus, the software used and the control or computer system used) Reaction time with short-circuit ca. 1 s Reaction time with ohmic overload ca. 3 s Behavior at voltage switch-off The output follows the power supply without delay One-time unsolicited energy 300 mJ Limitation of the voltage induced on circuit interruption -15 V ≤ Udemag ≤ -45.8 V (Udemag = demagnetization voltage) Output voltage when switched off max. 1 V Output current when switched off max. 300 µA Behavior with overload Auto restart

8462_en_00 PHOENIX CONTACT 5 Restart frequency with ohmic overload 400 Hz Restart frequency with lamp overload 400 Hz Behavior with inductive overload Output can be destroyed Reverse voltage resistance to short pulses Reverse voltage proof Resistance to permanent reverse voltage max. 500 mA Overcurrent shut-down min. 0.7 A Overload protection, short-circuit protection of outputs Zener diode in output chip Digital outputs Programming Data ID code (hex) BD ID code (dec.) 189 Length code (hex) 81 Length code (dec.) 129 Process data channel 8 Bit Input address area 0 Bit Output address area 8 Bit Parameter channel (PCP) 0 Bit Register length (bus) 8 Bit For the programming data/configuration data of other bus systems, please refer to the corresponding electronic device data sheet (e.g., GSD, EDS). PROFIBUS telegram data Required parameter data 3 Byte Need for configuration data 4 Byte Error messages to the higher level control or computer system Short-circuit / overload of the digital outputs Error message in the diagnostic code (bus) and display (2 Hz) via the LED (D) on the module Electrical isolation/isolation of the voltage areas 5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC , 50 Hz , 1 min 5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC , 50 Hz , 1 min

7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC , 50 Hz , 1 min

24 V supply (I/O) / functional earth ground 500 V AC , 50 Hz , 1 min

To achieve electrical isolation between the logic level and the I/O area, supply these areas from separate power supply units. Interconnection of the power supply units in the 24 V area is not permitted (see also user manual). Approvals For the latest approvals, please visit www.phoenixcontact.net/catalog.

8462_en_00 PHOENIX CONTACT 6

5 Additional tables 6 Tested su ccessfully: Use under ex-

The terminal has been tested successfully over 250 tempera- ture change cycles in accordance with IEC 61131-2 in the range from -40°C to +70°C. The following conditions were observed: – The Inline devices for all connecting cables were con- nected with a minimum conductor cross section of 0.5 mm² – The Inline station was asse mbled on a wall-mounted hor- izontal DIN rail – Fans were used to ensure continuous movement of air in the control cabinet – The Inline station was not exposed to vibration or shock – The Inline station was operated with a maximum of

24.5 V (ensured by using regulated power supply units)

Figure 1 Temperature change cycle Output characteristic curve when switched on (typical) Output current (A) Differential output voltage (V) 0.1 0.02 0.2 0.03 0.3 0.04 0.4 0.06 0.5 0.07 Temperature in the control cabinet/ambient temperature Cycle WARNING: The terminal is not approved for use in poten- tially explosive areas. The terminal is not approved for use in safety technology. 3 h + 30 min 3 h + 30 min (3 0,6) K/min+

3 K+Tmin

2 K+Tmax

8462_en_00 PHOENIX CONTACT 7

7 Internal circuit diagram

Figure 2 Internal wiring of the terminal points Key:

8 Local status and diagnostic indica-

Figure 3 Local status and diagnostic indicators Function identification Pink Explanation for other used symbols has been provided in the IL SYS INST UM E user manu- al. Protocol chip (Bus logic including voltage conditioning) LED (status indicator) Optocoupler Transistor Digital output Local bus UL OPC 88 16 +24V( U )M +24V( U)S US 4x 4x OPC Explanation for other used symbols has been provided in the IL SYS INST UM E user manu- al. Designa- tion Color Meaning D green Diagnostics (bus and logic voltage) 1 to 8 Yellow Status of the outputs D 7 8

8462_en_00 8PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany www.phoenixcontact.com

9 Terminal point assignment

Figure 4 Terminal point assignment

10 Connection notes and examples

If you connect the actuators via external busbars, make sure that the GND of the actuators and the GND for US have the same potential. Figure 5 Typical connection of actuators when using ex- ternal busbars

11 Process data

Assignment of the terminal points to the output process data Terminal point Assignment 1.1 / 2.1 Signal output (OUT 1 / OUT 2) 1.2 / 2.2 Signal output (OUT 3 / OUT 4) 1.3 / 2.3 Signal output (OUT 5 / OUT 6) 1.4 / 2.4 Signal output (OUT 7 / OUT 8) 1.1 2.1 1.2 2.2 1.3 2.3 1.4 2.4 1.1 1.2 1.3 1.4 2.1 2.3 2.4 2.2 When connecting the actuators, observe the assignment of the terminal points to the pro- cess data. NOTE: Malfunction GND of the actuators and GND of the supply voltage US, which supply the actuators, must have the same potential. (Byte.Bit) view Byte Byte 0 Bit 7 6 5 4 3 2 1 0 Assign- ment Termi- nal point (signal) Status in- dicator L E D 87654321 For the assignment of the illustrated (byte.bit) view to your INTERBUS control or computer system, please refer to the DB GB IBS SYS ADDRESS data sheet. 1.1 2.1 1.2 1.3 1.4 2.2 2.3 2.4 OUT2 OUT8OUT7 OUT1