Technical content

Features

– A serial input and output channel (RS-485 or RS-422) – Various protocols supported – Transmission speed can be set up to 38,400 baud – Number of data bits, stop bits, and parity can be set – 4 kbyte receive buffer an d 1 kbyte transmit buffer – Parameterization and data exchange via the bus using PCP services – Diagnostic and status indicators Inline terminal for serial data transmission Firmware Version 1.20 or later This data sheet only is valid with the IL SYS INST UM E user manual (see "Ordering data" on page 4). Make sure you always use the latest documentation. It can be downloaded at www.phoenixcontact.net/download. This data sheet is valid for all products listed on the following page: /G36 /G31 /G39 /G39 /G41 /G30 /G30 /G32 /G32 /G78

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 2 Table of contents

11 Data storage and

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 3

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 4 2O r d e r i n g d a t a

3 Technical data

Description Type Order No. Pcs./Pkt. Inline terminal for serial data transmission; transmission speed of 500 kbps; including connectors and labeling fields IB IL RS 485/422-PAC 2861933 1 Inline terminal for serial data transmission; transmission speed of 500 kbps; without accessories IB IL RS 485/422 2836793 1 Inline terminal for serial data transmission; transmission speed of 2 Mbps; including connectors and labeling fields IB IL RS 485/422-2MBD-PAC 2862097 1 Inline terminal for serial data transmission; transmission speed of 2 Mbps; without accessories IB IL RS 485/422-2MBD 2855839 1 The connector set listed below is needed for the complete fitting of the IB IL RS 485/422 and IB IL RS 485/422-2MBD terminals. Accessories Description Type Order No. Pcs./Pkt. Connector set with a standard connector and a shield connector IB IL AO/CNT-PLSET 2732664 1 Documentation Description Type Order No. Pcs./Pkt. "Automation terminals of the Inline product range" user manual IL SYS INST UM E 2698737 1 "INTERBUS addressing" data sheet DB GB IBS SYS ADDRESS 9000990 1 "Peripherals Communication Protocol (PCP)" user manual IBS SYS PCP G4 UM E 2745169 1 General data Housing dimensions (width x height x depth) 24.4 mm x 120 mm x 72 mm (with connectors) Weight 90 g (without connectors), 135 g (with connectors) Operating mode Process data mode with 1 word PCP mode with 2 words Transmission speed IB IL RS 485/422-PAC 500 kbps IB IL RS 485/422 500 kbps IB IL RS 485/422-2MBD-PAC 2 Mbps IB IL RS 485/422-2MBD 2 Mbps Permissible temperature (operation) -25°C to +55°C Permissible temperature (storage/transport) -25°C to +85°C Permissible humidity (operation/storage/transport) 75% to 85% according to DIN EN 61131-2 Permissible air pressure (operation) 80 kPa to 106 kPa (up to 2000 m above sea level) Permissible air pressure (storage/transport) 70 kPa to 106 kPa (up to 3000 m above sea level) Degree of protection IP20 according to IEC 60529 Protection class Class 3 according to EN 61131-2, IEC 61131-2 Connection data for Inline connectors Connection method Spring-cage terminals Conductor cross-section 0.08 mm2 to 1.5 mm2 (solid or stranded), 28 - 16 AWG

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 5 Interfaces Bus Local bus Through data routing Serial interfaces Type RS-485 half duplex or RS-422 full duplex Cannot be operated simultaneously Electrical data according to EIA (RS) 485, EIA (RS) 422, CCITT V.11 Cable termination resistance 120 Ω, typical Permissible input differential voltage ±5.7 V, maximum Hysteresis 50 mV, typical Input sensitivity -0.2 V, minimum; +0.2 V, maximum Output differential voltage (with 100 Ω load) ±2.0 V, minimum Output differential voltage (with 54 Ω load) ±1.5 V, minimum Short-circuit output current ±80 mA, typical Owing to the 120 Ω termination resistor, the input differential voltage is limited to ±5.7 V. Power consumption 500 kbps 2 Mbps Communications power UL 7.5 V 7.5 V Current consumption at UL 170 mA, typical; 260 mA, maximum* 185 mA, typical; 260 mA, maximum* Total power consumption Approximately 1.275 W, typical;

1.950 W, maximum*

Approximately 1.388 W, typical;

