Technical content
Features
– A serial input and output channel in RS-232, RS-422 and RS-485 format – Various protocols supported – Transmission speed can be set up to 250000 baud – Number of data bits, stop bits and parity can be set – Parameterization via process data or PCP – Process data width can be set via DIP switches: 7, 15 or 31 words – Diagnostic and status indicators This data sheet is only valid in association with the IL SYS INST UM E user manual. Make sure you always use the latest documentation. It can be downloaded from the product at www.phoenixcontact.net/catalog. 8235_en_01 2012-03-14
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 2 2T a b l e o f c o n t e n t s
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 3 Description Type Order No. Pcs. / Pkt. Inline communication terminal, for serial data transmission, complete with accessories (plug connector and labeling field), 1 serial input and output channel in RS-485/422 or RS-232 design IB IL RS UNI-PAC 2700893 1 Inline communication terminal, for serial data transmission, complete with accessories (plug connector and labeling field), 1 serial input and output channel in RS-485/422 or RS-232 design, transmission speed 2 Mbaud IB IL RS UNI-2MBD-PAC 2701025 1 3O r d e r i n g d a t a Accessories Type Order No. Pcs. / Pkt. Connector set ( Plug/Adapter ) IB IL AO/CNT-PLSET 2732664 1 Inline shield connector ( Plug/Adapter ) IB IL SCN-6 SHIELD 2726353 5 Labeling field, width: 12.2 mm ( Marking ) IB IL FIELD 2 2727501 10 Insert strip, Sheet, white, Unlabeled, Can be labeled with: Office-Drucksys- teme, Plotter: Laser printer, Mounting type: Insert, Lettering field: 62 x 10 mm ( Marking ) ESL 62X10 0809492 1 Documentation Type Order No. Pcs. / Pkt. User manual, English, Automation terminals of the Inline product range IL SYS INST UM E - - Data sheet, English, INTERBUS addressing DB GB IBS SYS ADDRESS - - Dimensions (nominal sizes in mm) Width 24.4 mm Height 136.8 mm Depth 71.5 mm
4 Technical data
119,8 71,5 General data Color green Weight 135 g Mounting type DIN rail Ambient temperature (operation) -25 °C ... 55 °C Ambient temperature (storage/transport) -25 °C ... 85 °C Permissible humidity (operation) 10 % ... 95 % (DIN EN 61131-2) Permissible humidity (storage/transport) 10 % ... 95 % (DIN EN 61131-2)
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 4 Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level) Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level) Degree of protection IP20 Protection class III, IEC 61140, EN 61140, VDE 0140-1 General data Connection data Name Inline connectors Connection method Spring-cage connection Conductor cross section [AWG] 28 ... 16 Interface Inline local bus Connection method Inline data jumper Interface RS-232, RS-485, RS-422 Connection method Spring-cage connection Transmission physics Copper Transmission speed Inline local bus IB IL RS UNI-PAC 500 kBit/s IB IL RS UNI-2MBD-PAC 2 MBit/s Power consumption Main circuit supply UM 24 V DC I/O voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple) Current consumption from UM Typ. 15 mA Current consumption from UM max. 25 mA Communications power UL 7.5 V (via voltage jumper) Current consumption from UL Typ. 78 mA Current consumption from UL max. 90 mA Power loss max. 1.2 W (Within the permissible operating temperature) This terminal takes no current from the UANA und US potential jumpers. Electrical isolation/isolation of the voltage areas Serial interface/7.5 V supply (bus logic) 500 V AC , 50 Hz , 1 min Serial interface/24 V supply UM 500 V AC , 50 Hz , 1 min Serial interface/functional earth ground 500 V AC , 50 Hz , 1 min
7.5 V supply (bus logics) / functional earth ground 500 V AC , 50 Hz , 1 min
24 V supply (UM)/functional earth ground 500 V AC , 50 Hz , 1 min
Electrical isolation of the logic level from the serial interface is ensured by the DC/DC converter. The serial interface control and data lines galvanically have the same potential. FE is a separate potential area. Error messages to the higher level control or computer system None Approvals For the latest approvals, please visit www.phoenixcontact.net/catalog.
