Features
– Supplying the L phase (230 V AC) – Diagnostic indicators – Protecting the L phase by an internal fuseWARNING: dangerous contact voltage Connecting and disconnecting the Inline terminals for the 230 V AC voltage range is only permitted when the power supply is disconnected! This data sheet is only valid in association with the IL SYS INST UM E user manual. Make sure you always use the latest documentation. It can be downloaded from the product at www.phoenixcontact.net/catalog. 7187_de_01 2011-06-14
IB IL 230 PWR IN/F-D (-PAC) 7187_de_01 PHOENIX CONTACT 2 2T a b l e o f c o n t e n t s
IB IL 230 PWR IN/F-D (-PAC) 7187_de_01 PHOENIX CONTACT 3 Description Type Order No. Pcs. / Pkt. Inline power terminal, complete with accessories (connector and labeling field), 230 V AC, with fuse and diagnostics IB IL 230 PWR IN/F-D-PAC 2878971 1 Inline power terminal, without accessories, 230 V AC, with fuse and diag- nostics IB IL 230 PWR IN/F-D 2878081 1 3O r d e r i n g d a t a Accessories Type Order No. Pcs. / Pkt. Connector set, for Inline input terminal blocks with AC voltage ( Plug/Adapter ) IB IL AC-PWR-IN-PLSET 2740180 1 Labeling field, width: 12.2 mm ( Marking ) IB IL FIELD 2 2727501 10 Insert strip for laser printer, lettering field: 62 x 10 mm ( Marking ) ESL 62X10 0809492 1 Replacement fuse ( Fuse ) SI 5X20 6,3 A T DIN 41662 2726104 10 Documentation Type Order No. Pcs. / Pkt. User manual, English, Automation terminals of the Inline product range IL SYS INST UM E - - Dimensions (nominal sizes in mm) Width 36.6 mm Height 119.8 mm Depth 71.5 mm Wide power terminal block 24.4 mm Wide end terminal block 12.2 mm
4 Technical data
140,5 119,8 71,5 General data Color Gray Weight 80 g Mounting type DIN rail Ambient temperature (operation) -25 °C ... 55 °C Ambient temperature (storage/transport) -25 °C ... 85 °C Permissible humidity (operation) 10 % ... 95 % (according to DIN EN 61131-2) Permissible humidity (storage/transport) 10 % ... 95 % (according to DIN EN 61131-2)
IB IL 230 PWR IN/F-D (-PAC) 7187_de_01 PHOENIX CONTACT 4 Air pressure (operation) 70 kPa ... 106 kPa (up to 2000 m above mean sea level) Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above mean sea level) Degree of protection IP20 Protection class I, IEC 61140, EN 61140, VDE 0140-1 General data Connection data Name Inline connectors Connection method Spring-cage connection Conductor cross section [AWG] 28 ... 16 Interface Interface Inline local bus Connection method Inline data jumper Power consumption Main circuit supply UM 230 V AC (nominal value) Peripherals voltage range 207 V AC ... 253 V AC (including all tolerances, including ripple) Power supply at UM 8 A (nominal value) Communications power UL 7.5 V DC (via voltage jumper) Current consumption from UL 25 mA Programming Data ID code (hex) BE ID code (dec.) 190 Length code (hex) C2 Length code (dec.) 194 Process data channel 2 Bit Input address area 2 Bit Output address area 0 Byte Parameter channel (PCP) 0 Byte Register length 2 Bit For the programming data/configuration data of other bus systems, please refer to the corresponding electronic device data sheet (e.g., GSD, EDS). PROFIBUS telegram data Required parameter data 1 Byte Need for configuration data 4 Byte Electrical isolation/isolation of the voltage areas 5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC , 50 Hz , 1 min 5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC , 50 Hz , 1 min
7.5 V supply (bus logic) / peripheral range 230 V AC 2500 V AC , 50 Hz , 1 min
7.5 V supply (bus logic) / peripheral range 230 V AC (routine test) 1200 V AC , 50 Hz , 1 min
Peripheral range 230 V AC / PE 500 V AC , 50 Hz , 1 min Output / Phase 500 V AC , 50 Hz , 1 min Approvals For the latest approvals, please visit www.phoenixcontact.net/catalog.
IB IL 230 PWR IN/F-D (-PAC) 7187_de_01 PHOENIX CONTACT 5
5 Internal circuit diagram
Figure 1 Internal wiring of the terminal points Key: UL+ UANA UL- Local bus IB IL AC ENDIB IL 230 PWR IN/2-F-D-PAC N L L OPC D E Optocoupler LED Protocol chip (Bus logic including voltage conditioning) Terminal point without metal contact Terminal point without metal contact with filler plugs Explanation for other used symbols has been provided in the IL SYS INST UM E user manu- al. OPC
IB IL 230 PWR IN/F-D (-PAC) 7187_de_01 PHOENIX CONTACT 6
6 Intended use
The terminal is only to be used within an Inline station in accordance with the specifications in the data sheet and IL SYS INST UM E user manual. Phoenix Contact accepts no liability when used for anything other than its intended pur- pose.