  • All serial interface connections short circuited. NOTE: Damage to the device A continuous short circuit can damage the device. This terminal takes no current from potential jumpers UM and US. Supply of the module electronics through the bus coupler Connection method Potential routing Power dissipation 500 kbps 2 Mbps Power dissipation of the electronics PTOT PTOT = 1.2 W P TOT = 1.4 W Power dissipation of the housing PHOU 1.2 W, maximum* 1.4 W, maximum* * Within the permissible operating temperature Limitation of simultaneity, derating 500 kbps 2 Mbps TA ≤ 50°C No limitation of simultaneity, no derating No limitation of simultaneity, no derating TA > 50°C No limitation of simultaneity, no derating IQ = 4 A IQ: Total diagonal routing current IM/IS/GND Safety equipment None

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 6 Electrical isolation/isolation of the voltage areas The electrical isolation of the logic level from the serial interface is ensured by the DC/DC converter. Common potentials The serial interface control and data cables have the same potential. FE is a separate potential area. Separate potentials in the system consisting of bus coupler/power terminal and I/O terminal - Test distance - Test voltage 5 V supply incoming remote bus/7.5 V supply (bus logic) 500 V AC, 50 Hz, 1 min. 5 V supply outgoing remote bus/7.5 V supply (bus logic) 500 V AC, 50 Hz, 1 min. RS-485/422 interface/7.5 V supply (bus logic) 500 V AC, 50 Hz, 1 min. RS-485/422 interface/24 V supply (I/O) 500 V AC, 50 Hz, 1 min. RS-485/422 interface/functional earth ground 500 V AC, 50 Hz, 1 min. 7.5 V supply (bus logic)/24 V supply (I/O) 500 V AC, 50 Hz, 1 min. 7.5 V supply (bus logic)/functional earth ground 500 V AC, 50 Hz, 1 min. 24 V supply (I/O)/functional earth ground 500 V AC, 50 Hz, 1 min. Error messages to the higher-level control or computer system None Approvals For the latest approvals, please visit www.phoenixcontact.net/catalog.

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 7

4 Internal basic circuit diagram

Figure 1 Internal wiring of the terminal points Key: Protocol chip (bus logic including voltage conditioning) Diagnostic and status indicators with function information Optocoupler DC/DC converter with electrical isolation Microprocessor RS-485/422 interface Capacitor Resistor Ground, electrically isolated from ground of the communications power UL Other symbols used are explained in the IL SYS INST UM E user manual. /G36 /G31 /G39 /G39 /G44 /G30 /G30 /G34 /G2B /G32 /G34 /G20 /G56 /G20 /G28 /G55 /G4D /G29 /G2B /G32 /G34 /G20 /G56 /G20 /G28 /G55 /G53 /G29 /G4C /G6F /G63 /G61 /G6C /G20 /G62 /G75 /G73 /G55 /G4C /G2B /G55 /G41 /G4E /G41 /G55 /G4C /G2D /G4F /G50 /G43 /G44 /GB5 /G50 /G54 /G78 /G44 /G2D /G35 /G20 /G56 /G35 /G20 /G56 /G35 /G20 /G56 /G32 /G34 /G20 /G56 /G54 /G52 /G31 /G54 /G78 /G44 /G52 /G78 /G44 /G52 /G53 /G2D /G34 /G38 /G35 /G2F /G34 /G32 /G32 /G20 /G49 /G6E /G74 /G65 /G72 /G66 /G61 /G63 /G65 /G2F /G2F /G54 /G78 /G44 /G2B /G52 /G78 /G44 /G2B /G52 /G2B /G52 /G2D /G31 /G52 /G78 /G44 /G2D OPC /G78 /G78 /G78 /G58 /G58 /G58 /GB5 /G50 /G52 /G53 /G2D /G34 /G38 /G35 /G2F /G34 /G32 /G32 /G20 /G49 /G6E /G74 /G65 /G72 /G66 /G61 /G63 /G65 /G2F /G2F /G31

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 8

5 Diagnostic and status indicators

and terminal point assignment Figure 2 Diagnostic and status indicators and terminal point assignment

5.1 Local diagnostic and status indicators

5.2 Function identification

2 Mbps: White stripe in the vicinity of the D LED

5.3 Terminal point assignment in half duplex mode

(RS-485)