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 5
5 Internal circuit diagram
Figure 1 Internal wiring of the terminal points Key: +24 V (U )M +24 V (U )S Local bus UL+ UAna UL- SUPI 4 µP RxD_232 +5 V DTR_232 TxD_232 CTS_232 24 V 5 V RS-485 RS-232 Switch TxD_485 /TxD_485 RxD_485 DSR_232 /RxD_485 RTS_232 R+_485 DCD_232 R-_485 DSR RTS DCD Current limit short cut protection RS-232 ±5 V ±5 V GND ±5 V±5 V ±5 V Protocol chip Microprocessor RS-485/422/232 interface Diagnostic and status indicators Optocoupler DC/DC converter with electrical isolation SUPI 4 µC Electrically isolated area Capacitor Ground, electrically isolated from ground of the communications power U L Explanation for other used symbols has been provided in the IL SYS INST UM E user manu- al. There is a combination of resistors between R+_485 and R-_485 which serve as a termina- tion resistor when being used as RS-485 or RS- 422 interface.
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 6
6 Terminal point assignment
Figure 2 Terminal point assignment
6.1 RS-485/422 communication
6.2 RS-232 communication
1.1 TxD+ Transmit data positive
2.1 TxD- Transmit data negative
1.2 RxD+ Receive data positive
2.2 RxD- Receive data negative
1.3 R+ Termination resistor Positive
2.3 R- Termination resistor Negative
1.4 / 2.4 Shield Shield connection, same potential as FE Connector 2 The terminal points of this connector are not used. 1.1 2.1 1.2 2.2 1.3 2.3 1.4 2.4 1.1 2.1 1.2 2.2 1.3 2.3 1.4 2.4 1.1 1.2 1.3 1.1 1.2 1.3 1.4 2.1 2.2 2.3 2.1 2.2 2.3 2.4 Terminal point Signal Description Connector 1 1.1 / 2.1 - Not used
1.2 DSR Data set
ready to operate; handshake signal; input
2.2 RTS Request to
Request to send; handshake signal; out- put
1.3 DCD Data car-
ready to operate; handshake signal; input 2.3 - Not used 1.4 / 2.4 - Not used Connector 2
1.1 RxD Serial data input
2.1 TxD Serial data output
1.2 +5 V DC Control output; inter- nally wired to +5 V
2.2 CTS Clear to
Permission to send; connected device ready to receive; hand- shake signal; input
1.3 DTR Data ter-
connected device; handshake signal; out- put
2.3 GND Ground for the serial
1.4 / 2.4 Shield Shield connection, ca- pacitive to FE Ensure that on connector 2, terminal point 1.2 (+5 V DC) is exclusively used to provide the 5 V signal for the CTS input (terminal point 2.2), in the event of communication without a hand- shake. In this case, insert a jumper between the terminal points.
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 7
7 Local status and diagnostic indica-
Figure 3 Local status and diagnostic indicators Function identification Orange
2 Mbps: White stripe in the vicinity of the D LED
D green Diagnostics (bus and logic voltage) TR Green PCP communication DCD Yellow Data carrier detect RxD Yellow Terminal receives data from the connected device TxD Yellow Terminal transmits data to the con- nected device CTS Yellow Clear to send RTS Yellow Request to send DSR Yellow Data set ready DTR Yellow Data terminal ready For detailed information on diagnostics, please refer to the IL SYS INST UM E user manual. D TR DCD TxD RxD RS UNI CTS RTS DTR DSR
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 8
8 Serial interfaces
8.1 RS-232
The RS-232 interface on the terminal represents some form of DTE (data termination equipment). This means that connector 2 terminal point 2.1 (TxD) is al- ways used to transmit and connector 2 terminal point 1.1 (RxD) is always used to receive. According to the standard, some form of DCE (data commu- nication equipment) should be connected to the RS-232 inter- face as a peer. DTE can also be connected. Measuring the voltage between the connection points for the TxD and GND signals in idle state will determine whether the device to be connected to the RS-232 interface is a form of DTE or DCE. If the voltage measures approximately -5 V, the device is a form of DTE. If the voltage is approximately 0 V, the device is a form of DCE. Example: When using a 25-pos. standard connector the volt- age between pin 2 (TxD) and pin 7 (GND) must be measured. RS-232 module handshake signals Any device with a RS-232 interface can be connected to the RS-232 interface on the terminal. Both the terminal and the device connected to the RS-232 interface can act as a trans- mitter and a receiver for data exchange. As errors can occur during data exchange if both devices transmit or receive si- multaneously, the handshake is used as a procedure for the mutual signaling of clear to receive and clear to transmit. The terminal supports the RTS, CTS, CTR, DSR and DCD handshake signals. Each uses one wire of the connecting ca- ble. The connecting signals are described from the point of view of the terminal, i.e., from the point of view of the DTE.