7 Local diagnostic indicators
Figure 2 Local diagnostic indicators Function identification Flashing white light AP o w e r t e r m i n a l BE n d t e r m i n a l LED Color Meaning D Green Diagnostics (bus and logic voltage) ER e d F u s e Red off Fuse OK Red off Fuse blown L Green Supply voltage 230 V AC Green OFF No supply voltage Green ON Supply voltage is available If there is no L phase or the fuse has blown or is missing, an I/O error message is generated for the higher-level control or computer system. A blown or missing fuse is indicated via both diagnostics displays. The LED E lights up and the green LED D flashes at 2 Hz. B L DE A D E L
IB IL 230 PWR IN/F-D (-PAC) 7187_de_01 PHOENIX CONTACT 7
8 Terminal point assignment
Figure 3 Terminal point assignment 9C o n n e c t i o n e x a m p l e Figure 4 Typical connection of the supply voltage
10 Installation and startup
Install the system according to the requirements of EN 50178! Only qualified personnel may work on low voltage area Inline terminals. Qualified personnel are people who, because of their educa- tion, experience and instruction and their knowledge of rele- vant standards, regulations, accident prevention and service conditions, have been authorized by those responsible for the safety of the plant, to carry out any required operations and who are able to recognize and avoid any possible dangers. (definitions for skilled workers according to EN 50110-1:1996). Terminal point Designa- tion Assignment Power terminal (A) Connector 1 All Not used Connector 2 (marked according to function) 1.1 / 2.1 Not used 1.2 / 2.2 L Supply points for the phase of the L supply; Terminal points bridged internally 1.3 / 2.3 N Neutral conductor connection; termi- nal points bridged internally
1.4 PE Protective conductor connection; the
contact is connected directly to the PE potential jumper. Ground the ter- minal via the PE connection! This en- sures protective earth ground con- nection of all terminals within this area when the 230 V AC area is cor- rectly established.
2.4 Not used
End clamp (B) Connector 3 All Not used L DE 1 2 1 2 1.1 1.2 1.3 1.4 2.1 2.2 2.3 2.4 A B WARNING: dangerous contact voltage Protect the 230 V AC supply via an external fuse! Strictly observe the instructions in the data sheet and the IL SYS INST UM E user manual during installation and startup. 1.2 2.2 1.3 2.3 1.4 2.4 1.1 2.1 1.2 2.2 1.3 2.3 1.4 2.4 1.1 2.1 1.2 2.2 1.3 2.3 1.4 2.4 1.1 2.1 L N
230 VA C
IB IL 230 PWR IN/F-D (-PAC) 7187_de_01 8PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00 PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300 www.phoenixcontact.com Installing the Inline station The maximum total current flowing through the potential jumpers is 8 A. If it is necessary to establish another voltage range behind the
230 V AC area, terminate the 230 V area with an end clamp
and begin the new voltage area with a new power terminal. Startup of an Inline station An Inline station may only be put into operation when it is com- pletely installed. That means: – all terminals must be properly snapped in with their con- nectors. – The station must be terminat ed with the end plate and the two end clamps.
11 Process data
WARNING: dangerous contact voltage Please be aware of dangerous voltages when working on circuits that do not meet SELV re- quirements. Connecting and disconnecting the Inline termi- nals for the 230 V AC voltage range is only per- mitted when the power supply is disconnected! When working on the terminals and wiring, al- ways switch off the supply voltage and ensure it cannot be switched on again. Failure to observe these instructions can lead to damage to health or even life-threatening injuries. WARNING: dangerous contact voltage in the event of ground faults (if for example, the FI switch is triggered or star point is "exposed") Only operate Inline terminals for 230 V AC volt- age range in grounded AC voltage networks. WARNING:multiple supplies are not per- mitted! The supply voltage may only be connected to the intended power terminal. The connecting cables of all actuators and sen- sors may only be connected to the Inline AC terminals. Do not use external busbars for group poten- tials! WARNING: Use the intended power connector for supply- ing the voltage. The full current carrying capacity is ensured by internal bridging of the terminal points (see connection assignment). Observe the specifications in the IL SYS INST UM E user manual on the low volt- age area. The input process data only maps the status of the fuse and the main voltage. (Byte.Bit) view 0.1 0.0 Assign- ment Phase L exists, fuse is OK 1 1 Phase L exists, fuse has blown or is missing Phase L does not exist, fuse has blown or is missing For the assignment of the illustrated (byte.bit) view to your INTERBUS control or computer system, please refer to the DB GB IBS SYS ADDRESS data sheet.