Technical content

© PHOENIX CONTACT - 02/20077280_en_02 AUTOMATIONWORX I L BI BA I 4A O 2 Data Sheet

1 Description

The ILB IB AI4 AO2 module is designed for use within an INTERBUS network. It is used to acquire analog input signals and output analog signals. Features of INTERBUS – Remote bus branch; Inline connector – 500 kbps transmission speed – I/O areas can be parameterized individually for each channel – Parameterization via process data or PCP Features of Inputs – 4 differential analog signal inputs or 4 universal RTD inputs – Connection of sensors in 2, 3 or 4-wire technology – Sensor supply with channel-specific integrated short-circuit and overload protection – Three current measuring ranges: 0 mA to 20 mA, ±20 mA, 4 mA to 20 mA – Four voltage measuring ranges:

0 V to 5 V, ±5 V, 0 V to 10 V, ±10 V

– Various RTD measuring ranges: E.g., linear R: 0 Ω to 9500 Ω, Pt 100, Pt 1000, Ni 1000 – Measured value representation in four possible formats – 16-bit measured value resolution (15 bits + sign bit) – Adjustable filter times Features of Outputs – 2 universal analog signal outputs to connect either voltage or current signals – Connection of actuators in 2-wire technology – Three current ranges: 0 mA to 20 mA, ±20 mA, 4 mA to 20 mA – Four voltage ranges: – Short-circuit-p roof outputs UL BATR RC RD SFSF PWR PWR BUS1 BUS1 BUS2 BUS2 US RTD3 RTD2 RTD1 AI4 AI3 AI2 AI1 RTD4 1 2 AO1/2 Please refer to the "Assembly and Removal of Inline Block IO Modules" application note (see "Ordering Data" on page 4). Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com. A conversion table is available on the Internet at Inline Block IO Module for INTERBUS With 4 Analog Inputs and 2 Analog Outputs

7280_en_02 PHOENIX CONTACT 2 Table of Contents

11.1 Assignment of the Process Data to the Terminal Points for the

7280_en_02 PHOENIX CONTACT 3 22 Notes on Systematic and Random Errors During Resistance and Temperature Measurement ...

7280_en_02 PHOENIX CONTACT 4 2O r d e r i n g D a t a

3 Technical Data

Figure 1 Module housing dimensions (in mm) Module Description Type Order No. Pcs./Pck. Inline Block IO module for INTERBUS with 4 analog inputs and 2 analog outputs ILB IB AI4 AO2 2878777 1 Accessories: Connectors as Replacement Item Description Type Order No. Pcs./Pck. Shield connector for the bus connection (with color print) IB IL SCN-6 SHIELD-CP 2863151 5 Connector for the supply (with color print) On request Shield connector for the connection of analog sensors (without color print) IB IL SCN-6 SHIELD 2726353 5 Shield connector for the connection of analog actuators (without color print) IB IL SCN 6-SHIELD-TWIN 2740245 5 Connector (without color print) IB IL SCN-8 2726337 10 Accessories: Other Description Type Order No. Pcs./Pck. Recommended end clamp; placed both to the right and left of the module to secure it on the DIN rail CLIPFIX 35-5 3022276 50 Documentation Description Type Order No. Pcs./Pck. "Assembly and Removal of Inline Block IO Modules" application note AH ILB INSTALLATION 9014931 1 "General Introduction to the INTERBUS System" user manual IBS SYS INTRO G4 UM E 2745211 1 "Peripherals Communication Protocol (PCP)" user manual IBS SYS PCP G4 UM E 2745169 1 "Porting Using PCP Compact" user manual IBS PCP COMPACT UM E 9015349 1 General Data Housing dimensions with connectors (width x height x depth) 156 mm x 59 mm x 141 mm Weight 505 g (with connectors) Operating mode INTERBUS Transmission speed 500 kbps Connection method for sensors 2, 3, and 4-wire technology (shielded) Connection method for actuators 2-wire technology (shielded) 7280B001 141 120 156

7280_en_02 PHOENIX CONTACT 5 Ambient Conditions Guidelines Developed according to VDE 0160/EN 50178/IEC 62103, UL 508 Ambient temperature (operation) -25°C to +60°C Ambient temperature (storage/transport) -25°C to +85°C Humidity (operation/storage/transport) 10% to 95%, according to DIN EN 61131-2 Air pressure (operation) 80 kPa to 108 kPa (up to 2000 m above sea level) Air pressure (storage/transport) 66 kPa to 108 kPa (up to 3500 m above sea level) Degree of protection according to DIN 40050, IEC 60529 IP20 Protection class according to DIN 57106-1 Class 3 according to VDE 0106/IEC 60536 Air and creepage distances According to DIN VDE 0110/IEC 60664, IEC 60664A, DIN VDE 0160/EN 50178/IEC 62103 Housing material Plastic, PVC-free, PBT, self-extinguishing (V0) Pollution degree according to EN 60664-1/IEC 60664-1, EN 61131-2/IEC 61131-2 2; condensation not permitted during operation Surge voltage class II Electrical Isolation/Isolation of the Voltage Areas Test Distance Test Voltage Incoming remote bus/logic area, outgoing remote bus 500 V AC, 50 Hz, 1 min. Incoming remote bus/analog I/O 500 V AC, 50 Hz, 1 min. Incoming remote bus/communications power UL (primary) 500 V AC, 50 Hz, 1 min. Incoming remote bus/initiator supply UIS 500 V AC, 50 Hz, 1 min. Incoming remote bus/functional earth ground 500 V AC, 50 Hz, 1 min. Logic area, outgoing remote bus/analog I/O 500 V AC, 50 Hz, 1 min. Logic area, outgoing remote bus/communications power UL (primary) 500 V AC, 50 Hz, 1 min. Logic area, outgoing remote bus/initiator supply UIS 500 V AC, 50 Hz, 1 min. Logic area, outgoing remote bus/functional earth ground 500 V AC, 50 Hz, 1 min. Analog I/O/communications power UL (primary) 500 V AC, 50 Hz, 1 min. Analog I/O/initiator supply UIS 500 V AC, 50 Hz, 1 min. Analog I/O/functional earth ground 500 V AC, 50 Hz, 1 min. Communications power UL (primary)/initiator supply UIS 500 V AC, 50 Hz, 1 min. Communications power UL (primary)/functional earth ground 500 V AC, 50 Hz, 1 min. Initiator supply UIS/functional earth ground 500 V AC, 50 Hz, 1 min. Outgoing remote bus/analog I/O 500 V AC, 50 Hz, 1 min. Outgoing remote bus/functional earth ground 500 V AC, 50 Hz, 1 min. Mechanical Requirements Vibration test sinusoidal vibrations according to EN 60068-2-6/IEC 60068-2-6 5g load, 2.5 hours in each space direction Shock test according to EN 60068-2-27/IEC 60068-2-27 30g load for 11 ms, half sinusoidal wave, 3 shocks in each space direction and orientation Broadband noise according to EN 60068-2-64/IEC 60068-2-64 0.78g load, 2.5 hours in each space direction

7280_en_02 PHOENIX CONTACT 6 Conformance With EMC Directive 89/336/EEC Noise Immunity Test According to EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2 IEC 61000-4-2 Criterion B 6 kV contact discharge 8 kV air discharge Electromagnetic fields EN 61000-4-3 IEC 61000-4-3 Criterion A Field strength: 10 V/m Fast transients (burst) EN 61000-4-4/ IEC 61000-4-4 Criterion B Remote bus: 2 kV Power supply: 2 kV I/O cables: 2 kV Criterion A All interfaces: 1 kV Surge voltage EN 61000-4-5 IEC 61000-4-5 Criterion B DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical) Signal lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical) Conducted interference EN 61000-4-6 IEC 61000-4-6 Criterion A Test voltage 10 V Noise Emission Test According to EN 61000-6-4 Noise emission of housing EN 55011 Class A Interface: INTERBUS Incoming remote bus Copper cable (RS-422), conn ected with Inline shield connector; supply electrically isolated; shielding connected with a capacitor to functional earth ground Outgoing remote bus Copper cable (RS-422), connected with Inline shield connector; supply electrically isolated; shielding connected directly to functional earth ground Recommended cable lengths See INTERBUS system data in the IBS SYS INTRO G4 UM E user manual