8.2 RS-485
In RS-485 operating mode, an RS-485 network with several devices can be created. Use a twisted-pair, shared and shielded data line to connect the devices. Fit this data line with termination resistors at the two most remote points of the RS-485 network. Use the termi- nation resistor integrated in the device when connecting the Inline terminal. This operating mode supports half-duplex transmission. Make sure that only one device is transmitting data at a time. To ensure a defined idle cable state, the terminal contains data line polarization.
8.3 RS-422
In RS-422 operating mode, a point-to-point connection can be established. Use a twisted-pair, shared and shielded data line to connect the devices. Fit this data line with termination resistors at every device. Use the termination resistor integrated in the device when connecting the Inline terminal. This operating mode supports full duplex transmission.
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 9
9 Connection examples
Please observe the following when wiring: – Always connect the shield between two devices on one side using a capacitor and on the other side directly to FE. – Fit a termination resistor to the RS-485 network begin- ning and end. – For an RS-422 point-to-point connection, the receive sig- nals on every device must be fitted with termination resis- tors.
9.1 RS-485: Terminal as the network end point
Figure 4 RS-485 interface wiring: Terminal as end point of a network, shield or data cable directly connected to FE Operating mode Special feature Shield connection Notes Required connectors RS-485 Inline terminal as net- work end point Directly Termination resistor re- quired Supplied connectors (connector set) RS-485 Inline terminal as net- work end point With a capacitor Termination resistor re- quired Supplied connectors (connector set) RS-485 Terminal in the network center With a capacitor/di- rectly -2 s h i e l d c o n n e c t o r s RS-422 Shield connected using a capacitor With a capacitor Termination resistor re- quired Supplied connectors (connector set) The connector set consists of a shield connec- tor and a standard connector. It is supplied as standard. Connect the shield directly to FE. RS 485 RS 485 RS 485 TxD+ TxD- RxD- 1.1 2.1 1.2 2.2 R+ 1.3 2.3 RxD+ IB IL RS UNI ... D TR CTS RTS RxD TxD DCD DSR DTR Transmit/receive data( positive) Transmit/receive data( negative) Connecting the termination resistor via R+a nd R- Inline connector (Connector 1) Connector
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 10
9.2 RS-485: Terminal as the network end point
Figure 5 RS-485 interface wiring: Terminal as end point of a network, shield or data cable connected capacitively to FE
9.3 RS-485: Terminal in the network center
Figure 6 RS-485 interface wiring: Terminal in the center of a network, data line shield connected directly capacitively to FE
9.4 RS-422: Shield connected to the terminal using a capacitor
Figure 7 RS-422 interface wiring: Data lin e shield connected capacitively to FE Connect the shield to FE using a capacitor. RS 485RS 485 IB IL RS UNI ... TxD+ TxD- RxD- 1.1 2.1 1.2 2.2 R+ 1.3 2.3 RxD+ D TR CTS RTS RxD TxD DCD DSR DTR Connecting the termination resistor via R+a nd R- Transmit/receive data( negative) Transmit/receive data( positive) Inline connector (Connector 1) Connector D TR CTS RTS RS 485 RS 485 RS 485 TxD+ TxD- RxD- 1.1 2.1 1.2 2.2 R+ 1.3 2.3 RxD+ IB IL RS UNI ... RS 485RS 485 RxD TxD DCD DSR DTR Transmit/ receive data (negative) Transmit/ receive data (positive) Inline connector (Connector 1) Connector RS 422 TxD+ TxD- RxD- 1.1 2.1 1.2 2.2 R+ 1.3 2.3 RxD+ IB IL RS UNI ... D TR CTS RTS RxD TxD DCD DSR DTR Transmit data( positive) Transmit data( negative) Receive data( positive) Receive data( negative) Connecting the termination resistor via R+a nd R- Receive data( positive) Receive data( negative) Transmit data( positive) Transmit data( negative) Connecting the termination resistor Inline connector (Connector 1) RS-422 device Connector
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 11
9.5 RS-232: With 4-wire handshake
Figure 8 RS-232 interface wiring: data cable shield con- nected capacitively to FE
9.6 RS-232: Without handshake
Figure 9 RS-232 interface wiring: data cable shield con- nected directly to FE For wiring without handshake, insert a bridge between termi- nal points 1.2 (+5 V) and 2.2 (CTS).
