© PHOENIX CONTACT - 03/20076885_en_05 AUTOMATIONWORX ILB DN 24 DI16 DO16 Data Sheet
Description
The ILB DN 24 DI16 DO16 module is designed for use within a DeviceNet™ network. It is used to acquire and output digital signals. DeviceNet™ Features – I/O peer-to-peer communication – Direct peer-to-peer communication – Consistent configuration – Faulted node recovery – Baud rates: 125 kbaud, 250 kbaud, 500 kbaud – I/O slave messages: Polling, cyclic transmission, change of state (COS), bit strobing Input Features – Connections for 16 digital sensors – Connection of sensors in 2 and 3-wire technology – Maximum permissible load current per sensor: 125 mA – Maximum permissible load current from the sensor supply: 2.0 A – Diagnostic and status indicators Output Features – Connections for 16 digital actuators – Connection of actuators in 2 and 3-wire technology – Nominal current per output: 0.5 A – Total current of all outputs: 8 A – Short-circuit and overload protected outputs – Diagnostic and status indicators Inline Block IO Module for DeviceNet™ With 16 Digital Inputs and 16 Digital Outputs Please refer to the "Mounting and Removing Inline Block IO Modules" application note (see "Ordering Data" on page 2). Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com. Here you will also find the current EDS file. A conversion table is available on the Internet at
6885_en_05 PHOENIX CONTACT 2 Ordering Data Product Description Type Order No. Pcs./Pkt. Inline Block IO module for DeviceNet™ with 16 digital inputs and 16 digital outputs ILB DN 24 DI16 DO16 2862602 1 Accessories: Connector Description Type Order No. Pcs./Pkt. TWIN-COMBICON connector for bus connection TM STBP 2,5/ 5-STF-5,08 GNAU CP 2862576 1 Accessories: Connectors as Replacement Item Description Type Order No. Pcs./Pkt. Connector for the supply (color print) IB IL SCN-PWR IN-CP 2727637 5 Connector, with color print, for digital 4-channel or 16-channel Inline output terminals IB IL SCN-12-OPC 2727624 10 Connector, with color print, for digital 4-channel or 16-channel Inline input terminals IB IL SCN-12-IPC 2727611 10 Accessories: Other Description Type Order No. Pcs./Pkt. Recommended end clamp; placed both to the right and left of the module to secure it on the DIN rail CLIPFIX 35-5 3022276 50 Documentation Description Type Order No. Pcs./Pkt. "Mounting and Removing Inline Block IO Modules" application note AH ILB INSTALLATION 9014931 1 "Configuring a DeviceNet™ System Using Devices in the Fieldline Product Range" user manual FLS FLM DN SYS PRO UM E 2699082 1 "Addressing of 16-Channel ILB Modules" application note AH ILB 24 DI/DO 16 ADDRESS 9014962 1
6885_en_05 PHOENIX CONTACT 3 Technical Data Housing Dimensions Figure 1 Housing dimensions of the module (dimensions in mm) General Data Housing dimensions with connectors (width x height x depth) 156 mm x 55 mm x 141 mm Weight 500 g, approximately (with connectors) Operating mode Process data mode with 4 bytes Transmission speed 125 kbaud, 500 kbaud Type of sensor and actuator connection 2 and 3-wire technology 120 141 156 6885A003 Ambient Conditions Regulations Developed according to VDE 0160/EN 50178/IEC 62103, UL 508 Ambient temperature (operation) -25°C to +60°C Ambient temperature (storage/transport) -25°C to +85°C Humidity (operation/storage/transport) 10% to 95% according to EN 61131-2 Air pressure (operation) 80 kPa to 108 kPa (up to 2000 m above sea level) Air pressure (storage/transport) 66 kPa to 108 kPa (up to 3500 m above sea level) Degree of protection according to IEC 60529 IP20 Class of protection Class 3 according to VDE 0106/IEC 60536 Air and creepage distances According to DIN VDE 0110/IEC 60664, IEC 60664A, DIN VDE 0160/EN 50178/IEC 62103 Housing material Plastic, PVC-free, PBT, self-extinguishing (V0) Pollution degree according to EN 60664-1/IEC 60664-1, EN 61131-2/IEC 61131-2 2; condensation not permitted during operation Surge voltage class II