24 V Module Supply (Communications Power and Sensor Supply; UL and US)

Tolerance -15%/+20% according to EN 61131-2 Ripple ±5% according to EN 61131-2 Permissible range 19.2 V DC to 30.0 V DC Current consumption at UL See "Current Consumption at UL and US" Current consumption at US See "Current Consumption at UL and US" Power dissipation at UL See "Power Consumption at UL and US" on page 7 Power dissipation at US See "Power Consumption at UL and US" on page 7 Safety equipment for UL Transient surge protection via arresters, serial protection against polarity reversal Safety equipment for US Transient surge protection via arresters, serial protection against polarity reversal, channel-specific short-circuit protection with single-channel diagnostics Connection Via power connectors Diagnostics Single-channel diagnostics in the process data Failure indication via group error LED at PWR slot Single-channel failure indication via LED at slot for the sensors Electronically Protected Initiator Supply UIS (via Supply of US) Nominal value UIS 24 V DC Nominal current IIS per channel 50 mA Protection Internal, channel -specific electronic fuse, short-circuit-proof with single-channel diagnostics

7280_en_02 PHOENIX CONTACT 7 Current Consumption at UL and US Typical Maximum Current consumption at UL No-load operation of outputs and AI mode 100 mA 130 mA RTD nominal load 100 mA 130 mA AO U nominal load (UOUT1 and UOUT2 = 10 V with RL = 2 kΩ) 110 mA 140 mA AO I nominal load (IOUT1 and IOUT2 = 20 mA with RL = 0 Ω) 135 mA 175 mA Current consumption at US IiS = 0 mA (no load) 12 mA 20 mA IiS = 4 x 20 mA (nominal load) 92 mA 100 mA IiS = 4 x 50 mA (maximum full load) 212 mA 220 mA Total current consumption at UL and US No-load operation of outputs and AI mode; IiS = 0 mA (no load) 112 mA 150 mA AO U nominal load and AI nominal load; IiS = 4 x 20 mA 202 mA 240 mA AO I nominal load and AI nominal load; IiS = 4 x 20 mA 227 mA 275 mA AO I nominal load and AI full load; IiS = 4 x 50 mA 347 mA 395 mA Power Consumption at UL and US (Current Consumption at Voltages UL and US; Specifications for Nominal Operation (UL = 24 V; US = 24 V Without Load), Full Load Same as Nominal Operation But With US Under Load) Typical Supply of Control Cabinet Power Supply Unit P 24V_Supply AO Load Marginal Conditions Typical Supply Current Typical Power Dissipation Typical power supply P24V_Supply in U nominal operation U mode of the analog outputs (UOUT1,2 = 10 V with RL = 10 K) IS = 0 mA 125 mA 3.00 W Typical power supply P24V_Supply in I nominal operation I mode of the analog outputs OUT1,2 = 20 mA, with Rb = 0 Ω) IS = 0 mA 150 mA 3.60 W Typical power supply P24V_Supply in nominal operation U mode of the analog outputs (UOUT1,2 = 10 V with RL = 10 K) IS = 4 x 20 mA 200 mA 4.80 W Typical power supply P24V_Supply at full load I mode of the analog outputs OUT1,2 = 20 mA, with Rb = 0 Ω) IS = 4 x 20 mA 230 mA 5.45 W Typical power supply P24V_Supply in nominal operation U mode of the analog outputs (UOUT1,2 = +10 V with RL = 10 K) IS = 4 x 50 mA 325 mA 7.75 W Typical power supply P24V_Supply at full load I mode of the analog outputs OUT1,2 = 20 mA, with Rb = 0 Ω) IS = 4 x 50 mA 350 mA 8.35 W Analog Inputs Number 4 differential analog inputs Measured value resolution 16 bits (15 bits + sign bit) Measured value representation In the following formats: IB IL (15 bits with sign bit) RT (15 bits with sign bit) S7-compatible (15 bits with sign bit) Standardized representation (15 bits with sign bit)Filtering RFI filtering; passive TP 1st order Filter time of the A/D converter 4.5 ms (default) or 1.1 ms; adjustable for each channel Conversion time of the A/D converter 180 µs Channel conversion times and process data update time See "Channel Conversion Times and Process Data Update Time" on page 39 Limit frequency (-3 dB) of the input filters 120 Hz (for 4.5 ms filter default) or 450 Hz (for 1.1 ms filter) Transient protection Yes, via arresters Signal connection method 2, 3, and 4-wire connection; shielded, twisted pair cable Overload protection Yes, ±30 V DC, minimum For measured value representation, please refer to the notes on page 24 and onwards.

7280_en_02 PHOENIX CONTACT 8 Differential Analog Voltage Inputs Number 4 Input range 0 V to 10 V; ±10 V; 0 V to 5 V; ±5 V Input resistance 276 k Ω, typical Open circuit response Goes to 0 V Maximum permissible voltage between analog voltage inputs and functional earth ground ±50 V DC Differential Analog Current Inputs Number 4 Input range 0 mA to 20 mA; ±20 mA; 4 mA to 20 mA Input resistance 107 Ω, typical Open circuit response Goes to 0 mA Maximum permissible current per current input Electronic overload protection Overload protection at the analog current inputs Yes, ±30 V DC, minimum Analog RTD Inputs Number 4 Input range Pt 100, Pt 500, Pt 1000, Ni 100, Ni 1000, Ni 1000 L&S, 0 Ω to 3200 Ω, 0 Ω to 9500 Ω Sensor supply current 231 mA, typical Analog Outputs Number 2 Voltage output range 0 V to 10 V; ±10 V; 0 V to 5 V; ±5 V Current output range 0 mA to 20 mA; ±20 mA; 4 mA to 20 mA Measured value resolution 16 bits (15 bits + sign bit) Measured value representation In the following formats: IB IL (15 bits with sign bit) RT (15 bits with sign bit) S7-compatible (15 bits with sign bit) Standardized representation (15 bits with sign bit)Conversion time of the D/A converters 70 µs, typical Resolution of the D/A converters 16 bits Process data update time See "Channel Conversion Times and Process Data Update Time" on page 39 Output load Voltage output R Lmin = 2 kΩ Current output RLB = 0 Ω to 500 Ω Transient protection Yes, internally via arresters Signal connection method 2-wire termination; shielded, twisted pair cable Short-circuit protection Voltage output Yes, permanent electronic short-circuit protection Current output Yes, permanent elec tronic short-circuit protection Enabling function Yes, internal electronic Optical indicators 5% output LED, channel-specific For measured value representation, please refer to the notes on page 24 and onwards.

7280_en_02 PHOENIX CONTACT 9 Permissible Cable Lengths Permissible cable lengths 250 m Reference conditions The specifications refer to nominal operation observing the installation instructions. The specifications refer to the following reference cable type: Shielded power station cable: LiYCY; 2 x 2 x 0.5 mm2; VDE0812 Limit Values for Temperature Measurement Sensor Type Nominal Range Lower Limit Upper Limit Pt DIN -200°C +850°C Ni DIN -60°C +180°C Ni 1000 L&S -50°C +160°C In the event of underrange or overrange of the nominal range, the "Underrange" or "Overrange" error message is generated. Tolerances at TA = 25°C AI Measuring Range Absolute (T ypical) Absolute (Maximum) Relati ve (Typical) Relative (Maximum) 0 V to 5 V, ±5 V ±5.0 mV ±20 mV 0.10% ±0.40% 0 V to 10 V, ±10 V ±6.0 mV ±25 mV 0.06% ±0.25% 0 mA to 20 mA, ±20 mA, 4 mA to 20 mA 0 Ω to 3200 Ω ±0.4 Ω ±2.75 Ω 0.01% ±0.18% 0 Ω to 9500 Ω ±2.0 Ω ±12.0 Ω 0.02% ±0.13% AO Output Range Absolute (Typical) Absolute (Maximum) Relative (Typical) Relative (Maximum) 0 V to 5 V, ±5 V ±10 mV ±30 mV 0.20% ±0.60% 0 V to 10 V, ±10 V ±10 mV ±30 mV 0.10% ±0.30% 0 mA to 20 mA, ±20 mA, 4 mA to 20 mA The ambient conditions and the local conditions in the system can result in special requirements for the installation of cables. These must be observed accordingly. For the integration of shielded I/O cables in an equipotential bonding concept for the automation system, the following applies in principle: Shielded analog I/O cables may only be connected directly to functional earth ground potential at a single point. This results in the prevention of voltage equalization currents via the analog cable. Additional information is available on request. Other: In order to observe the tolerance of RTD inputs, make allowance for the effects of the connecting cable and connection method (2, 3, and 4-wire technology). The data contains the offset error, gain error, and linearity error. All percentage tolerance values refer to the relevant measuring range final value. Unless otherwise stated, nominal operation (nominal voltage US = UL = 24 V, preferred mounting position, default format "IB IL", default filter setting (4.5 ms), identical measuring range setting for channels, etc.) is used as the basis. For RTD inputs, the tolerances are specified in 4-wire connection method, the installation instructions should be implemented accordingly. Please also observe the values for temperature drift and the tolerances influenced by electromagnetic interference. The maximum tolerance values represent the worst-case measurement inaccuracy. They contain the theoretical maximum possible tolerances in the measuring ranges. Moreover, the theoretical maximum possible tolerances of the calibration and test equipment have been taken into consideration.