10 Data storage and transmission
The terminal stores the received serial data in an intermediate buffer until it is requested from the serial interface by the bus controller board or the device. Serial data traffic can be man- aged using various protocols. The protocol used depends on the type of protocol supported by the peer.
10.1 Supported protocols
10.2 Transparent protocol
If the transparent protocol is used, serial data is transmitted in the same format it is received from the serial interface or from the bus side. The transmit FIFO (First-In-First-Out memory) can store 1023 bytes (1 kbyte) and the receive FIFO can store 4096 bytes (4 kbytes). If the terminal receives another character after the 4095th character, the error pattern is stored in the re- ceive FIFO. All other subsequent characters are ignored. This protocol supports a CTS hardware handshake. If the available space in the receive memory is less than 15 bytes, DTR is set to logic 0. As soon as more memory space becomes available again, DTR is set to logic 1. 1.1 2.1 1.2 1.3 1.4 2.2 2.3 2.4 1.1 2.1 1.2 1.3 1.4 2.2 2.3 2.4 DTR CTS TxD RxD 1.1 2.1 1.2 1.3 1.4 2.2 2.3 2.4 1.1 2.1 1.2 1.3 1.4 2.2 2.3 2.4 TxDRxD Protocol Receive memory Transmit memory Special fea- tures when receiving Transparent 4096 bytes 1023 bytes End-to-end 3 buffers with 330 bytes each 1023 bytes (including end charac- ters) Two end characters are filtered out XON/XOFF 4096 bytes 1023 bytes Software handshake
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 12
10.3 End-to-end protocol
The serial data is conditioned for the end-to-end protocol. If serial data is sent from the bus side, two additional charac- ters, the first and second delimiters, are attached for transmis- sion to the serial interface. A block of serial data sent from the serial interface is only valid if the terminal has received the first and second delimiters. Only then the data can be read via the bus side. The delimit- ers are filtered out. Unlike in the transparent protocol, the receive memory is not organized as a FIFO but as a buffer. There are 3 buffers avail- able, each with 330 bytes. If the buffer size of 330 bytes is ex- ceeded without the two delimiters being detected, the previ- ous characters will be ignored and the buffer will be written again. The transmit FIFO can store 1023 bytes (1 kbyte). The delim- iters are attached to, and stored with, the data to be sent.
10.4 XON/XOFF protocol
This protocol operates in the same way as the transparent protocol, but uses a software handshake. Data transmission with this protocol is controlled by the XON and XOFF characters. XON is preset to 11hex and XOFF to 13hex. If the terminal receives an XOFF, no more serial data will be sent until an XON is received. The terminal itself will transmit an XOFF if the available space in the receive memory is less than 15 bytes. As soon as more memory space becomes available again, the terminal will transmit a single XON. Transmission does not depend on the CTS input. Transmission of serial data is not filtered. So any characters occurring with the code defined for XON and XOFF are trans- mitted and may trigger undesirable events at the receiver. When serial data is received, the XON and XOFF characters are filtered and are not available as data. Any characters with the XON or XOFF code are lost. Ensure that characters with these codes do not appear in the data stream.
11 Programming data/configuration
11.1 Local bus (INTERBUS)
11.2 Other bus systems or networks
I D c o d e [ h e x ] D FD FD F ID code (dec) 223 223 223 Length code [hex] 07 0F 1F Process data channel 112 bits 240 bits 496 bits Input address space 7 words 15 words 31 words Output ad- dress space 7 words 15 words 31 words Parameter channel (PCP) 1 word 1 word 1 word Register length (bus) 8 words 16 words 32 words For the programming data/configuration data of other bus systems, please refer to the corre- sponding electronic device data sheet (e.g., GSD, EDS).