6885_en_05 PHOENIX CONTACT 4 Electrical Isolation/Isolation of the Voltage Areas Test Distance Test Voltage DeviceNet™ / I/O 500 V AC, 50 Hz, 1 min DeviceNet™ / functional earth ground 500 V AC, 50 Hz, 1 min I/O / functional earth ground 500 V AC, 50 Hz, 1 min Mechanical Requirements Vibration test, sinusoidal vibrations according to EN 60068-2-6/IEC 60068-2-6 5g load, 2.5 hours in each space direction Shock test according to EN 60068-2-27/IEC 60068-2-27 25g load for 11 ms, half sinusoidal wave, 3 shocks in each space direction and orientation Broadband noise according to EN 60068-2-64/IEC 60068-2-64 0.78g load, 2.5 hours in each space direction Conformance With EMC Directive 89/336/EEC Noise Immunity Test According to EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2 IEC 61000-4-2 Criterion B 6 kV contact discharge 8 kV air discharge Electromagnetic fields EN 61000-4-3 IEC 61000-4-3 Criterion A Field strength: 10 V/m Fast transients (burst) EN 61000-4-4/ IEC 61000-4-4 Criterion B Remote bus: 2 kV Power supply: 2 kV I/O cables: 2 kV Criterion A All interfaces: 1 kV Surge voltage EN 61000-4-5 IEC 61000-4-5 Criterion B DC supply lines: ±0.5 kV/±1.0 kV (symmetrical/asymmetrical) Signal cables: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical) Conducted interference EN 61000-4-6 IEC 61000-4-6 Criterion A Test voltage 10 V Noise Emission Test According to EN 61000-6-4 Noise emission of housing EN 55011 Class A Interface DeviceNet™ interface RS-485; COMBICON connector; shielding directly connected with functional earth ground
24 V Module Supply
Tolerance 11 V DC to 25 V DC according to the ODVA specification Ripple ±5% according to EN 61131-2 Permissible range 11.0 V DC to 30.0 V DC Current consumption at UL 25 mA Safety equipment Surge protection and protection against polarity reversal Connection Via power connectors
6885_en_05 PHOENIX CONTACT 5 Sensor and Actuator Supply; US and UA Nominal value 24 V DC Tolerance -15%/+20% according to EN 61131-2 Ripple ±5% according to EN 61131-2 Permissible range 19.2 V DC to 30.0 V DC Current consumption at US 2 A Current consumption at UA1 and UA2 2 x 4 A Safety equipment for the sensor supply Surge, overload and short-circuit protection Safety equipment for the actuator supply Surge protection Connection Via power connectors
24 V Module Supply (Continued)
Connection method for actuators 2 and 3-wire technology Nominal output voltage UOUT 24 V DC Differential voltage at Inom ≤ 1 V Nominal current Inom per channel 0.5 A Total current 2 x 4 A Protection Short-circuit and overload protection Nominal load Ohmic 48 Ω/12 W Lamp 12 W Inductive 12 VA (1.2 H, 50 Ω) Switching frequency with nominal inductive load 0.5 Hz (1.2 H, 50 Ω), maximum Overload response Auto restart Response with inductive overload Output may be damaged Reverse voltage protection against short pulses Protected against reverse voltages Resistance to permanently applied reverse voltages Protected against reverse voltages, permissible current 2 A, maximum Validity of output data after connecting the 24 V supply voltage (power up) 5 ms, typical Response upon power down The output follows the supply voltage without delay. Limitation of the voltage induced on circuit interruption -41.0 V One-time unsolicited energy 1 J, maximum Protective circuit type Integrated fr ee running circuit in the output chip Overcurrent shutdown 0.7 A, minimum Maximum output current when switched off 10 µA When not loaded, a voltage can be measured even at an output that is not set.