7280_en_02 PHOENIX CONTACT 10 Tolerance and Temperature Response at TA = -25°C to +60°C AI Measuring Range Drift (Typical) Drift (Maximum)

0 V to 5 V, ±5 V ±15 ppm/K ±35 ppm/K

0 V to 10 V, ±10 V ±15 ppm/K ±35 ppm/K

0 mA to 20 mA, ±20 mA, 4 mA to 20 mA ±20 ppm/K ±50 ppm/K Pt 100 (-200°C ... +850°C) ±40 ppm/K ±100 ppm/K Pt 500 (-200°C ... +850°C) ±35 ppm/K ±90 ppm/K Pt 1000 (-200°C ... +850°C) ±30 ppm/K ±80 ppm/K Ni 100 (-60°C ... +180°C) ±60 ppm/K ±110 ppm/K Ni 1000 L&S (-50°C ... +180°C) ±20 ppm/K ±50 ppm/K Ni 1000 (-60°C ... +180°C) ±20 ppm/K ±50 ppm/K 0 Ω to 3200 Ω ±20 ppm/K ±60 ppm/K 0 Ω to 9500 Ω ±25 ppm/K ±50 ppm/K AO Output Range Drift (Typical) Drift (Maximum)

0 V to 5 V, ±5 V, 0 V to 10 V, ±10 V ±55 ppm/K ±95 ppm/K

0 mA to 20 mA, ±20 mA, 4 mA to 20 mA ±50 ppm/K ±90 ppm/K The values refer to the relevant measuring range final value. The values refer to nominal operation in the recommended mounting position (horizontal wall mounting). Formula for Calculating the Tolerance Influenced by Temperature Typical temperature drift Drift typ = Δϑ x TCtyp * MFV Where: Drifttyp Typical temperature drift Δϑ Temperature difference between the ambient temperature of the module TA and +25°C TCtyp Typical temperature coefficient in ppm/K MFV Measuring range final value (e.g., +850°C for Pt 100) Maximum temperature drift Drift max = Δϑ x TCmax * MFV Where: Driftmax Maximum temperature drift Δϑ Temperature difference between the ambient temperature of the module TA and +25°C TCmax Maximum temperature coefficient in ppm/K MFV Measuring range final value (e.g., +850°C for Pt 100) Example Sensor = Pt 100; ambient temperature T A = +40°C Δϑ = +15 K TCtyp = ±40 ppm/K (typical); TCmax = ±100 ppm/K Measuring range final value Pt 100 MFV = +850°C Drifttyp = Δϑ x TCtyp x MFV = 15 K x ±40 ppm/K x 850°C = ±0.51°C Driftmax = Δϑ x TCmax x MFV = 15 K x ±100 ppm/K x 850°C = ±1.28°C The maximum drift is a worst-case value (theoretical assumption).

7280_en_02 PHOENIX CONTACT 11 Tolerances Influenced by Electromagnetic Interference Analog Input Analog Output Current Voltage RTD Current Voltage Electromagnetic fields EN 61000-4-3 IEC 61000-4-3 Fast transients (burst) EN 61000-4-4/ IEC 61000-4-4 Conducted interference EN 61000-4-6 IEC 61000-4-6 Under the influence of high-frequency electromagnetic interference phenomena caused by radio transmission systems in close proximity, additional tolerances can occur. The values specified refer to nominal operation in the event of direct interference to components without additional shielding such as a steel cabinet, etc. This information is valid for device firmware ID HW/FW 04/100 or later. The tolerances specified above can be reduced through additional shielding for the I/O module (e.g., use of a shielded control box/control cabinet, etc.). Please refer to the recommended measures in the Inline system manual for your bus system. Signal Rise Times: Voltage Output 0 V to 10 V (Typical Values) 10% to 90% 0% to > 99% Ohmic load RL = 2 k Ω 160 µs 240 µs Ohmic/capacitive load RL = 2k Ω/CL = 10 nF 160 µs 240 µs Ohmic/capacitive load RL = 2k Ω/CL = 220 nF 170 µs 240 µs Ohmic/inductive load RL = 2k Ω/LL = 3.3 mH 170 µs 240 µs Signal Rise Times: Current Output 0 mA to 20 mA (Typical Values) 10% to 90% 0% to > 99% Ohmic load RL = 500 Ω 450 µs 730 µs Ohmic/capacitive load RL = 500 Ω/CL = 10 nF 460 µs 750 µs Ohmic/capacitive load RL = 500 Ω/CL = 220 nF 770 µs 1.3 ms Ohmic/inductive load RL = 500 Ω/LL = 3.3 mH 610 µs 1.1 ms Ohmic/capacitive load RL = 50 Ω/CL = 100 nF 11 ms 20.7 ms Signal Rise Times: Current Output 4 mA to 20 mA (Typical Values) 10% to 90% 0% to > 99% Ohmic load RL = 500 Ω 400 µs 810 µs Ohmic/capacitive load RL = 500 Ω/CL = 10 nF 470 µs 840 µs Ohmic/capacitive load RL = 500 Ω/CL = 220 nF 800 µs 1.4 ms Ohmic/inductive load RL = 500 Ω/LL = 3.3 mH 590 µs 990 µs Approvals For the latest approvals, please visit www.download.phoenixcontact.com.

7280_en_02 PHOENIX CONTACT 12

4 Internal Circuit Diagram

Figure 2 Internal wiring of the terminal points AI/RTD1...4 GNDUS GNDUL UL FE 7280A020 Shield US UI AGND AI RTD AO1/2INTERBUS IN OUT PWR REF µC 24 V

24 V5V

3.3 V 24 V 15 V 24 V Key: Microprocessor Protocol chip with register expansion Optocoupler Hardware monitoring Digital/analog converter /GB5 /G43 OPC / SRE /G53 /G75 /G70 /G65 /G72 /G76 /G69 /G73 /G6F /G72 Universal output driver with integrated output shutdown Reference voltage Amplifier Constant current source Power supply unit with electrical isolation Electronic fuse U/I /G52 /G45 /G46 /G45 /G4C /G46

7280_en_02 PHOENIX CONTACT 13

5 Electrical Isolation

Figure 3 Electrical isolation of the individual function areas

6 Local Diagnostic and Status Indicators

Figure 4 Diagnostic and status indicators Incoming remote bus (5 V DC) Logic area and outgoing remote bus (3.6 V DC/5 V DC) Microprocessor, protocol chip Analog I/O (5 V DC/±15 V DC) Communications power (primary) 2 4VD C UL Initiator supply UIS Analog inputs (24 V DC) Supply of initiator supply 2 4VD C US U (24 V DC)L U (24 V DC)S U1IS U2IS U3IS U4IS Analog inputs Analog outputs 7280A004 FE potential Electrical isolation between area A and B A B UL RC BA RD BUS1 BUS2 PWR E1 E2 E3 E4 1 7280B002 US SF AI1 AI2 AI3 AI4 AO1/2RTD1 RTD2 RTD3 RTD4 TR Designation Color Meaning BUS UL Green Communications power RC Green Remote bus cable check BA Green Bus active RD Yellow Outgoing remote bus disabled TR Green PCP communication active PWR US Green Sensor supply SF Red Group error AI E1 to E4 Red Channel-specific error indication (sensor supply short circuit or open circuit) AO 1, 2 Yellow Analog output value is ≥ 5% of the positive measuring range final value

7280_en_02 PHOENIX CONTACT 14

7 Connection of INTERBUS , Supply, Analog Sensors, and Actuators

Figure 5 Terminal point assignment of the connectors 7280B003 AI1 AI2 AI3 AI4 AO1/2RTD1 RTD2 RTD3 RTD4 INTERBUS IN OUT 12 3 4 56 7 89 1 0 11 12 1.1 1.2 1.3 1.4 2.1 2.2 2.3 2.4 1.1 1.2 1.3 1.4 2.1 2.2 2.3 2.4 BUS PWR AI, RTD, AO 1 2 1.1 1.2 1.3 1.4 2.1 2.2 2.3 2.4 US UL GND UL FE UIS U1+U1- I1+ I1- GND UIS 24V U2+ U2- I2+ I2- GND 24V U3+ U3- I3+ I3- GND 24V U4+ U4- I4+ I4- GNDI1+ - I1- - U1- U1+ I2+ - I2- - U2- U2+ I3+ - I3- - U3- U3+ I4+ - I4- - U4- U4+ AGND GND US US UL

7280_en_02 PHOENIX CONTACT 15

7.1 Terminal Point Assignment of the INTERBUS Connectors

7.2 Terminal Point Assignment of the Power Connector

7.3 Terminal Point Assignment of the Connectors for the Analog Inputs

(AI; connectors 4, 6, 8, and 10 in Figure 5 on page 14) Terminal Point Assignment Remark/Wire Color in the INTERBUS Standard Cable Connector 1 (BUS 1) Incoming Remote Bus