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 13
12 Process data
The process image width of the terminal depends on the DIP switch positions and comprises 7, 15 or 31 data words in input and output direction respectively. Figure 10 DIP switches Example for the assignment of seven words of process data The command is used to determine the function. The actually transmitted data depends on the command. Data length ON Switch 2 Switch 1 Data width User data when transmitting and reading OFF OFF 7 words 11 bytes OFF ON 15 words 27 bytes ON OFF 31 words 59 bytes ON ON Reserved Reserved For the assignment of the illustrated (byte.bit) view to your INTERBUS control or computer system, please refer to the DB GB IBS SYS ADDRESS data sheet. W o r d 0123456 Byte in the Motor- ola format 0123456789 1 0 1 1 1 2 1 3 Byte in the Intel format 1032547698 1 1 1 0 1 3 1 2 O U T K / P SLDDDDDDDDDDD I N K / P SLDDDDDDDDDDD K/P Command/parameter S Control bits (OUT) or status bits (IN) L Length: Number of characters to be written (OUT) or to be read (IN) DD a t a The byte representation in the Motorola format, also called Big Endian (high order byte at start- ing address) corresponds to the INTERBUS standard representation. All byte representa- tions in the data sheet have this format. The byte representation in the Intel format is also called Little Endian (low order byte at start- ing address).
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 14
13 Process data word 0
13.1 Control word
Command toggling is used to execute a command on a termi- nal again. In this way, a second command code is available for the same function. This applies for the following commands: – Transmit characters – Store characters temporarily –R e a d c h a r a c t e r s –R e a d c o u n t e r s Here, bit 14 is used for toggling. If, for example, you wish to transmit character strings in sequence, use command code 001 hex for the first transmission and then use 101hex and 001hex alternately. 1 5 1 4 1 3 1 2 1 1 1 0 9876543210
0 Command OUT parameter Control bits
D T R 0000 R e s e t t r a n s - mit error Reset receive error DTR (if DTR control enabled) Code [bin] Meaning 0D T R = l o g i c 0 1D T R = l o g i c 1 The DTR signal can only be controlled when DTR control is enabled via process data, that is when the DTR control bit has been enabled in the configuration (see "Write configuration" command). Code [bin] Meaning Reset transmit error
0 No action
1 Reset transmit error
Code [bin] Meaning
1 Reset receive error
The listed protocols do not support transmit and receive errors. Code [bin] Code [hex] Command 000 0 Read number of characters received 001 1 Transmit characters 010 2 Store characters temporarily 011 3 OUT parameter = 0 hex: Read characters 011 3 OUT parameter = C hex: Read firmware version 011 3 OUT parameter = D hex: Read configura- tion 011 3 OUT parameter = E hex: Read counters 100 4 Write configuration 101 5 Toggling command 1: Transmit charac- ters 110 6 Toggling command 2: Store characters temporarily 111 7 Toggling command 3: Read characters
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 15
13.2 Status word
Reasons for an error bit set: – Invalid parameter for the specified command – Failure of the I/O voltage Status bits 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 St Command IN parameter Status bits St Error bit 76543210 DSR Transmit buf- fer not empty Transmit buf- fer full Receive buf- fer full DCD Transmit error Receive error Receive buf- fer not empty DSR Code [bin] Meaning 0D S R = l o g i c 0 1D S R = l o g i c 1 Transmit buffer not empty Code [bin] Meaning 0E m p t y 1N o t e m p t y Transmit buffer full Code [bin] Meaning 0N o t f u l l 1F u l l Receive buffer full Code [bin] Meaning 0N o t f u l l 1F u l l DCD Code [bin] Meaning 0D C D = l o g i c 0 1D C D = l o g i c 1 Transmit error Code [bin] Meaning
0 No error
1 Transmit error
Code [bin] Meaning
1 Receive error
Code [bin] Meaning Receive buffer not empty 0E m p t y 1N o t e m p t y The listed protocols do not support transmit and receive errors.