5.4 Terminal point assignment in full duplex mode

(RS-422) Des. Color Meaning D Green Diagnostics TR Green PCP active Serial interface: RxD Yellow Terminal is receiving data from the connected device TxD Yellow Terminal is transmitting data to the connected device /G36 /G31 /G39 /G39 /G30 /G30 /G30 /G33 /G44 /G52 /G53 /G34 /G38 /G35 /G2F /G34 /G32 /G32 /G54 /G52 /G52 /G78 /G44 /G54 /G78 /G44 /G31 /G32 /G31 /G32 /G33 /G34 /G31 /G32 /G33 /G34 /G31 /G2E /G31 /G31 /G2E /G32 /G31 /G2E /G33 /G31 /G2E /G34 /G32 /G2E /G31 /G32 /G2E /G32 /G32 /G2E /G33 /G32 /G2E /G34 /G32 /G31 Connector Terminal point Signal Assignment Data direction 1 1.4, 2.4 FE Functional earth ground All other terminal points of this connector are not used. 2 1.1 TxD+ Reserved

2.1 TxD- Reserved

1.2 RxD+ Receive/

(positive) Input/ output

2.2 RxD- Receive/

(negative) Input/ output

1.3 R+ Termination

(positive)

2.3 R- Termination

(negative) 1.4, 2.4 Shield Shield connection Connector Terminal point Signal Assignment Data direction 1 1.4, 2.4 FE Functional earth ground All other terminal points of this connector are not used. 2 1.1 TxD+ Transmit data (positive) Output

2.1 TxD- Transmit data

(negative) Output

1.2 RxD+ Receive data

(positive) Input

2.2 RxD- Receive data

(negative) Input (positive) (negative) 1.4, 2.4 Shield Shield connection

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 9

6 Installation instructions

7 Serial interface

The IB IL RS 485/422 terminal has one RS-485 and one RS-422 interface. The interfaces cannot be operated simultaneously.

7.1 RS-485

In RS-485 mode, an RS-485 network with multiple devices can be created. Use a twisted pair, common shielded data cable to connect the devices. Fit this data cable with a termination resistor at the two furthest points of the RS-485 network. For connection to the Inline terminal, use the termination resistor installed in the device (see Figure 1). Connection examples are shown in Figure 5 to Figure 7 on page 11 to page 12. This operating mode supports half duplex transmission. Make sure that only one device is transmitting data at a time. To ensure a defined idle cable state, data cable polarization is included in the IB IL RS 485/422 terminal.

7.2 RS-422

In RS-422 mode, a point-to-point connection can be established. Use a twisted pair, common shielded data cable to connect the devices. Fit this data cable with a termination resistor at each device. For connection to the Inline terminal, use the termination resistor installed in the device (see Figure 1). Connection examples are shown in Figure 8 on page 12 and Figure 9 on page 13. This operating mode supports full duplex transmission.

8 Connection notes

8.1 Capacitor between shield and FE

Figure 3 Position of the shield connector to connect the shield to FE using a capacitor Please observe the "Connection notes" on page 9. By assigning terminal points 1.4 and 2.4 of both connectors, you can connect the cable shield either using a capacitor (connector 2) or directly (connector 1) to functional earth ground (FE). With the two connection options, you can connect one side of the cable shield directly and one side using a capacitor to FE without any additional effort. In this way, you can prevent ground loops, which can occur if a shield is connected directly to FE on both sides. Regardless of the side to which the shield is connected, all wires must be wired to connector 2. Use at least one connector with shield connection when connecting the I/O device. /G36 /G38 /G37 /G38 /G42 /G30 /G30 /G35

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 10

8.2 Shield connected directly to FE

Figure 4 Position of the shield connector to connect the shield directly to FE

9 Connection examples

9.1 Comparison of the wiring examples in Figure 5 to Figure 9

When wiring, please observe the following notes: – Always connect the shield between two devices on one side using a capacitor and on the other side directly to FE. – An RS-485 network must be equipped with a termination resistor at both ends. – For an RS-422 point-to-point connection, the receive signals on every device must have a termination resistor. /G36 /G38 /G37 /G38 /G42 /G30 /G30 /G36 Operating mode Special feature Shield connection Remark Connectors required per IB IL RS 485/422 Example in RS-485 IB IL RS 485/422 as the end point of a network Capacitive Termination resistor required Connector set Figure 5 RS-485 IB IL RS 485/422 in the center of a network Capacitive/ direct – 2 shield connectors Figure 6 RS-485 IB IL RS 485/422 as the end point of a network Direct Termination resistor required Connector set Figure 7 RS-422 Shield connected using a capacitor Capacitive Termination resistor required Connector set Figure 8 RS-422 Shield connected directly Direct Termination resistor required Connector set Figure 9 The connector set consists of a shield connector and a standard connector.