1.1 DO1 Receive Green

2.1 DO1 Receive Yellow

1.2 DI1 Transmit Pink

2.2 DI1 Transmit Gray

1.3 F-GND Reference potential Brown

2.3 Not used

1.4, 2.4 Shield Shield potential is connected with a capacitor to functional earth ground (FE) of the potential jumper. Connector 2 (BUS 2) Outgoing Remote Bus

1.1 DO2 Transmit Green

2.1 DO2 Transmit Yellow

1.2 DI2 Receive Pink

2.2 DI2 Receive Gray

1.3 R-GND Reference potential Brown

1.4, 2.4 Shield Shield potential is connected dire ctly to functional earth ground (FE) of the potential jumper. Terminal Point Assignment Connector 3 (PWR) 1.1, 2.1 24 V supply US 1.2, 2.2 24 V communications power UL 1.3, GND UL

2.3 GND US

1.2, 2.4 FE Terminal Point Signal Assignment Connector 4 (AI1) Connector 6 (AI2) Connector 8 (AI3) Connector 10 (AI4) 1.1 1.1 1.1 1.1 UISx (24 V) Initiator supply for channel x 2.1 2.1 2.1 2.1 GNDiSx Ground of UiSx 1.2 1.2 1.2 1.2 Ux+ Positive voltage input for channel x 2.2 2.2 2.2 2.2 Ux- Negative voltage input for channel x 1.3 1.3 1.3 1.3 Ix+ Positive current input for channel x 2.3 2.3 2.3 2.3 Ix- Negative current input for channel x x = 1 to 4

7280_en_02 PHOENIX CONTACT 16

7.4 Terminal Point Assignment of the Connectors for the Analog RTD Inputs

(RTD; connectors 5, 7, 9, and 11 in Figure 5 on page 14)

7.5 Terminal Point Assignment of the Connectors for the Analog Outputs

(AO, connector 12 in Figure 5 on page 14) Terminal Point Signal Assignment Connector 5 (RTD1) Connector 7 (RTD2) Connector 9 (RTD3) Connector 11 (RTD4) 1.1 1.1 1.1 1.1 Ix+ Positive constant current supply for RTD sensor channel x 2.1 2.1 2.1 2.1 – Reserved 1.2 1.2 1.2 1.2 Ix- Negative constant current supply for RTD sensor channel x 2.2 2.2 2.2 2.2 – Reserved 1.3 1.3 1.3 1.3 Ux- Negative voltage input for RTD sensor channel x 2.3 2.3 2.3 2.3 Ux+ Positive voltage input for RTD sensor channel x x = 1 to 4 Terminal Point Signal Assignment Connector 12 (AO)

1.1 U1/I1 Voltage or current output

2.1 U2/I2 Voltage or current output

1.2 U1/I1 Voltage or current output

2.2 U2/I2 Voltage or current output

1.3 AGND Analog ground channel 1

2.3 AGND Analog ground channel 2

1.4, 2.4 Shield Shield connection The relevant unused terminal point for voltage or current output of a channel can be used for test purposes.

7280_en_02 PHOENIX CONTACT 17

8 Connection Notes

9 Connection Examples

Figure 6 General connection example Always connect the analog sensors using shielded, twisted pair cables. Connect the shielding to the module using the shield connection clamp. The clamp connects the shield to FE on the module side. Avoid connection to FE from both sides. The module is supplied with a shield connector and a standard connector for each input channel. The shield connection can be used for the standard signal (current/voltage) as well as for the RTD signal. The module has an FE spring (metal clip) on the bottom of the electronics base. This spring establishes an electrical connection to the DIN rail. Use grounding terminals to connect the DIN rail to protective earth ground. The module is grounded when it is snapped onto the DIN rail. To ensure reliable functional earth grounding of the module even when the DIN rail is dirty or the metal clip is damaged, always ground the module via the FE terminal point (see Figure 6). 7280B005 AI AI AI AI AORTD RTD RTD RTD OUT2 U + -+-USUL + -INTERBUS IN OUT 12 3 4 56 7 89 1 0 11 12 Ideal current source Application: Passive 2-wire transmitter Variable resistor General actuator + - OUT2 The numbers above the module illustration indicate the connector slots.

7280_en_02 PHOENIX CONTACT 18

9.1 Connection Examples for Analog Inputs

Figure 7 Voltage measurement Figure 8 Current measurement Figure 9 Passive transmitter (4 mA to 20 mA) Figure 10 Differential mo de voltage measurement, e.g., for shunt, jumpering, and battery charging applications Figure 11 Active transmitter (4 mA to 20 mA) Ideal current source Ideal voltage source + - + - 1 2 24VGND U+ U- I+ I- + 7280A006 AI 1 2 24VGND U+ U- I+ I- 7280A007 AI 1 2 24VGND U+ U- I+ I- 7280A008 AI 1 2 24VGND U+ U- I+ I- US 7280A009 AI IS 1 2 24VGND U+ U- I+ I- 7280A010 AI

24 VGND

7280_en_02 PHOENIX CONTACT 19

9.2 Connection Examples for RTD Inputs

Figure 12 RTD 2-wire connection with connector compensation Figure 13 RTD 3-wire connection Figure 14 RTD 4-wire connection

9.3 Connection Examples for Analog Outputs

Figure 15 Analog current output Figure 16 Analog voltage output Please refer to the connection notes for the RTD 2-wire connection in "RTD 2-Wire Connection With Connector Compensation" on page 41. 1 2 I+ RES I- RES U- U+ RTD RL I+ 7280B011 RL 1 2 I+ RES I- RES U- U+ RTD RL RL 7280A012 RL U- (I = 0 µA) 1 2 I+ RES I- RES U- U+ RTD RL RL 7280A013 RL U- (I = 0 µA) RL U+ (I = 0 µA) 1 2 7280A014 AO I2I1 OUT2OUT1 1 2 7280A015 AO U2U1 OUT2OUT1

7280_en_02 PHOENIX CONTACT 20

10 Programming Data

11 Process Data

The device has 5 process data words and 1 PCP word. Figure 17 Order of the process data words ID code F3 hex (243dec) Length code 05 hex Process data channel 80 bits Input address area 5 words Output address area 5 words Parameter channel (PCP) 1 word Register length (bus) 6 words OUT1 7280A026 OUT2 OUT3 OUT4 OUT5 IN2 IN3 IN4 IN5 Control word Status word IN1 OUT IN Channel 1 Channel 1 Channel 2 Channel 2 Channel 3 Channel 3 Channel 4 Channel 4

7280_en_02 PHOENIX CONTACT 21

11.1 Assignment of the Process Data to the Terminal Points for the "Read and Write Analog Values"

Assignment of the Terminal Points for Connector 12 to the Process Data Output Words Assignment of the Terminal Points to the Process Data Input Words (Word.bit) view Word Word x B i t 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 (Byte.bit) view Byte Byte 0 Byte 1 B i t 7654321076543210 Word 2: Channel AO1 Signal Terminal point 1.1: Voltage output Terminal point 1.2: Current output Signal reference Terminal point 1.3: Analog ground Shielding (FE) Terminal point 1.4, 2.4 Word 3: Channel AO2 Signal Terminal point 1.1: Voltage output Terminal point 1.2: Current output Signal reference Terminal point 1.3: Analog ground Shielding (FE) Terminal point 1.4, 2.4 (Word.bit) view Word Word x B i t 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 (Byte.bit) view Byte Byte 0 Byte 1 B i t 7654321076543210 AI Word 2: Channel 1 (connector 4) Word 3: Channel 2 (connector 6) Word 4: Channel 3 (connector 8) Word 5: Channel 4 (connector 10) Signal Terminal point 1.2: Positive voltage input Terminal point 1.3: Positive current input Signal reference Terminal point 2.2: Negative voltage input Terminal point 2.3: Negative current input Shielding (FE) Terminal point 1.4, 2.4 RTD Word 2: Channel 1 (connector 5) Word 3: Channel 2 (connector 7) Word 4: Channel 3 (connector 9) Word 5: Channel 4 (connector 11) Signal Terminal point 2.3: Voltage input for RTD sensor Signal reference Terminal point 1.3 (negative voltage input for RTD sensor) Constant current supply Terminal point 1.1 (positive constant current supply) Terminal point 1.2 (negative constant current supply) Shielding (FE) Terminal point 1.4, 2.4

7280_en_02 PHOENIX CONTACT 22

12 OUT Process Data Words

Five OUT process data words are available. The first output word (OUT1) represents the control word, the following words (OUT2 to OUT5) each refer to an analog channel. They are used for channel-specific configuration and to output analog values. As confirmation for a control word action, the first input word contains a partial copy of the control word. Bit 15 to bit 8 (command code) OUT1 Byte 0 Byte 1 B i t 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 Assignment Command code 0 0000000 Bit 15 to Bit 8 OUT1 Command Function 0 1 0 0 0 0 0 0 40xx hex Configure device. The channel parameters of the four channels are configured in OUT2 to OUT5. Read configuration. The configuration of each channel is displayed channel-by-channel in IN2. 0 0 0 1 0 0 0 01 0 0 0 hex Configuration channel 1 0 0 0 1 0 0 0 11 1 0 0 hex Configuration channel 2 0 0 0 1 0 0 1 01 2 0 0 hex Configuration channel 3 0 0 0 1 0 0 1 11 3 0 0 hex Configuration channel 4 Read and write analog values. The analog values for the input channels are displayed in IN2 to IN5. The analog values for the output channels are displayed in OUT2 and OUT3. 0 0 0 0 0 0 0 00 0 0 0 hex OUT process data not transmitted, the analog outputs are not modified. 0 0 0 0 0 0 0 10 1 0 0 hex The analog outputs accept the value specified via OUT2 and OUT3. 0 0 1 1 1 1 0 03 C 0 0 hex Read device data. The firmware version and the device ID are displayed in IN2, see "Input Words IN2 to IN5" on page 23.