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 16
14 Commands
14.1 "Read number of characters received" command The command result is the number of characters that have been received but not yet read. This command can be used to first reach a minimum number of characters before transmitting the "Read characters" com- mand. Process data assignment for the "Read number of characters received" command (process data width: 7 words) 14.2 "Transmit characters" command The transmit data located in the process data is stored in the transmit memory. From there the data is transmitted directly via the interface. Depending on the process data width a max- imum of 11, 27 or 59 characters can be transmitted. Enter the number of characters to be transmitted in the third byte. If there are characters in the intermediate buffer, these are transmitted first. After the command has been executed suc- cessfully, the intermediate buffer is cleared. Process data assignment for the "Transmit characters" command with 11 characters (Z1 - Z11; process data width: 7 words) Reasons for an error bit set: – Byte 2 (number of characters to be transmitted) = 0 or > maximum user data length (11, 27 or 59 charac- ters) – "Neutral" interface type 14.3 "Store characters temporarily" command The transmit data located in the process data is stored in an intermediate buffer, which can store up to 330 characters. No characters are transmitted. The "Transmit characters" com- mand is used to transmit temporarily stored data. In this way, blocks of up to 330 characters can be transmitted. They are, for example, divided into 30 telegrams, each with 11 charac- ters. Reasons for an error bit set: – Byte 2 (number of characters to be transmitted) = 0 or > maximum user data length (11, 27 or 59 charac- ters) – Not enough space in the intermediate buffer W o r d 0 1 23456 B y t e 0 1 2 3 456789 1 0 1 1 1 2 1 3 OUT 00 hex xx xx xx xx xx xx xx xx xx xx xx xx xx IN 00 hex Status bits Read number of char- acters received xx xx xx xx xx xx xx xx xx xx W o r d 0123456 B y t e 0123456789 1 0 1 1 1 2 1 3 OUT 10 hex xx 0B hex C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 IN 10 hex Status bits xx xx xx xx xx xx xx xx xx xx xx xx
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 17 14.4 "Read characters" command Depending on the process data width set a maximum of 11, 27 or 59 characters can be read. The third byte (byte 2) con- tains the number of valid characters available in the input data. Process data assignment for the "Read characters" command with eleven characters (C1 - C11) Bit 7 in the third input byte (byte 2) 14.5 "Read counters" command This command can be used to read several counters. The counters are used for interface diagnostics. Process data assignment for the "Read counters" command W o r d 0123456 B y t e 0 1 23456789 1 0 1 1 1 2 1 3 OUT 30 hex xx xx xx xx xx xx xx xx xx xx xx xx xx IN 30 hex Status bits 0Bhex C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 Byte 2, bit 7 Effect Protocol
0 The characters read are the
last ones in the block re- ceived. E.g., end-to- end
1 There are still more charac-
ters to be read from the block received. E.g., end-to- endW o r d 0123 B y t e 01234567 OUT 3E hex 00hex xx xx xx xx xx xx IN 3E hex Status bits Number of valid charac- ters received Number of invalid charac- ters received (parity, overrun or framing errors) Number of characters transmitted
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 18 14.6 "Write configuration" command Output words 0 to 6 Process data assignment for the "Write configuration" com- mand Element value range Byte 2 (T/P: interface type/protocol) W o r d 0123456 B y t e 0 1 23456789 1 0 1 1 1 2 1 3 OUT 40 hex xx T/P B/DB 1st del 2nd del ErrP Uni1 Uni2 Uni3 res. res. Tv Tn IN 40 hex Status bits The options in bold are default settings. 76543210 res. DTR Interface type Protocol DTR: DTR control Code [bin] Meaning
0 Automatic
1 Can be controlled via process data
Code [bin] Meaning
00 RS-232
01 RS-485
10 RS-422
11 Neutral
Select an RS-xxx interface type. With the "neu- tral" default setting, no data is transmitted or re- ceived. When using the default setting, an error message is generated and the error bit is set. Protocol Code [hex] Meaning
0 Transparent
2 XON/XOFF
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 19 Byte 3 (D/DB: baud rate/data width) Byte 4 and 5 (1st del, 2nd del: 1st and 2nd delimiters) The 1st delimiter and 2nd delimiter contain the end characters for the end-to-end and dual buffer protocols. When selecting the end-to-end protocol, the two delimiters can be adjusted. Default settings: Byte 6 (ErrP: error pattern) The error pattern contains the character that is written to the FIFO if a character was received with errors (e.g., in the event of a parity error). The error pattern is used for the following protocols: – Transparent –E n d - t o - e n d – XON/XOFF Baud rate Code [hex] Wert [baud] 01 1 0 13 0 0 26 0 0 3 1200 4 1800 5 2400 6 4800 7 9600 8 15625 9 19200 A 38400 B 57600 C 115200 D 230400 E 250000 F Direct (Uni1 ... 3) The specified baud rates of 110 baud to 250000 baud are adequate for most applica- tions. However, you can freely choose the baud rate by direct programming. For this, use the 0F hex baud rate code. Data width Code [hex] Meaning - Data bits Parity Stop bits
07 E v e n 1
17 O d d 1
28 E v e n 1
38 O d d 1
48 W i t h o u t 1
57 W i t h o u t 1
67 E v e n 2
77 O d d 2
88 E v e n 2
98 O d d 2
C8 C o n s t a n t l y a t 0 1 D8 C o n s t a n t l y a t 1 1 E6 W i t h o u t 1 FD i r e c t l y (Uni1) The specified combinations of data width, pari- ty and stop bits are adequate for most applica- tions. However, you can freely choose the combination by direct programming. For this, use the 0Fhex data width code. Delimiter Default value ASCII character 1st del 0D hex CR = carriage return 2nd del 0A hex LF = line feed Error pattern Code [hex] Meaning 24 $ xx Any character
00 If a character is received with an error, no
error pattern is stored. FF The invalid character is stored instead of the error pattern.
