700-015485-0000 ADVANCEDENERGY
Document overview
- Manufacturer or author: Provided By www.digicamel.com(free datasheet download site)
- PDF pages: 6
Technical content
©2022 Advanced Energy Industries, Inc. Total Output Power 30 kW Input Voltage 360 to 456 VAC (3 phase, L-L) Output Voltage
48 VDC
987 x 448 x 86 mm (L x W x H) Operating Temperature O C to 40 O C AT A GLANCEAdvanced Energy's Artesyn introduces the 30 kW stand-alone Power Shelf, single voltage 48 VDC output, powered from three-phase AC line. The Power Shelf sits in a 2RU high slot in a EIA 19” rack, which hosts twelve power modules with the outputs connected in parallel. Each module is an AC/DC power converter rated at 3000 W,
48 VDC of nominal output power, hot-swappable, accurate
current sharing and is self-cooled. The shelf will power the IT system through the OCP compatible busbar. ARTESYN
48 V 30 KW EIA 19"
30 kW (10 + 2) Redundancy KEY FEATURES 30 kW at 48 V with 10 + 2 redundancy Highly accurate droop + active current sharing Houses 12 x 3000 W (10 + 2) power modules and a removable shelf controller Very high efficiency EMC / SAFETY COMPLIANCE EN61000 / IEC61000 applicable standards for Emissions & Immunity requirements UL/CSA 62368-1 UL94/V-0
2 advancedenergy.com
48 V 30 kW EIA 19" POWER SHELF
Conditions Min Typ Max Unit Input Voltage (3 Phase, L-L) All 360 400/415 456 VAC Input Current 100% load (Max current for each AC input connector) - - 30 A Input AC Frequency All 45 50/60 65 Hz Output Specifications Conditions Min Typ Max Unit Output Current All - - 618 A Ripple & Noise 20 MHz bandwidth - - 500 mVpp Set Point 20% Load 49.55 49.60 49.65 VDC V O Dynamic Response Peak Deviation Dynamic load: 50 to 10 kHz Duty cycle: 10% to 90% Slew rate: 1A/us 10% to 60% load step 50% to 100% load step Vpp Vpp Power Distribution Loss 100% Load - - 50 W ENVIRONMENTAL SPECIFICATIONS Temperature Range Operational: 0 to +40 °C; Non-operational: -40 to +70 °C. PSU is able to start at -10°C of ambient temperature. Humidity Operational: 10% to 85% non-condensing; Non-operational: 10% to 95% non-condensing Altitude Operational: 2000 m; Non-operational: 15200 m Shock Operating: 5 G, 11 ms half sine pulses. 3 pulses in each sense Non-operating: 12 G, 11 ms half sine pulses. 3 pulses in each sense Vibration Operating vibration: 0.25 G zero to peak. Frequency is 5 to 500 Hz, 0.25 oct/min in each of three mutually perpendicular axes. 3 sweeps from 5 to 500 to 5 Hz in each axis. Non-operating sine sweep vibrations: 5 to 500 Hz @ 0.5 G at 0.5 octave/min; dwell 15 min at each of 3 resonant points. Non-operating random vibration: 5 Hz @ 0.01 g/Hz to 20 Hz @ 0.02 g/Hz (slope up); 20 to 500 Hz @ 0.02 g/Hz (flat); Input acceleration = 3.13 gRMS; 10 minutes per axis for 3 axis. RELIABILITY Calculated MTBF The PSU meet a calculated MTBF of at least 100K hours at 90% confidence level, 40°C ambient temperature, 230 Vac input voltage, and 75% load per Belicore RPP . The fan is not included in the calculation. Demonstrated MTBF The PSU meet a demonstrated MTBF of minimum 250K hours at 90% confidence level, 40°C of ambient temperature and 75% load. Life The PSU have a minimum service life of 5 years (24 hours/day, full load, 230 Vac, 40°C of ambient temperature).
advancedenergy.com 3 The power shelf enclosure is mounted to the front rack mount ears using standard EIA-310 19” rack mounting screw patterns. It sits upon supplied 1.2 mm thick shelf flanges which are pre-mounted into the rack. Shelf Mechanical Drawing
4 advancedenergy.com
advancedenergy.com 5 Output / Bus Bar Interface The power shelf mates with the 48 V bus bars which are mounted to the rack. The output bus bars use slots to slide into the clinch studs that are mounted to the vertical bus bars. The busbars and power shelf to busbar interface are defined by using the lower surface of the lowest square mount hole as DATUM A. Also, the front surface of the rack mount posts (where the server “ears” contact) are DATUM B. MECHANICAL
ORDERING INFORMATION
Model Input Output Description 700-015485-0000 1 Phase AC, 180 to 305 VAC, 50 to 60 Hz 48 V 62 A 48 V, 3 kW, ATS PSU 700-015496-0000 3 Phase AC, 200/480 V, 50 to 60 Hz 48 V 618 A 48 V, 30 kW, EIA 19 Inch Power Shelf 700-015499-0000 SMC Note 1 - PSUS are related products (not covered by this data sheet). Refer to PSU data sheet.
ENG - 48 V 30 kW EIA 19" POWER SHELF - 12.07.22 For international contact information, visit advancedenergy .com. powersales@aei.com (Sales Support) productsupport.ep@aei.com (Technical Support) +1 888 412 7832 ABOUT ADVANCED ENERGY Advanced Energy (AE) has devoted more than three decades to perfecting power for its global customers. AE designs and manufactures highly engineered, precision power conversion, measurement and control solutions for mission-critical applications and processes. Our products enable customer innovation in complex applications for a wide range of industries including semiconductor equipment, industrial, manufacturing, telecommunications, data center computing, and medical. With deep applications know-how and responsive service and support across the globe, we build collaborative partnerships to meet rapid technological developments, propel growth for our customers, and innovate the future of power. TRUST Specifications are subject to change without notice. Not responsible for errors or omissions. ©2022 Advanced Energy Industries, Inc. All rights reserved. Advanced Energy®, and AE® are U.S. trademarks of Advanced Energy Industries, Inc.