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 11

9.2 RS-485: IB IL RS 485/422 termin al as the end point of a network

Figure 5 RS-485 interface wiring: IB IL RS 4 85/422 as the end point of a network, capacitor between data cable shield and FE

9.3 RS-485: IB IL RS 485/422 termin al in the center of a network

Figure 6 RS-485 interface wiring: IB IL RS 485/ 422 in the center of a network, data cable shield connected directly and using a capacitor to FE Connect the shield to FE using a capacitor. Connector Transmit/receive data (positive) Transmit/receive data (negative) Connection of termination resistor via R+ and R- Inline connector (connector 2) Connector Transmit/ receive data (positive)Inline connector (connector 2) Transmit/ receive data (negative)

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 12

9.4 RS-485: IB IL RS 485/422 termin al as the end point of a network

Figure 7 RS-485 interface wiring: IB IL RS 485/422 as the end po int of a network, data cable shield connected directly to FE

9.5 RS-422: Shield connecte d using a capacitor to the IB IL RS 485/422 terminal

Figure 8 RS-422 interface wiring: Data cable shield connected using a capacitor to FE Connect the shield directly to FE. Connector Transmit/receive data (positive) Transmit/receive data (negative) Connection of termination resistor via R+ and R- Inline connector (connector 2) Connector Transmit data (positive) Transmit data (negative) Receive data (positive) Receive data (negative) Transmit data (positive) Transmit data (negative) Connection of termination resistor Receive data (positive) Receive data (negative) Connection of termination resistor via R+ and R- Inline connector (connector 2) RS-422 device

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 13

9.6 RS-422: Shield connected directly to the IB IL RS 485/422 terminal

Figure 9 RS-422 interface wiring: Data cabl e shield connected directly to FE Connector Transmit data (positive) Receive data (positive) Transmit data (positive) Transmit data (negative) Connection of termination resistor Receive data (negative) RS-422 device Inline connector (connector 2) Transmit data (negative) Receive data (positive) Receive data (negative) Connection of termination resistor via R+ and R-

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 14

10 Programming data/configuration

10.1 Local bus (INTERBUS)

10.2 Other bus systems

The terminal stores the received serial data in an intermediate buffer until it is requested by the bus controller board or the device at the serial interface. Serial data traffic can be managed using various protocols. The protocol used depends on the type of protocol supported by the peer.

11.1 Overview of supported protocols

ID code DChex (220dec) Length code 01hex Process data channel 16 bits Input address area 2 bytes Output address area 2 bytes Parameter channel (PCP) 4 bytes Register length (bus) 6 bytes For the programming data of other bus systems, please refer to the corresponding electronic device data sheet, e.g., GSD, EDS. Protocol Receive memory Transmit memory Special Transparent 4096 bytes 1023 bytes End-to-end 25 buffers with 58 bytes each 1023 bytes (including end characters) Two end characters are filtered out Dual buffer 2 buffers with bytes each 1023 bytes (including end characters) Only stores the most recently received data, end characters are filtered out 3964R 25 buffers with 58 bytes each 15 buffers with 58 bytes each Data exchange with software handshake, time monitoring, and checksum XON/XOFF 4096 bytes 1023 bytes Software handshake Modbus RTU 25 buffers with 58 bytes each 15 buffers with 58 bytes each Time monitoring and checksum Modbus ASCII 25 buffers with 58 bytes each 15 buffers with 58 bytes each Time monitoring and checksum

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 15

11.2 Transparent protocol

If the transparent protocol is used, serial data is forwarded by the terminal in the same format it was received from the serial interface or the bus side. The transmit FIFO (First In, First Out memory) can store 1023 bytes (1 kbyte) and the receive FIFO can store 4096 bytes (4 kbytes). If the terminal receives another character after the 4095th character, the error pattern is stored in the receive FIFO. All subsequent characters are ignored.