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 20 These bytes can be used as universal bytes for direct specifi- cation of the baud rate or the data width. Direct specification of baud rate If the provided baud rates do not correspond to the desired baud rate, the baud rate can be directly specified. For this, write the desired baud rate on the Uni1 to Uni3 fields in the form of a numeric value. Transfer is right-aligned. However, only the 2 lower bits of Uni1 are permitted. The maximum value is 18 bits. The maximum value = 3FFFFhex which corresponds to 262143 baud. Direct specification of the data width If the provided combinations of data width, parity and stop bits are inadequate, they can be directly specified. Use the Uni1 byte. Bit 1 and bit 0 are reserved. Example for direct specification of the baud rate: – Baud rate: 100000 baud – 100000 dec = 01 86 A0hex Byte 7 Byte 8 Byte 9 Data width Baud rate 76 5 4 3 21 0 Parity Enable parity Stop bits Data bits res. res. Parity Code [bin] Meaning
00 Odd
01 Even
10 Constantly at 1
11 Constantly at 0
Code [bin] Meaning 0D i s a b l e 1E n a b l e Stop bits Code [bin] Meaning 01 s t o p b i t 12 s t o p b i t s Data bits Code [bin] Meaning 00 5 bits 01 6 bits 10 7 bits 11 8 bits W o r d 0123456 B y t e 1123456789 1 0 1 1 1 2 1 3 OUT 40 hex xxhex T/P B/DB res. res. ErrP Uni1 Uni2 Uni3 res. res. Tv Tn OUT 40 hex xxhex xx Fx hex 00 00 xx 01 86 A0 00 00 xx xx
IB IL RS UNI(-2MBD)-PAC 8235_en_01 PHOENIX CONTACT 21 Byte 12 und 13 (Tv, Tn: lead time, lag time) These two times are used for the RS-232 protocol The times are specified with a resolution of 1 ms. This allows for waiting times of 1 ms ... 255 ms. When transmitting data via RS-232 the RTS signal is set. If Tv does not equal 0, transmission only starts after this time has elapsed. After all the data is sent and Tn does not equal 0, the RTS signal is only set to LOW after this time has elapsed.
15 PCP communication
15.1 General information
By default upon delivery, the terminal is configured according to the default settings (under configuration). The terminal can be configured using process data or PCP to suit your applica- tion. In PCP mode, the terminal is configured with the "Config Ta- ble" object. Tv Lead time Tn Lag time For information on PCP communication, please refer to the PCP user manuals (see Or- dering data). The programs IBS CMD (for standard control- ler boards) and PC WorX (for Controllers (ILC), Field Controllers (FC) and Remote Field Con- trollers (RFC)) are available for the configura- tion and parameterization of your INTERBUS system. For additional information, please refer to the documentation of the software used.
IB IL RS UNI(-2MBD)-PAC 8235_en_01 22PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany www.phoenixcontact.com
15.2 Object dictionary for PCP communication
15.3 "Config Table" object Configure the terminal using this object. Access this object via subindex 0, i.e., read or write the entire project. The first twelve bytes correspond to byte 2 through byte 13 of the "Write configuration" command. The other four bytes are reserved. If an invalid configuration is specified, a negative confirmation is generated with error message 08hex, 00hex or xx30hex. The low byte of the Additional_Error_Code is 30hex (value is out of range), the high byte contains the number of the affected byte. Index Data type A L Meaning Object name Rights 0080hex Record 1 16 Terminal configuration Config Table rd/wr A Number of elements rd Read access permitted L Length of an element in bytes wr Write access permitted Byte Meaning Default value
0 Type, protocol 00 hex
1 Baud rate, data width 72 hex
4 Error pattern 24 hex
8, 9 Reserved 00 00 hex
10 Tv 00 hex
11 Tn 00 hex
12 ... 15 Reserved 00 00 00 00 hex