Visit product website DATA SHEET Type 3280 2-way motor valve Type 3285 2/2 way Proportional Valve (motor-driven) Type 8611 eCONTROL - Universal controller Type 8802 ELEMENT continuous control valve systems - overview 1000196000 | Standard | EU | en | 202106 | 12 Flowmeter for gases
- Depth scale for accur ate installation in existing pipes Usable in pipes fr om ½" up to 12" (DN 300) Easy installation under pr essure Int egrated Display S tandard and Heavy Duty version available This flowmeter series is made for the measurement of especially large flow rates and use the calorimetric measuring principle. A heated sensor element is cooled down by the gas flow. This cooling effect which depends on the flow velocity and the gas characteristics serves as a flow indication, the kind of cooling directly depends on the flow velocity and the kind of gas. This kind of mass flow measurement is independent of pressure and temperature. The flowmeter can be used for monitoring air supplies, but also qualifies for the measurement of other gases, see technical data. Type 8007 is available in two versions: - Standard - Heavy Duty (with a robust aluminium die casting electronics housing). In the Heavy Duty version the sensor is encapsulated in stainless steel. Product variants described in the data sheet may differ from the product presentation and description. Type descriptionCan be combined with Type 8007 © Christian Bürkert GmbH & Co. KG, Subject to alteration
2 | 10Visit product website Table of contents 1. Gener al technical data 3 Materials 3. Dimensions 4 3.2. Heav y Duty version 4. Device/P rocess connections 5 4.2. Heav y Duty version 5. P roduct installation 7 5.2. Installation not es 6. P roduct operation 8 7. Or dering information 8 7.2. Bürk ert product filter 7.3. Or dering chart for air with operating pressure of 6 bar(g) - Standard version 7.4. Or dering chart for air with operating pressure of 6 bar(g) - Heavy Duty version 7.5. Or dering chart accessories - Standard version
3 | 10Visit product website 1. Gener al technical data Product properties Materials Body Stainless steel 1.4301 (standard), stainless steel 1.4571 (Heavy Duty) Electronics housing Polycarbonat (standard), aluminium Die casting (Heavy Duty) Seal NBR, FKM (for oxygen) Dimensions Detailed information can be found in chapter “3. Dimensions” on page 4. Operating pressure Up to max. 16 bar; optional to PN 40 (standard) Up to max. 50 bar (Heavy Duty) Options Other probe lengths Oxygen conformity declaration Cleaned, free of oil and fat Performance data Full scale range (Q Nom) Up to 44030 Nm3/h (air), see “6.1. Measuring principle” on page 8. Pulse output 1 Impulse per m3 ation of the inlet and outlet sections; only when properly installed) Measuring range 1:50 Electrical data Operating voltage 18…36 V DC, 5 W Output signal (Actual value) 4…20 mA Load (current output) Maximum 500 Ω Medium data Oper ating medium Air, nitrogen, oxygen, natural gas, methane, argon Temperature of gas - °C…+ 110 °C (higher t emperatures on request) Calibration medium Air, zero point adjustment with operating gas Process/Port connection & communication Digital inputs 1 input 10…30 V DC, 2 outputs 24 V DC Digital outputs RS 485 Interface, Modbus-RTU Pulse output 1 pulse per m Environment and installation Assembling screw G ½" (others on request) Ambient temperature - °C…+ °C (higher t emperatures on request) Degree of protection IP65 2. Mat erials 2.1. Chemical Resistance Char t – Bürkert resistApp Bürkert resistApp – Chemical Resistance Chart You want to ensure the reliability and durability of the materials in your individual application case? V erify your combination of media and materials on our website or in our resistApp. Start Chemical Resistance Check
4 | 10Visit product website 3. Dimensions 3.1. S tandard version Note: Dimensions in mm ø 11.6 mm 77 mm 72 mm 415 mm (Standard shaft 220 mm) SW 17 SW 32 SW 27 220 mm 3.2. Heav y Duty version Note: Dimensions in mm 134.8 mm (max.) (Ex Version) 441 mm (Standard shaft 220 mm) 99.8 mm (max.) 220 mm 156 mm (max.)