7280_en_02 PHOENIX CONTACT 23

13 IN Process Data Words

13.1 Input Word IN1 (Status Word)

Error bit: The error bit is available as a group error message. Possible errors and their effects are listed in "Diagnostics" on page 38. * Mirrored command code: A command code mirrored from the control word. Here, the MSB is suppressed.

13.2 Input Words IN2 to IN5

The measured values, firmware version or configuration are transmitted to the controller board or the computer via IN process data words IN2 to IN5 according to the configuration. * Input data IN1 contains the error bit and the mirrored command code. Example for "Read device data": OUT1 Byte 0 Byte 1 B i t 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 Assignment EB M i r r o r e d c o m m a n d c o d e * 00000000 EB = 0 No error has occurred. EB = 1 An error has occurred. IN1* IN2 IN3 IN4 IN5 Configure device. Configuration data following transmission to the channels 40xxhex Configuration data channel 1 Configuration data channel 2 Configuration data channel 3 Configuration data channel 4 Read configuration. 1000hex Configuration channel 1 Not relevant Not relevant Not relevant1100hex Configuration channel 2 1200hex Configuration channel 3 1300hex Configuration channel 4 Read and write analog values. 00xxhex Measured value of the analog input channel 1 Measured value of the analog input channel 2 Measured value of the analog input channel 3 Measured value of the analog input channel 4 01xxhex Read device data. 3C00hex Firmware version and device ID, see below Not relevant Not relevant Not relevant IN2 B i t 1 51 41 31 21 11 0 9 8 7 6 5 4 3 2 1 0 Assignment (hex) 1 2 3 4 Meaning Firmware Version 1.23 Device ID 4 hex

7280_en_02 PHOENIX CONTACT 24

14 Formats for the Representation of Measured Values (IN2 to IN5)

14.1 Format: "IB IL" (Default Setting)

The measured value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit. Measured value representation in "IB IL" format (15 bits) This format supports extended diagnostics. Values > 8000hex and < 8100hex indicate an error. Following an error message in the status word (error bit), the following errors/messages are displayed in words IN2 to IN5: Significant Measured Values MSB LSB 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 SB Analog value SB Sign bit Input Data Word (hex) Errors

8001 Overrange

8002 Open circuit

8004 Measured value invalid

8020 Sensor and/or analog supply not present

8040 Module faulty

8080 Underrange

(Two's Complement) 0V t o 1 0 V UInput ±10 V UInput 0V t o 5 V UInput ±5 V UInput 0m A t o 20 mA IInput ±20 mA IInput 4m A t o 20 mA IInput hex dec V V V V mA mA mA FFFF -1 – -333.33 μV – -166.67 μV – -0.6667 μA– 8080 Underrange – < -10.837 – < -5.419 – < -21.6747 – 8002 Open circuit – – – – – – < +3.2

7280_en_02 PHOENIX CONTACT 25 Input Data Word (Two's Complement) R: 0 ... 3.2 kΩ RInput R: 0 ... 9.5 kΩ RInput Pt and Ni hex dec Ω Ω °C

8001 Overrange > 3200 > 10000 > Limit value

251C 9500 – 9500 – 03E8 1000 100.0 1000 +100.0 0000 0 ≤0 ≤00 FFFF -1 – – -0.1 FC18 -1000 – – -100.0

8080 Underrange – – < Limit value

For the limit values, please refer to "Limit Values for Temperature Measurement" on page 9. Output Data Word 0V t o 1 0 V UOutput ±10 V UOutput 0V t o 5 V UOutput ±5 V UOutput 0m A t o 20 mA IOutput ±20 mA IOutput 4m A t o 20 mA IOutput hex dec V V V V mA V mA 0000 0 0 0 0 0 0 0 +4.0 FFFF -1 0 -333.33 μV0- 1 6 6 . 6 7 μV0- 0 . 6 6 6 7 μA+ 4 . 0 C568 -15000 0 -5.0 0 -2.5 0 -10.0 +4.0 8AD0 -30000 0 -10.0 0 -5.0 0 -20.0 +4.0 8100 -32512 0 -10.837 0 -5.419 0 -21.6764 +4.0 80FF to 8000 without 8001, 8080, 8002 – HOLD HOLD HOLD HOLD HOLD HOLD HOLD 8080 Underrange 0 -10.837 0 -5.419 0 -10.837 HOLD

8002 Line break HOLD HOLD HOLD HOLD HOLD HOLD 0

7280_en_02 PHOENIX CONTACT 26

14.2 Format: "RT"

The measured value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit. Measured value representation in "RT" format (15 bits) Significant Measured Values MSB LSB 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 SB Analog value SB Sign bit Input Data Word 0 V to 10 V UInput ±10 V UInput 0V t o 5 V UInput ±5 V UInput 0m A t o 20 mA IInput ±20 mA IInput 4m A t o 20 mA IInput hex dec V V V V mA mA mA 0000 0 ≤ 00 ≤ 00 ≤ 00 4 . 0 FFFF -1 – -305.18 μV – -152.6 μV – -0.610 μA– Output Data Word 0V t o 1 0V UOutput ±10 V UOutput 0V t o 5 V UOutput ±5 V UOutput 0m A t o 20 mA IOutput ±20 mA IOutput 4m A t o 20 mA IOutput hex dec V V V V mA V mA 0000 0 ≤ 00 ≤ 00 ≤ 0 ≤ 0 +4.0 FFFF -1 0 -305.18 μV 0 -152.6 μV 0 -0.610 μA+ 4 . 0 8001 -32767 0 -10.0 0 -5.0 0 -20.0 +4.0

7280_en_02 PHOENIX CONTACT 27

14.3 Format: "S7-Compatible"

The measured value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit. Measured value representation in "S7-compatible" format Significant Measured Values Formula for Calculating the Measured Value from the Process Data Input Value for the 4 mA to 20 mA Measuring Range Measured value = PD IW x 0.0005787 mA + 4 mA PD IW = Process data MSB LSB 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 SB Analog value SB Sign bit Input Data Word 0 V to 10 V UInput ±10 V UInput 0V t o 5 V UInput ±5 V UInput 0m A t o 20 mA IInput ±20 mA IInput 4m A t o 20 mA IInput hex dec V V V V mA mA mA 0000 0 ≤ 00 ≤ 00 ≤ 00 + 4 . 0 FFFF -1 – -361.69 μV – -180.85 μV – -0.7234 μA +3.999422 8 0 0 0 L i n e b r e a k –––––– < + 1 . 1 8 5 2 8000 Underrange – < -11.759 – < -5.879 – < -23.516 – Example 1 PD IW 6C00 hex = 27648dec Value x resolution 27648 x 0.0005787 mA = 16 mA + 4 mA 16 mA + 4 mA = 20 mA Measured value 20 mA Example 2 PD IW F940 hex -> FFFFhex - F940hex + 1 = -1728dec Value x resolution -1728 x 0.0005787 mA = -1 mA + 4 mA -1 mA + 4 mA = 3 mA Measured value 3 mA

7280_en_02 PHOENIX CONTACT 28 Input Data Word (Two's Complement) R: 0 ... 3.2 kΩ RInput R: 0 ... 9.5 kΩ RInput Pt and Ni hex dec Ω Ω °C 7FFF Overrange > 3200 > 10000 > Limit value 251C 9500 – 9500 – 03E8 1000 100.0 1000 +100.0 0001 1 0.1 1 +0.1 0000 0 ≤0 ≤00 FFFF -1 – – -0.1 FC18 -1000 – – -100.0