6885_en_05 PHOENIX CONTACT 6 Digital Inputs Number 16 Connection method for sensors 2 and 3-wire technology Input design According to EN 61131-2 Type 1 Definition of switching thresholds Maximum low-level voltage U Lmax < 5 V Minimum high-level voltage UHmin > 15 V Common potentials Sensor supply U S, ground Nominal input voltage UIN 24 V DC Permissible range -30 V < U IN < +30 V DC Nominal input current for UIN 5 mA, typical Current flow Linear in the range 1 V < U IN < 30 V Delay time ≤ 500 µs Permissible cable length to the sensor 100 m Use of AC sensors AC sensors in the voltage range < UIN are limited in application Power Dissipation Formula to Calculate the Power Dissipation of the Electronics Where PTOT Total power dissipation of the module IS Current from the sensor supply i Index n Number of set outputs (n = 1 to 16) ILi Load current of the output i j Index m Number of set inputs (m = 1 to 16) P = 1.92 W + (0.0 4W+I x 0.28 ) + 0.125 WTOT Li/c83/c87 /c83 + I x 0.06S /c87 i=1 n j=1 m Limitation of Simultaneity, Derating No limitation of simultaneity, no derating Approvals For the latest approvals, please visit www.download.phoenixcontact.com.
6885_en_05 PHOENIX CONTACT 7 Internal Circuit Diagram Figure 2 Internal wiring of the terminal points /G38 /G78 /G31 /G36 /G78 /G4F /G55 /G54 /G31 /G36 /G78 /G49 /G4E /G38 /G78 /G38 /G78 /G38 /G78 /G55 /G41 /G31 /G55 /G41 /G32 /G44 /G4F /G31 /G2E /G2E /G2E /G38 /G44 /G4F /G39 /G2E /G2E /G31 /G36 /G44 /G49 /G31 /G2E /G2E /G2E /G38 /G44 /G49 /G39 /G2E /G2E /G31 /G36 /G55 /G4C /G55 /G53 /G32 /G34 /G20 /G56 /G20 /G35 /G20 /G56 /G20 /G49 /G4F /G4E /G54 /G44 /G65 /G76 /G69 /G63 /G65 /G4E /G65 /G74 /G4D /G44 /G44 /G4E /G36 /G38 /G38 /G35 /G41 /G30 /G30 /G32 Key: LED DeviceNet™ protocol chip (bus logic) Power supply unit with electrical isolation Optocoupler Short-circuit-proof output Short-circuit-proof sensor supply /G44 /G4E
6885_en_05 PHOENIX CONTACT 8 Local Diagnostic and Status Indicators Figure 3 Diagnostic and status indicators of the ILB DN 24 DI16 DO16 module Designation Color Meaning BUS NT Red/green LED Network status ON (green) Module online, connection established. Group 2 devices are assigned to a master. ON (red) Error that prevents communication with the network (e.g., bus offline or double device ID). Flashing (green) Device online, connections not established. Device has finished the "Dup_MAC_ID" test but has not established connections to other nodes. Group 2 devices are not assigned to a master. Flashing (red) One or more connections are in timeout state. Flashing (red-green) N etwork access error OFF Device not online. Device has not yet finished the "Dup_MAC_ID" test. Device is not supplied with voltage. /G4E /G54 /G4D /G44 /G49 /G4F /G31 /G32 /G33 /G34 /G45 /G4F /G31 /G31 /G32 /G33 /G34 /G4F /G32 /G31 /G32 /G33 /G34 /G4F /G33 /G45 /G31 /G32 /G33 /G34 /G4F /G34 /G50 /G57 /G52 /G31 /G55 /G4C /G55 /G53 /G55 /G41 /G31 /G55 /G41 /G32 /G50 /G57 /G52 /G32 /G31 /G32 /G33 /G34 /G45 /G49 /G31 /G31 /G32 /G33 /G34 /G49 /G32 /G31 /G32 /G33 /G34 /G49 /G33 /G31 /G32 /G33 /G34 /G49 /G34 /G42 /G55 /G53 /G50 /G57 /G52 /G4F /G55 /G54 /G49 /G4E /G36 /G38 /G38 /G35 /G41 /G30 /G30 /G35
6885_en_05 PHOENIX CONTACT 9 IO Red/green LED I/O status (input/output) ON (green) One or more outputs are active, no error state is present. ON (red) Error parameterization due to undervoltage or overload at US Flashing (green) Error parameterization due to undervoltage at +24 V DC or at UA Flashing (red) Inputs and outputs mainta in their state despite error message. Error parameterization is not active. Error state detected due to undervoltage at +24 V DC or UA. Flashing (red-green) Baud rate setting/detection (autobaud) OFF No output is active, no error state is present. MD Red/green LED Device status (module diagnostics) ON (green) Normal operation ON (red) Unrecoverable error Flashing (green) – Device not c onfigured, or device configuration not complete or faulty – Device in standby mode Flashing (red) Recoverable error Flashing (red-green) Selftest OFF No supply voltage PWR US Green Sensor supply UL Green 24 V communications power UA1 Green Actuator supply 1 (connector 3 and connector 4 for actuators) UA2 Green Actuator supply 2 (connector 5 and connector 6 for actuators) OUT E Red Short circuit or overload at one of the outputs 1 - 4 Yellow Status indica tors of the outputs IN E Red Short circuit or overload of the sensor supply 1 - 4 Yellow Status indicators of the inputs Designation Color Meaning The NT, IO and MD LEDs may flash green and red at the same time. If the error LED (E) of a group of 8 outputs is on (e.g., connector 3 and connector 4), this indicates that a short circuit or overload is present at one or more of the outputs in this group. Default setting of the error parameterization: – All outputs are deactivated. – All inputs remain unchanged.