11.3 End-to-end protocol

The serial data is conditioned for the end-to-end protocol. If serial data is sent from the bus side, two additional characters, the first and second delimiters, are attached for transmission to the serial interface. The first and second delimiters are defined when the terminal is configured using the INIT-TABLE object. Serial data sent from the serial interface can only be read by the user if the terminal has received the first and second delimiters. The two delimiters confirm that the serial data has been received without error and the maximum data length of 58 bytes has been observed. The delimiters are filtered out when the data is read by the bus side. Unlike in the transparent protocol, the receive memory is not organized as a FIFO but as a buffer. 25 buffers of 58 bytes each are available. If the buffer size of 58 bytes is exceeded without the two delimiters being detected, the buffer is overwritten again. Depending on the INIT-TABLE object, subindex 0Chex (rotation switch), there are two variants. Variant 1 (0Chex = 0; default setting): Only the new data is available in the overwritten buffer, i.e., any existing data from the previous cycle is rejected (no rotation). Variant 2 (0Chex = 1): The buffer is re-written character by character. If the two delimiters are detected, the new characters and the remaining characters from the previous cycle are available in the overwritten buffer (rotation). The transmit FIFO is 1023 bytes in size. The delimiters are attached to, and stored with, the data to be sent.

11.4 Dual buffer protocol

With this protocol, the last received data block is stored. A data block is defined as a sequence of characters with the first and second delimiter, as in the end-to-end protocol. As soon as a new data block is received, the previous one is overwritten. This is achieved using two buffers, which are written to alternately. This means that one buffer will always be available to receive serial data, while the other stores the last received data block. A data block is only regarded as complete once both delimiters have been detected, one after the other. It can then be read from the bus side. If the buffer size of 58 bytes is exceeded without the two end characters (delimiters) being detected, the buffer is overwritten again. Depending on the INIT-TABLE object, subindex 0Chex (rotation switch), there are two variants. Variant 1 (0Chex = 0): Only the new data is available in the overwritten buffer, i.e., any existing data from the previous cycle is rejected (no rotation). Variant 2 (0Chex = 1): The buffer is re-written character by character. If the two delimiters are detected, the new characters and the remaining characters from the previous cycle are available in the overwritten buffer (rotation). The same conditions as in the end-to-end protocol apply to sending serial data. If serial data is sent from the bus side, two additional characters, the first and second delimiters, are attached for transmission to the serial interface. 11.5 3964R protocol This protocol, developed by Siemens, is the most complex. It uses start and end identifiers, a checksum, and time monitoring. 15 buffers are available for transmitting and 25 buffers are available for receiving. The optional 3964 priority defines which device may send first (high priority) if there is an initialization conflict (several devices attempting to send data simultaneously). Character delay time: 220 ms Acknowledgment delay time: 2 s Block waiting time: 10 s Number of attempts to establish a connection: 6

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 16

11.6 XON/XOFF protocol

This protocol operates in the same way as the transparent protocol, but uses a software handshake. Data transmission with this protocol is controlled by the XON and XOFF characters. XON is preset to 11hex and XOFF to 13hex. These characters can also be defined when the terminal is configured using the INIT-TABLE object. If the terminal receives an XOFF, no more serial data will be sent until an XON is received. The terminal itself transmits an XOFF if the available space in the receive memory is less than 5 bytes. As soon as more memory becomes available again, the terminal transmits a single XON. Serial data is not filtered when it is transmitted. So any characters that occur with the code defined for XON and XOFF are sent and may trigger undesirable events at the receiver. When serial data is received, the XON and XOFF characters are filtered and are not available as data. Any characters with the XON or XOFF code are lost. Ensure that characters with these codes do not appear in the data stream.

11.7 Modbus RTU (Remote Terminal Unit)

Telegram structure in RTU mode: A frame (telegram) is finished if there is a break in transmission of at least 3.5 characters (referred to as t3.5). If there is a break in frame transmission of more than 1.5 characters (referred to as t1.5), the message is considered incomplete and is thus rejected. In the Modbus environment, two timeouts are always required: t1.5 and t3.5. For baud rates above 19,200 baud, the timeouts are specified as t1.5 = 1.5 ms and t3.5 = 3.0 ms.

11.8 Modbus ASCII

Telegram structure in ASCII mode: In Modbus ASCII mode, each hex value is converted into two ASCII characters. In this way, the data throughput is halved compared to RTU mode. Example: The number 5Bhex is split into ASCII characters 5 and B. The corresponding ASCII codes are 35hex (5) and 42hex (B). Both end characters can be modified using the first delimiter and second delimiter entries in the INIT-TABLE object.