8000 Underrange – – < Limit value

Output Data Word 0 V to 10 V UOutput ±10 V UOutput 0V t o 5 V UOutput ±5 V UOutput 0m A t o 20 mA IOutput ±20 mA IOutput 4m A t o 20 mA IOutput hex dec V V V V mA mA mA 7FFF to 7F00 Overrange 0 0 0 0 0 0 0 00 0 00 00 0 + 4 . 0 FFFF -1 0 -361.69 μV 0 -180.845 μV 0 -0.7234 μA +3.99942 E501 -6911 0 -2.4996 0 -1.2498 0 -4.99942 +0.578 μA E500 -6912 0 -2.5000 0 -1.2500 0 -5.0 0 AF00 -20736 0 -7.5000 0 -3.7500 0 -15.0 0 9400 -27648 0 -10.0000 0 -5.0000 0 -20.0 0 8100 -32511 0 -11.7589 0 -5.8800 0 -23.5157 0 80FF to 8000 Underrange 0 0 0 0 0 0 0

7280_en_02 PHOENIX CONTACT 29

14.4 Format: "Standardized Representation"

The data is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit. In this format, data is standardized to the measuring range and represented in such a way that it indicates the corresponding value without conversion. In this format one bit has the value of 1 mV or 1 μA. Measured value representation in "standardized representation" format This format supports extended diagnostics. Values > 8000hex and < 8100hex indicate an error. Following an error message in the status word (error bit), the following errors/messages are displayed in words IN2 to IN5: Significant Measured Values MSB LSB 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 SB Analog value SB Sign bit Input Data Word (hex) Errors

8020 Analog supply not present

Input Data Word 0 V to 10 V UInput ±10 V UInput 0V t o 5 V UInput ±5 V UInput 0m A t o 20 mA IInput ±20 mA IInput 4m A t o 20 mA IInput hex dec V V V V mA mA mA 8080 Underrange – < -10.837 – < -5.419 – < -21.6747 – 8 0 0 2 O p e n c i r c u i t –– –––– < + 3 . 2

7280_en_02 PHOENIX CONTACT 30 Input Data Word (Two's Complement) R: 0 ... 3.2 kΩ RInput R: 0 ... 9.5 kΩ RInput Pt and Ni hex dec Ω Ω °C 251C 9500 – 9500 – 03E8 1000 100.0 1000 +100.0 0000 0 ≤0 ≤00 FFFF -1 – – -0.1 FC18 -1000 – – -100.0 Output Data Word 0V t o 1 0 V UOutput ±10 V UOutput 0V t o 5 V UOutput ±5 V UOutput 0m A t o 20 mA IOutput ±20 mA IOutput 4m A t o 20 mA IOutput hex dec V V V V mA mA mA 7FFF to 54AB 0001 1 +1 mV +1 mV +1 mV +1 mV +1 μA+ 1 μA +4.001 0000 0 0 0 0 0 0 0 +4.0 FFFF -1 0 -1 mV 0 -1 mV 0 -1 μA+ 4 . 0 EC78 -5000 0 -5.0 0 -5.0 0 -5.0 +4.0 D8F0 -10000 0 -10.0 0 -5.419 0 -10.0 +4.0 B1E0 -20000 0 -10.837 0 -5.419 0 -20.0 +4.0 AB56 -21674 0 -10.837 0 -5.419 0 -21.674 +4.0 AB55 to 8100 80FF to 8000 without 8001, 8080, 8002 – H O L DH O L DH O L D H O L D H O L DH O L DH O L D 8080 Underrange 0 -10.837 0 -5.419 0 -21.674 HOLD

7280_en_02 PHOENIX CONTACT 31

15 Configuration

Module configuration is only required if the channels are not to be operated with the default values (see "Parameters for Configuration" on page 32). You can either configure the module via process data or via PCP and transmit analog values accordingly. If the module has been configured via PCP, subsequent configuration via process data is only possible if configuration via process data is permitted with the "Config Table" PCP object. To do this, in the "AO format, AI format, system bits" element set "Conf" bit = 1. As long as "Conf" = 0, the error bit is set in the status word when an attempt is made to configure via process data.

16 Configuration via Process Data

Five OUT process data words are available. The first output word represents the control word, the following words each refer to an analog channel. As confirmation for a control word action, the first input word contains a partial copy of the control word. For the device configuration, channel-specific parameter data is set in the relevant channel output words. Once configuration has been completed, and depending on the format set, the measured values in the corresponding input words are either transmitted to the controller board or to the computer.

16.1 Output Word OUT1 (Control Word) for Command Code 40xxhex (Configure Device)

B i t 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 Assignment Command code 40hex 000 PF AO format AI format Code (bin) PF (Peripheral Fault in the Event of Sensor Error)

0 Not permitted (default)

1 Permitted

Code (bin) AO Format

00 IB IL (15 bits) (default)

10 S7-compatible

11 Standardized representation

Code (bin) AI Format

7280_en_02 PHOENIX CONTACT 32

16.2 Output Words OUT2 to OUT5 (Configuration)

Each channel can be configured independently of the other channels. The first channel is configured via the second output word, the second channel via the third output word, etc. If the format "IB IL" is set, the error code "measured value invalid" is output during configuration. If the configuration is invalid, a corresponding error message is output in the status word. The configuration is stored in a volatile memory. For command 40xxhex, specify the parameters for the appropriate channels 1 to 4 in OUT2 to OUT5. The parameter words are only evaluated by this command. Configuration words for analog inputs and outputs: – "Wire" indicates the number of wires for a resistance measurement. It is only relevant for the "Linear R ...", hex to Ehex). – "AO reset behavior" indicates the status of the analog outputs in the event of an INTERBUS reset and following power up. The failsafe value must be specified retentively via the Config Table PCP object. – "AO output range" indicates the range for the analog outputs. – "AI filter" indicates the time for the digital filter. – "AI measuring range" indicates the range for the analog inputs. An error message is generated during configuration due to the following reasons: – A reserved value was used. – Current or voltage is configured for "AI measuring range" AND 3 or 4-wire is configured for "Wire". – Configuration has already been carried out via PCP. Parameters for Configuration The values displayed in bold are default settings. Bit 15 and bit 14 Bit 13 and bit 12 Bit 10 to bit 8 Bit 6 OUTx (x = 2 to 5) Byte Byte 0 Byte 1 B i t 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 Assignment Wire AO reset behavior Res. AO output range Res. AI filter AI measuring range Code (bin) Wire 00 2-wire (default) 01 3-wire 10 4-wire, 2-wire with connector compensation

11 Reserved

Code (bin) AO Reset Behavior

00 Hold (default)

01 Reset

10 Failsafe value

Code (bin) Code (hex) AO Output Range 000 0 0 V to 10 V (default) 001 1 ±10 V 010 2 0 V to 5 V 011 3 ±5 V 100 4 0 mA to 20 mA 101 5 ±20 mA 110 6 4 mA to 20 mA 111 7 Reserved Code (bin) AI Filter 0 4.5 ms (default) 1 1.1 ms

7280_en_02 PHOENIX CONTACT 33 Bit 5 to bit 0

16.3 Example for the Module Configuration via Process Data

All input channels are configured differently. Code AI Measuring Range Code AI Measuring Range (dec) (bin) (hex) (dec) (bin) (hex) 0 00 0000 0 0 V to 10 V (default) 9 00 1001 9 Pt 100 DIN 1 00 0001 1 ±10 V 10 00 1010 A Pt 500 DIN 2 00 0010 2 0 V to 5 V 11 00 1011 B Pt 1000 DIN 3 00 0011 3 ±5 V 12 00 1100 C Ni 100 DIN 4 00 0100 4 0 mA to 20 mA 13 00 1101 D Ni 1000 DIN 5 00 0101 5 ±20 mA 14 00 1110 E Ni 1000 L&S 6 00 0110 6 4 mA to 20 mA F - 3F Reserved 7 00 0111 7 Linear R: 0 Ω to 3200 Ω 8 00 1000 8 Linear R: 0 Ω to 9500 Ω For easy module configuration a function block can be downloaded at www.phoenixcontact.com PF AO Format AI Format Configuration Value OUT1 (hex) Not permitted IB IL IB IL xx00 OUTx Channel Wire AO Reset Behavior AO Output Range Filter Time AI Measuring Range Configuration Value OUTx (hex) OUT2 AI1/AO1 2-wire Hold 0 mA to 20 mA 4.5 ms 0 V to 10 V 0400 OUT3 AI2/AO2 2-wire Hold ±10 V 1.1 ms 0 mA to 20 mA 0144 OUT4 AI3 4-wire – – 4.5 ms Pt 100 DIN 8009 OUT5 AI4 2-wire with connector compensation – – 4.5 ms Pt 1000 DIN 800B Step Process Data Meaning