5 | 10Visit product website 4. Device/P rocess connections 4.1. S tandard version Note: The P in assignment was changed with the new device generation. For questions, please contact the responsible Bürkert facility. If the sensor is placed at the end of the Modbus syst em a termination is required. The sensors have an internal switchable termination. To use that the 6 fastening screws from the lid must be released and the internal DIP switch must be set to “On”. Please ensure that the connection plugs are still plugged and the gasket is installed correctly. Alternatively, a 120R resistor can be installed in the plug between pin 2 and pin 4. Connector A Connector B M12 connector M12 connector A M12 connector B brown black 4...20 mA grey blue white Modbus (B) Modbus (A) + VB - VB black grey Pin Connector A (connection port) Connection cable A Connector B (pulse port) Connection cable B
1 VB +
Positive power supply 12…36 V DC smoothed brown 1.) brown
2 RS 485 (A)
3 VB -
Negative power supply 12…36 V DC smoothed blue DIR Direction input blue
4 RS 485 (B)
5 I +
Current signal 4…20 mA, selected measurement signal grey P Pulse for usage grey 1.) Not connected. It is not allowed to put to potential and/or earth.
6 | 10Visit product website 4.2. Heav y Duty version Note: If the sensor is used at the end of the Modbus system a bus termination is required. Please connect the enclosed 120R resistor to the terminals, Pin 1 and 3 of “X2” connector. Pulse 1 2 I (4-20 mA) 1 2 X1 X2 X4 X6X5 I (4-20 mA) 1 2 GND VB+ 1 2 3Mod(A) 1 2 3 4 Pulse DIR Main Board Mod(B) Pulse X 1 X 2 X 4 1 2 GND V B + 1 2 3 Mod(A ) 1 2 3 4 Pulse DIR Main Board Mod(B ) Pulse X 1 X 2 X 4 1 2 GND V B + 1 2 3 Mod(A ) 1 2 3 4 Pulse DIR Main Board Mod(B ) 1 2 0 R Shut down Modbus Plug layout Voltage supply Modbus Pin Plug Description
1 X1 Voltage supply VB - (negative supply voltage GND)
2 VB + (positive supply voltage 12 V…36 V DC)
1 X2 Modbus Modbus (B)
2 Modbus shield
3 Modbus (A)
1 X4 Direction / impulse Pulse / Alarm1.) 2 Pulse / Alarm1.)
3 Direction input
4 GND
1 X5 Power output 1 I- Active1.) 2 I+ Active1.) 1 X6 Power output 2 I- Active1.) 2 I+ Active1.) 1.) All analogue outputs are galvanic isolated.
7 | 10Visit product website 5. P roduct installation 5.1. Mounting options Note: In order to get the accuracy specified in the data sheets, the sensor must be inserted in the centre of a straight pipe section with an undisturbed gas stream. To obtain an undisturbed gas stream the sections in front of and behind the sensor must be straight, long enough and without any obstructions such as edges, seams, curves etc. Careful attention must be paid to the design of the outlet section as obstructions can cause counter-flow turbulences as well as turbulences in the direction of the flow. Installation in pipes at pressures > 10 bar r equires a high pressure safety device. 5.2. Installation not es Note: In order to maintain the accuracies specified in the data sheets, the sensor must be inserted centrally in a straight piece of pipe at a point with undisturbed flow. 45 x DN 5 x DN 35 x DN 5 x DN 20 x DN 5 x DN 15 x DN 5 x DN 15 x DN 5 x DN 15 x DN 5 x DN Control valve 2 × 90° elbow joint 3 dimensional 2 × 90° elbow joint 90° elbow joint or T-piece Pipe diameter expansion Pipe diameter reduction DN = pipe diameter Flow direction
8 | 10Visit product website 6. P roduct operation 6.1. Measuring principle Acc. to DIN 1343, with 0 °C and 1013 mbar(a)1.) Note: F or other internal pipe diameters see User Manual. Flow r anges depend on the version of Type 8007 (Basic, Extended, Maximum) and the internal pipe diameter. Type 8007 is adjust- able to different internal diameters through the mechanical depth scale. The sensor can be installed in any specified pipe siz e. The presetting of the sensor ex works applies to a 2" pipe (53.1 mm inner diameter). Each version is calibr ated to a flow velocity range: – Basic version up t o max. 92.7 m/s – Ext ended