6885_en_05 PHOENIX CONTACT 11 Connecting the Supply, Actuators, and Sensors Figure 6 Terminal point assignment of Inline connectors Terminal Point Assignment of Power Connectors (Connectors 1 and 2 in Figure 6) /G31 /G2D /G32 /G31 /G32 /G31 /G32 /G33 /G34 /G31 /G32 /G33 /G34 /G31 /G2E /G31 /G31 /G2E /G32 /G31 /G2E /G33 /G31 /G2E /G34 /G32 /G2E /G31 /G32 /G2E /G32 /G32 /G2E /G33 /G32 /G2E /G34 /G33 /G2D /G31 /G30 /G31 /G32 /G31 /G32 /G33 /G34 /G31 /G32 /G33 /G34 /G35 /G36 /G35 /G36 /G31 /G2E /G31 /G31 /G2E /G32 /G32 /G2E /G31 /G32 /G2E /G32 /G31 /G2E /G33 /G32 /G2E /G33 /G31 /G2E /G34 /G32 /G2E /G34 /G31 /G2E /G35 /G32 /G2E /G35 /G31 /G2E /G36 /G32 /G2E /G36 /G36 /G38 /G38 /G35 /G41 /G30 /G30 /G36 Terminal Point Assignment Connector 1 (PWR 1) 1.1, 2.1 24 V sensor supply US 1.2, 2.2 24 V communications power UL, (voltage for module test, not intended for use within the DeviceNet™ network) 1.3, 2.3 GND 1.4, 2.4 FE Connector 2 (PWR 2) 1.1, 2.1 24 V actuator supply UA1, UA2 1.2, 2.2 24 V communications power UL, (voltage for module test, not intended for use within the DeviceNet™ network) 1.3, 2.3 GND 1.4, 2.4 FE If the module is used in a DeviceNet™ network, UL must be connected to the COMBICON connector. Therefore, connect UL to the COMBICON connector at pin V+ and pin V-. The connection options at Inline connectors 1 and 2 are designed for test purposes only. The terminal points can have a total current of 8 A per terminal point. The maximum current carrying capacity of 8 A must not be exceeded. If the total output current in your application is > 8 A, supply the module via a minimum of two terminal points connected in parallel. The supply points have the same ground potential. All ground supplies on a module are electrically connected with one another. The communications power is also electrically connected via all contacts. In this way, it can supply all potentials with just one supply without the need for additional terminals, see "Connection Example" on page 13.