1 OUT1 = 0000 hex Ensures that the

2 Wait until

IN1 = 0000 hex Awaiting confirmation

3 OUT5 = 800B hex

OUT4 = 8009hex OUT3 = 0144hex OUT2 = 0400hex OUT1 = 4000hex Specified configuration

4 Wait until

IN1 = 4000hex Awaiting confirmation Step Process Data Meaning

5 OUT1 = 0000 hex Requesting the

6 Wait until

IN1 = 0000 hex Awaiting confirmation

7 OUT3 = analog value AO2

OUT2 = analog value AO1 OUT1 = 0100 hex Outputting analog values

8 Wait until

IN1 = 0100hex Awaiting confirmation

9 Measured value channel 1 = IN2,

..., Measured value channel 4 = IN5 OUT1 = 0100 hex Reading measured values

7280_en_02 PHOENIX CONTACT 34

17 Configuration via PCP

By default upon delivery, the device is configured according to the default settings (see "Parameters for Configuration" on page 32). In PCP mode, the device is configured with the "Config Table" object. Config Table Object Configure the device using this object. Object Description Element Value Range The "Configuration channel x" elements have the following structure: For the value ranges for the individual parameters, please refer to Section "Parameters for Configuration" on page 32. The "AO format, AI format, system bits" element has the following structure: Index Data Type N L Meaning Object Name Rights 0080hex Array of Unsigned 16 7 2 Device configuration Config Table rd/wr N: Number of elements rd: Read access permitted L: Length of an element in bytes wr: Write access permitted Object Config Table Access Read, write Data type Array of Unsigned 16 7 x 2 bytes Index 0080 hex Subindex 00 hex 01hex 02hex 03hex 04hex 05hex 06hex 07hex Write all elements Configuration channel 1 (AI1, AO1) Configuration channel 2 (AI2, AO2) Configuration channel 3 (AI3) Configuration channel 4 (AI4) AO format, AI format, system bits Failsafe value AO1 Failsafe value AO2 Length (bytes) 0E hex 02hex Subindex 00hex Subindex 01hex to 07hex Data Device configuration OUTx (x = 2 to 5) B i t 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 Assignment Wire AO reset Res. AO output range AI filter AI measuring range B i t 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 A s s i g n m e n t 0000 AO format A I f o r m a t 00000 PF AOV Conf

7280_en_02 PHOENIX CONTACT 35 For the value ranges for the "AO format" and "AI format" parameters, please refer to Section "Parameters for Configuration" on page 32. "PF" If bit 2 = 1, a peripheral fault is generated in the event of a sensor problem (overrange, underrange, open circuit). "AOV" If bit 1 = 1, the "Analog Out Values" object may be written. This specifies that analog values for AO1 and AO2 are specified via PCP and not via process data. "Conf" If bit 0 = 1, configuration via process data is permitted (command code 40xxhex). The format of the failsafe value must be the Inline format. If an invalid configuration is specified, a negative confirmation is generated with error message 08hex, 00hex or xx30hex. The low byte of the additional error code is 30hex (value is out of range), the high byte contains the number of the affected element. Example: Config Table is completely written with data (subindex 00) and the entry for channel 2 is invalid. In this case, the additional error code is equal to 0230hex.

18 PCP Communication

18.1 Object Dictionary

For information on PCP communication, please refer to the IBS SYS PCP G4 UM E and IBS PCP COMPACT UM E user manuals. Index Data Type N L Meaning Object Name Rights 0080hex Array of Unsigned 16 7 2 Device configuration Config Table rd/wr 0081hex Array of Unsigned 16 4 2 Input Data Analog In Values rd 0085hex Array of Unsigned 16 2 2 Output data Analog Out Values rd/wr 0018hex Record 6 17 Diagnostic status DiagState rd N: Number of elements rd: Read access permitted L: Length of an element in bytes wr: Write access permitted

7280_en_02 PHOENIX CONTACT 36

18.2 Object Description

Configure the device using this object. See "Config Table Object" on page 34. Analog In Values Object The elements of this object contain the analog values of the channels in the format that was selected for this channel. Object Description Analog Out Values Object The elements of this object specify the analog values of the output channels in the format that was selected for the relevant channel. Write access must be enabled in order to ensure error-free writing. To do this, in the "Config Table" object in element 5 set bit 1 (AOV) = 1. If write access is not enabled, a negative write confirmation will be generated with error message 08, 00, 0022hex (Service cannot be executed at present). Object Description Object Analog In Values Access Read Data type Array of Unsigned 16 4 x 2 bytes Index 0081 hex Subindex 00 hex 01hex 02hex 03hex 04hex Read all elements Analog value channel 1 (AI1) Analog value channel 2 (AI2) Analog value channel 3 (AI3) Analog value channel 4 (AI4) Length (bytes) 08 hex 02hex Subindex 00hex Subindex 01hex to 04hex Data Analog values of the channels (input data) Object Analog Out Values Access Read/write Data type Array of Unsigned 16 2 x 2 bytes Index 0085 hex Subindex 00 hex 01hex 02hex Read/write all elements Analog value channel 1 (AO1) Analog value channel 2 (AO2) Length (bytes) 04 hex 02hex Subindex 00hex Subindex 01hex to 02hex Data Analog values of the channels (output data)

7280_en_02 PHOENIX CONTACT 37 DiagState Object The elements of this object contain the current diagnostic status of the device. Object Description Object DiagState Access Read Data type Record Index 0018 hex Subindex 00 hex Read all elements 01hex Consecutive no. Unsigned 16 (2 bytes) 02hex Priority Unsigned 8 (1 byte) 03hex Channel Unsigned 8 (1 byte) 04hex Code Unsigned 16 (2 bytes) 05hex MoreFollows Unsigned 8 (1 byte) 06hex Text OctetString (10 bytes) Length (bytes) 11 hex 01hex 02hex 0Ahex Subindex 00hex Subindex 02hex, 03hex, 05hex Subindex 01hex, 04hex Subindex 06hex Data Diagnostic status of the device Meaning Possible Values Consecutive no. Unique, consecutive error number since the last power up reset or history reset 0 to 65535 Priority Priority of the message If Code = 0000 hex, Priority = 00hex otherwise Priority = 02hex Channel If Code = 0000 hex, Channel = 00hex otherwise Channel = 01hex to 04hex Code Error code 0000 hex: No error 8910hex: Overrange 8920hex: Underrange 7710hex: Cable break 5160hex: Power supply error 5010hex: Hardware fault MoreFollows 00 hex = No additional information is available for this error. 00hex Text The first 10 characters of the status message. Default: "Status OK" If Code = 0000hex, Text = "Status OK" otherwise text contains error-specific information

7280_en_02 PHOENIX CONTACT 38

19 Diagnostics

Error Table With Diagnostic Data and Status Indicators Error Type Diagnostic Data Status Indicators Sensor Supply Sensor supply failure or sensor supply voltage too low Message in the process data: Indication of error code 8020hex in the measured value (only for "IB IL" and "standardized representation" format) US LED is OFF, SF LED lights up red, E1 to E4 LEDs light up red Sensor supply short circuit M essage in the process data: Indication of error code 8020hex in the measured value (only for "IB IL" and "standardized representation" format) SF LED lights up red, Ex LED lights up red Analog Inputs Open circuit during temperature measurement or in the range from 4 mA to 20 mA Message in the process data: Indication of error code 8002hex in the measured value (only for "IB IL" and "standardized representation" format) Ex LED lights up red Analog Outputs Output value channel 1 ≥ 5% of measuring range final value LED 1 lights up yellow Output value channel 2 ≥ 5% of measuring range final value LED 2 lights up yellow General Voltage failure of the internal analog device supply (5 V and 15 V) Message in the process data: Indication of error code 8020hex in the measured value (only for "IB IL" and "standardized representation" format) Additional peripheral fault message sent to the control system Faulty configuration Message in the process data Module faulty (e.g., due to component failure) Message in the process data: Indication of error code 8040 hex in the measured value (only for "IB IL" and "standardized representation" format) Overrange of the measuring range Message in the process data: Indication of error code 8001hex in the measured value (only for "IB IL" and "standardized representation" format) Additional peripheral fault message sent to the control system, if this is permitted Underrange of the measuring range Message in the process data: Indication of error code 8080hex in the measured value (only for "IB IL" and "standardized representation" format) Additional peripheral fault message sent to the control system, if this is permitted In the event of a message in the process data, the error bit is always set.