version up to max. 185 m/s – Maximum version up t o max. 224 m/s The 20 mA output corresponds to this highest speed, which in turn, depending on the pipe size, can be assigned a maximum flow rate, which in turn, depending on the pipe size, a max. flow rate can be assigned. Type 8007 without display: The scaling of the 4…20 mA output is carried out in the signal receiver, e.g. the PLC, using the measuring range table. Type 8007 with display: For the scaling of the 4…20 mA output, the specific pipe size (inner diameter) can be entered here via the display and the keys. Fur- thermore, the desired flow unit can be selected. Pipe Inner diame- ter of pipe DIN 1343 (0 °C, 1013 mbar(a)) Basic Ext ended Maximum [Inch] velocity up to Nm 3/h velocity up to Nm3/h velocity up to Nm3/h ½" 16.1 92.7 m/s 41 185 m/s 80 224 m/s 100 ¾" 21.7 81 160 195 1" 27.3 136 270 325 1¼" 36.0 244 485 590 1½" 41.9 335 665 810 2" 53.1 550 1100 1330 2½" 71.1 1005 2010 2435 3" 84.9 1440 2880 3485 4" 110.0 2430 4850 5875 5" 133.7 3595 7180 8690 6" 159.3 5110 10200 12355 8" 200.0 8075 16120 19520 10" 250.0 12635 25220 30540 12" 300.0 18220 36360 44030 1.) Standard DIN 1945 (ISO 1217), at 20 °C and 1000 mbar = Standard DIN 1343, at 0 °C and 1013 mbar, multiplied by coefficient 1.087. 7. Or dering information 7.1. Bürk ert eShop – Easy ordering and quick delivery Bürkert eShop – Easy ordering and fast delivery You want to find your desired Bürkert product or spare part quickly and order dir ectly? Our online shop is available for you 24/7. Sign up and enjoy all the benefits. Order online now
9 | 10Visit product website 7.2. Bürk ert product filter Bürkert product filter – Get quickly to the right product You want to select products comfortably based on your technical requirements? Use the Bürkert product filter and find suitable articles for your application quickly and easily. Try out our product filter 7.3. Or dering chart for air with operating pressure of 6 bar(g) - Standard version Note: Calibration for other gases on request; probe lengths 120 mm, 160 mm, 300 mm, 400 mm on request. Description Article no. Type 8007 with integrated display, Basic [air 92.7 m/s], probe length 220 mm 773498 Type 8007 with integrated display, Extended [air 185 m/s], probe length 220 mm 773499 Type 8007 with integrated display, Maximum [air 224 m/s], probe length 220 mm 773500 7.4. Or dering chart for air with operating pressure of 6 bar(g) - Heavy Duty version Note: Calibration for other gases on request; probe lengths 120 mm, 160 mm, 300 mm, 400 mm on request. Description Article no. Type 8007 with integrated display, Basic [air 92.7 m/s], probe length 220 mm 773508 Type 8007 with integrated display, Extended [air 185 m/s], probe length 220 mm 773509 Type 8007 with integrated display, Maximum [air 224 m/s], probe length 220 mm 773510 7.5. Or dering chart accessories - Standard version Note: Without ordering cables, the flowmeter comes with M12-connector for port A. Description Article no. 5 m cable, with 5 pin, M12 plug at one end 770217 10 m cable, with 5 pin, M12 plug at one end 770795 Power supply Type 1573 for rail mounting, 100…240 V AC / 24 V DC, 1.25 A, NEC Class 2 (UL 1310) 772438 Power supply Type 1573 for rail mounting, 100…240 V AC / 24 V DC, 1 A, NEC Class 2 (UL 1310) 772361 Power supply Type 1573 for rail mounting, 100…240 V AC / 24 V DC, 2 A, NEC Class 2 (UL 1310) 772362 Power supply Type 1573 for rail mounting, 100…240 V AC /24 DC, 3.8 A, NEC Class 2 (UL60950 1) 772898
Bürkert – Close to You Austria Belgium Czech Republic Denmark Finland France Germany Italy Netherlands Norway Poland Spain Sweden Switzerland Turkey United Kingdom China Hong Kong India Japan Korea Malaysia Philippines Singapore Taiwan South Africa Russia United Arab Emirates Brazil Uruguay Canada USA Australia New Zealand Credits, © and concept: Christian Bürkert GmbH & Co. KG | Photographs: Marc Eggimann Fotografie - 4051 Basel | Scanner GmbH - Werbeagentur Künzelsau -