6885_en_05 PHOENIX CONTACT 12 Terminal Point Assignment of Output Connectors (Connectors 3 to 6 in Figure 6 on page 11) Terminal Point Assignment of Input Connectors (Connectors 7 to 10 in Figure 6 on page 11) Terminal Point Assignment Connector 3 (O1) Connector 4 (O2) Connector 5 (O3) Connector 6 (O4) Terminal Point Assignment Connector 7 (I1) Connector 8 (I2) Connector 9 (I3) Connector 10 (I4)
6885_en_05 PHOENIX CONTACT 13 Connection Example Figure 7 Connection example /G31 /G32 /G31 /G32 /G33 /G34 /G31 /G32 /G33 /G34 /G35 /G36 /G35 /G36 /G31 /G32 /G31 /G32 /G33 /G34 /G31 /G32 /G33 /G34 /G35 /G36 /G35 /G36 /G31 /G32 /G31 /G32 /G33 /G34 /G31 /G32 /G33 /G34 /G35 /G36 /G35 /G36 /G31 /G32 /G31 /G32 /G33 /G34 /G31 /G32 /G33 /G34 /G35 /G36 /G35 /G36 /G31 /G32 /G31 /G32 /G33 /G34 /G31 /G32 /G33 /G34 /G35 /G36 /G35 /G36 /G31 /G32 /G31 /G32 /G33 /G34 /G31 /G32 /G33 /G34 /G35 /G36 /G35 /G36 /G31 /G32 /G31 /G32 /G33 /G34 /G31 /G32 /G33 /G34 /G35 /G36 /G35 /G36 /G31 /G32 /G31 /G32 /G33 /G34 /G31 /G32 /G33 /G34 /G35 /G36 /G35 /G36 /G31 /G32 /G31 /G32 /G33 /G34 /G31 /G32 /G33 /G34 /G2B /G2D /G55 /G41 /G32 /G4F /G55 /G54 /G20 /G36 /G4F /G55 /G54 /G20 /G31 /G36 /G2B /G32 /G34 /G20 /G56 /G49 /G4E /G20 /G31 /G35 /G2B /G32 /G34 /G20 /G56 /G49 /G4E /G20 /G31 /G34 /G31 /G32 /G31 /G32 /G33 /G34 /G31 /G32 /G33 /G34 /G20 /G20 /G55 /G53 /G55 /G41 /G31 /G2B /G44 /G65 /G76 /G69 /G63 /G65 /G4E /G65 /G74 /G20 /G31 /G20 /G20 /G20 /G20 /G20 /G20 /G20 /G32 /G20 /G20 /G20 /G20 /G20 /G20 /G20 /G33 /G20 /G20 /G20 /G20 /G20 /G20 /G20 /G34 /G20 /G20 /G20 /G20 /G20 /G20 /G20 /G35 /G20 /G20 /G20 /G20 /G20 /G20 /G20 /G36 /G20 /G20 /G20 /G20 /G20 /G20 /G20 /G37 /G20 /G20 /G20 /G20 /G20 /G20 /G20 /G38 /G20 /G20 /G20 /G20 /G20 /G20 /G20 /G20 /G39 /G20 /G20 /G20 /G20 /G20 /G20 /G20 /G20 /G31 /G30 /G36 /G38 /G38 /G35 /G41 /G30 /G31 /G30 If the module is used in a DeviceNet™ network, UL must be connected to the COMBICON connector. Therefore, connect UL to the COMBICON connector at pin V+ and pin V-. The connection options at Inline connectors 1 and 2 are designed for test purposes only (see "Terminal Point Assignment of Power Connectors (Connectors 1 and 2 in Figure 6)" on page 11). The numbers above the module illustration identify the connector slots. The module has an FE spring (metal clip) on the bottom of the electronics base. This spring creates an electrical connection to the DIN rail. Use grounding terminals to connect the DIN rail to protective earth ground. The module is grounded when it is snapped onto the DIN rail. To ensure reliable functional earth grounding of the module even when the DIN rail is dirty or the metal clip is damaged, Phoenix Contact also recommends grounding the module via one of the FE terminal points.