7280_en_02 PHOENIX CONTACT 39

20 Channel Conversion Times a nd Process Data Update Time

The process data update time is determined from the sum of the channel conversion times for all four channels. The analog outputs must be maintained within these times. The conversion time of a channel is determined from the channel parameterization and combines the filter time plus special additional times. Channel conversion time = (Filter time + Time for resistance measurement + Measuring time for 4-wire connection) x 3-wire factor Example: Channel 1: Measuring range 0 V to 10 V, filter time = 4.5 ms Channel 2: Measuring range 0 mA to 20 mA, filter time = 1.1 ms Channel 3: Measuring range Pt 100, filter time = 4.5 ms, 4-wire Channel 4: Measuring range Pt 1000, filter time = 4.5 ms, 2-wire with connector compensation * 4-wire measuring time also applies for 2-wire with connector compensation Analog Conversion Time According to the Example Above: Figure 18 Analog conversion time according to the example above Filter Time Time for Resistance Measurement 4-Wire Measuring Time 3-Wire Factor Filter 1: 4.5 ms Filter 2: 1.1 ms 0.2 ms for all resistance measurements 1 ms, if resistor is connected in 4-wire technology 2 ms, if resistor is connected in 3-wire technology; otherwise 1 ms Channel Configuration [hex] Filter Time Time for Resistance Measurement 4-Wire Measuring Time* 3-Wire Factor Channel Conversion Time 1 0000 4.5 ms 0 ms 0 ms 1 4.5 ms 2 0044 1.1 ms 0 ms 0 ms 1 1.1 ms 3 8009 4.5 ms 0.2 ms 1 ms 1 5.7 ms 4 800B 4.5 ms 0.2 ms 1 ms 1 5.7 ms Process data update time = total of all channel conversion times 17 ms 2 4 68 10 12 14 16 7285B0210 Channel 2 Channel 1 Channel 3 Channel 4 ...Channel 1 18 20

7280_en_02 PHOENIX CONTACT 40

21 Behavior of the Analog Outputs in

the Event of INTERBUS Reset and Power Up Both analog outputs behave independently of each other.

22 Notes on Systematic and Random

Errors During Resistance and Temperature Measurement The extent of systematic and random errors (signal/noise ratio) is greatly influenced by the connection method and filter time selected. The lowest level of systematic and random deviations can be achieved by selecting 4-wire technology and a filter time of 4.5 ms.

22.1 Measures to Optimize Tolerances

– Set the filter time to 4.5 ms (default setting). – Reduce random errors through additional application filtering. – Minimize a large part of systematic errors through user-specific system calibration. – Short circuit unused RTD channels. – Increase the sensor grou nd (connect sensor ground, e.g., to a metal block). Attention: Connect only one end of the shielding. – For 2-wire connection, use the version with connector compensation. Event AO Reset Behavior Response INTERBUS reset Hold Analog value is held Reset If AO output range 4 mA to 20 mA is configured, 4 mA is output, otherwise 0 mA or 0 V is output Failsafe The failsafe value for the corresponding channel that is specified in the "Config Table" object is output Power up Hold Output of 0 V Reset 0 V or 0 mA Failsafe 0 V or 0 mA

7280_en_02 PHOENIX CONTACT 41

22.2 Connection Method

The contact resistance of the connections and the cable resistances have virtually no effect due to the 4-wire connection technology. Figure 19 RTD 4-wire connection

22.3 RTD 3-Wire Connection

With 3-wire technology, the effect of the cable resistance on the measured result in the terminal is minimized by multiple measuring of the temperature-related voltage and corresponding calculations. With this connection method, one cable can be eliminated. Figure 20 RTD 3-wire connection RTD 2-Wire Connection With Connector Compensation 2-wire technology is a more cost-effective connection method. The long U+ and U- cables to the sensor are no longer needed here. They are jumpered directly at the connector. The temperature-related voltage is not directly measured at the sensor and therefore not falsified by the two cable resistances RL. This connection method is ideal for sensors with high R0 (e.g., Pt 1000, Ni 1000). With 2-wire connection with connector compensation, minimized tolerances can be achieved through: – Parameterization of t he terminal on a 4-wire connection – Direct jumpering of the U+ and U- connections at the live measuring cables A larger conductor cross section and sensors with higher R0 further improve the tolerances of these connection versions. Figure 21 RTD 2-wire connection with connector compensation 1 2 I+ RES I- RES U- U+ RTD RL 7285A018 U- (I = 0 µA) RL U+ (I = 0 µA) 1 2 I+ RES I- RES U- U+ RTD RL RL 7285A017 U- (I = 0 µA) 1 2 I+ RES I- RES U- U+ RTD RL I+ 7280B011 RL

7280_en_02 PHOENIX CONTACT 42

22.4 Systematic Errors Duri ng Temperature Measurement With 2-Wire Technology

With 2-wire connection method, the cable resistances are in series for the sensor resistance and result in systematic measuring errors. This is described in greater detail below. Figure 22 Systematic temperature measuring error ΔT depending on the cable length l Curves depending on the cable cross section A (Measuring error valid for: copper cable χ = 57 m/Ωmm TA = 25°C and Pt 100 sensor) Figure 23 Systematic temperature measuring error ΔT depending on the cable cross section A (Measuring error valid for: copper cable χ = 57 m/Ωmm2, TA = 25°C, l = 5 m, and Pt 100 sensor) Figure 24 Systematic tem perature measuring error ΔT depending on the cable temperature TA (Measuring error valid for: copper cable χ =5 7m /Ωmm2, l = 5 m, A = 0.25 mm2, and Pt 100 sensor) All diagrams show that the increase in cable resistance causes the measuring error. A considerable improvement is made through the use of Pt 1000 sensors. Due to the 10-fold higher temperature coefficient α (α = 0.385 Ω/K for Pt 100 to α=3 . 8 5Ω/K for Pt 1000) the effect of the cable resistance on the measurement is decreased by factor 10. All errors in the diagrams above would be reduced by factor 10. Figure 22 clearly shows the effect of the cable length on the cable resistance and therefore on the measuring error. The solution is to use the shortest possible sensor cables. Figure 23 shows the effect of the cable cross section on the cable resistance. Cables with a cross section of less than 0.5 mm2 cause errors to increase exponentially. Figure 24 shows the effect of the ambient temperature on the cable resistance. This parameter does not play a great role and can hardly be influenced but it is mentioned here for the sake of completeness. (1) Temperature measurin g error for A = 0.14 mm (2) Temperature measurin g error for A = 0.25 mm2 (3) Temperature measurin g error for A = 0.50 mm2 /G30 /G2E /G30 /G33 /G2E /G30 /G36 /G2E /G30 /G39 /G2E /G30 /G31 /G32 /G2E /G30 /G31 /G35 /G2E /G30 /G30 /G2E /G30 /G32 /G2E /G35 /G35 /G2E /G30 /G37 /G2E /G35 /G31 /G30 /G2E /G30 /G31 /G32 /G2E /G35 /G31 /G35 /G2E /G30 /G31 /G37 /G2E /G35 /G32 /G30 /G2E /G30 /G4B /G6C /G6D /G35 /G37 /G35 /G35 /G31 /G30 /G31 /G34 /G28 /G31 /G29 /G28 /G32 /G29 /G28 /G33 /G29 /G44 /G54 0.0 1.0 2.0 3.0 4.0 5.0 6.0 K A mm 7285A022 /c68T K TA 0.0 0.5 1.0 1.5 2.0 2.5 -30 -20 -10 0 +10 +20 +30 +40 +50 +60 7285A023 /c68T

7280_en_02 43PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany Phone: +49 - 52 35 - 30 0 • Fax: +49 - 52 35 - 34 12 00 www.phoenixcontact.com The formula for calculating the cable resistance is as follows: Where: Since there are two cable resistances in the measuring system (forward and return), the value must be doubled. The absolute measuring error in Kelvin [K] according to DIN can be obtained for platinum sensors using the average temperature coefficient α (α =0 . 3 8 5Ω/K for Pt 100; α =3 . 8 5Ω/K for Pt 1000). © PHOENIX CONTACT 02/2007 RL Cable resistance in Ω RL20 Cable resistance at 20°C in Ω l Cable length in m χ Specific electrical resistance of copper in Ωmm2/m A Cable cross section in mm 2 0.0043 1/K Temperature coefficient for copper TA Ambient temperature (cable temperature) in °C /G52 /G4C /G20 /G3D /G31 /G4B /G78 /G20 /G28 /G20 /G31 /G20 /G2B /G20 /G30 /G2E /G30 /G30 /G34 /G33 /G20 /G20 /G20 /G20 /G20 /G78 /G20 /G54 /G41 /G29 /G52 /G4C /G20 /G3D /G20 /G20 /G20 /G20 /G20 /G20 /G52 /G4C /G32 /G30 /G20 /G20 /G20 /G20 /G78 /G20 /G28 /G20 /G31 /G20 /G2B /G20 /G30 /G2E /G30 /G30 /G34 /G33 /G20 /G20 /G20 /G20 /G20 /G78 /G20 /G54 /G41 /G29 /G20 /G6C /G63 /G20 /G78 /G20 /G41 /G31 /G4B