6885_en_05 PHOENIX CONTACT 14 Device Data Process Data Assignment of Terminal Points to the OUT Process Data Word (Slots 3 to 6) Assignment of Terminal Points to the IN Process Data Word (Slots 7 to 10) ID number 120 hex Input address area 4 bytes Output address area 4 bytes Input Address Area (Produced Process Data) Byte 0 (inputs) Byte 1 (inputs) Byte 2 (reading back output byte 0) Byte 3 (reading back output byte 1) Output Address Area (Consumed Process Data) Byte 0 Byte 1 Reserved Reserved Please refer to the application note for addressing 16-channel ILB modules. The documentation can be downloaded at www.download.phoenixcontact.com. Here you will also find the current EDS file. (Word.bit) view Word Word 0 B i t 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 (Byte.bit) view Byte Byte 0 Byte 1 B i t 7654321076543210 Module Slot 4 (O2) 3 (O1) 6 (O4) 5 (O3) Status indicator Slot 4 (O2) 3 (O1) 6 (O4) 5 (O3) L E D 4321432143214321 (Word.bit) view Word Word 0 B i t 1 51 41 31 21 11 0 9 8 7 6 5 4 3 2 1 0 (Byte.bit) view Byte Byte 0 Byte 1 B i t 7654321076543210 Module Slot 8 (I2) 7 (I1) 10 (I4) 9 (I3) Status indicator Slot 8 (I2) 7 (I1) 10 (I4) 9 (I3) L E D 4321432143214321
6885_en_05 PHOENIX CONTACT 15 Diagnostic Data Mapping of Diagnostic Data in DeviceNet™ (Class 1, Attribute 5) Class 102, Attribute 103 (Error Information) Diagnostic Data Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Byte 0 Undervoltage US Initiator supply
24 V supply voltage
An error is indicated in class 1, attribute 5 when the respective bit value is "1". (Byte.bit) view Byte Byte 0 Bit 7 6 5 4 3 2 1 0 Device Error 0: NMV has been re-initialized (possibly due to a hardware fault). 1: NMV has been initialized correctly with a corresponding parameterization at Phoenix Contact. Reserved U S failure US overload Actuator supply failure Short circuit of digital outputs Communications power failure at COMBICON connector Communications power failure at Inline connector An error is indicated in class 102, attribute 103 when the respective bit value is "0".
6885_en_05 PHOENIX CONTACT 16 Error Table With Diagnostic Data and Status Indicators The output behavior in the event of an error is parameterized using the "Discrete Output Point Object" (09dec, 09hex)(DOP). Outputs are reset by default. Attributes of the Connection Object (05dec, 05hex) Class The Connection Object class describes the individual connection types. The following tables have been taken from the ODVA specification for DeviceNet™. Attributes of the Connection Object Class Error Type Diagnostic Data Status Indicators Sensor voltage US too low Class 102, attribute 103 Byte 0 bit 5 is set to "0" US LED is off. IO LED is red. Actuator supply UA1 or UA2 too low Class 102, attribute 103 Byte 0 bit 3 is set to "0" UA1 or UA2 LED is off. IO LED flashes green or red if no error parameterization is activated. Short circuit of a sensor supply Class 102, attribute 103 Byte 0 bit 4 is set to "0" E LED of the sensor supply is red. IO LED is red. Short circuit of a digital output Class 102, attribute 103 Byte 0 bit 2 is set to "0" E LED of the affected output group is red. IO LED is green. For additional information, please refer to the FLS FLM DN SYS PRO UM E user manual (see "Ordering Data" on page 2). Attribute Requirement Attribute Name Type Short Description (According to ODVA)
1 Required State USINT State of the object
2 Required instance_type USINT Indicates either I/O or Messaging
3 Required transportClass_trigger BYTE D efines behavior of the Connection
4 Required produced_
connection_id UINT Placed in CAN Identifier Field when the Connection transmits
5 Required consumed_
connection_id UINT CAN Identifier Fiel d value that denotes message to be received
6 Required initial_comm_
BYTE Defines the Message Group(s) across which productions and consumptions associated with this Connection occur
7 Required produced_
connection_size UINT Maximum number of bytes transmitted across this Connection
8 Required consumed_
connection_size UINT Maximum number of by tes received across this Connection
6885_en_05 17PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany Phone: +49 - 52 35 - 30 0 • Fax: +49-(0) 5235-3-4 12 00 www.phoenixcontact.com © PHOENIX CONTACT 03/2007
9 Required expected_packet_rate UINT Defines timing associated with this
10, 11 N/A N/A N/A Not used. Thes e attribute IDs have been obsoleted and are no longer defined for a Connection Object
12 Required watchdog_
timeout_action USINT Defines how to handle Inactivity/ Watchdog Timeouts
13 Required produced_
connection_ path_length UINT Number of bytes in the produced_connection_path attribute
14 Required produced_
connection_path Array of USINT Specifies the Application Object(s) whose data is to be produced by this Connection Object.
15 Required consumed_
connection_ path_length UINT Number of bytes in the consumed_ connection_path attribute
16 Required consumed_
connection_path Array of USINT Specifies the Application Object(s) that are to receive the data consumed by this Connection Object
17 Conditional production_inhibit_
UINT Defines minimum time between new data production. This attribute is required for I/O Client connections Attribute Requirement Attribute Name Type Short Description (According to ODVA)