11.9 Time monitoring for Modbus

Time monitoring is valid for Modbus RTU as well as for Modbus ASCII. After a telegram is sent, a response is expected within the response time of 2.5 s. After a timeout, the transmit error bit is set in the process data. The broadcast telegram is an exception where no slave responds and thus the response timeout is not maintained. Instead, the turnaround delay of 200 ms is observed. The next telegram may not be sent until this time has elapsed.Address Function Data CRC check 1 byte 1 byte 0 ... 56 bytes 2 bytes (EXOR) Start Address Function Data CRC check End

1 ASCII

(:)

2 ASCII

2 x (0 ... 56) ASCII characters (CR, LF)

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 17

12 PCP communication

By default upon delivery, the terminal is configured for data transmission according to the parameters on page 22. You can configure the terminal to meet the requirements of your application. The terminal is configured in PCP mode using the INIT-TABLE object. Parameter records or text strings are transmitted to or from a connected I/O device in PCP mode using the SERIAL- DATA object.

12.1 Object dictionary

12.2 Object description

The object indicates whether or not the terminal was restarted. Following a power up, the byte will always have a value of 01hex. For a restart to be detected, the byte must be set to 00hex by the application. If it is then set to 01hex again by the terminal, this indicates that the terminal has been restarted. Object description: For information about PCP communication, please refer to the IBS SYS PCP G4 UM E user manual. The IBS CMD (for standard controller boards) and PC WorX (for Field Controllers (FC) and Remote Field Controllers (RFC)) programs are available for the configuration and parameterization of your INTERBUS system. For additional information, please refer to the "IBS CMD SWT G4 UM E" user manual and the Quick Start Guide for your version of PC WorX.Index Data type N L Meaning Object name Rights 5FC1hex Var of unsigned 8 1 1 Module st art indicator START-IND rd/wr 5FE0hex String var of octet string 1 58 Send/receive serial data SERIAL-DATA rd/wr 5FFFhex Array of unsigned 8 20 1 IB IL RS 485/422 terminal configuration INIT-TABLE rd/wr N: Number of elements rd: Read access permitted L: Length of an element in bytes wr: Write access permitted The object is of no significance to the function of the terminal. Object START-IND Access Read, write Data type Var of unsigned 8 1 byte Index 5FC1hex Subindex 00hex Length (bytes) 01hex Data Module start indicator Index Data type N L Meaning Object name Rights 5FC1hex Var of unsigned 8 1 1 Module start indicator START-IND rd/wr 5FE0hex String var of octet string 1 58 Send/receive serial data SERIAL-DATA rd/wr 5FFFhex Array of unsigned 8 20 1 IB IL RS 485/422 terminal configuration INIT-TABLE rd/wr

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 18 Value range of the object: SERIAL-DATA object This object is used to send and receive serial data. Object description: If no serial data is available on a read access, a read response (read service response) is generated with the result (+) and length of With a protocol data unit (PDU) size of 64 bytes, a maximum of 58 characters can be transmitted. The length of the read or write service depends on the number of characters to be transmitted. If, for example, 20 characters are to be read, the read response is 24 bytes long (20 bytes of data + 4-byte PCP overhead). Error messages for the SERIAL-DATA object: If, during a write service, there is not enough transmit memory available for serial data, the service will be answered with a negative confirmation. Here, the parameters are: A write service without user data (length = 0) will be answered with a negative confirmation. Here, the parameters are: Module start indicator Code Meaning Representation in CMD/PC WorX 00hex Reset power up message Reset power up message 01hex Power up was carried out Power up completed If you set the object to 01hex, it has no effect on the function of the terminal. A power up cannot be triggered in this way. However, it is then not possible to detect a terminal restart. Object SERIAL-DATA Access Read, write Data type String var of octet string 1 x 58 bytes Index 5FE0hex Subindex 00hex 00hex 3Ahex (Only access to all data possible) Length (bytes) 00hex 3Ahex Amount of data in the buffer Maximum length of the object Data Send/receive serial data Error_Class: 8 Error_Code: 0 Additional_Code: 0022hex Meaning: No character of the serial data will be accepted from this service. Error_Class: 8 Error_Code: 0 Additional_Code: 0030hex Meaning: Value is out of range

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 19 Mapping a write request to the Modbus telegrams: Figure 10 Write request Key: A read response service is mapped accordingly. Command Code Para Count Invoke ID Comm.Ref Index Subindex Length Data (0...58 byte) PCP Write Request Address field (1 byte) Function code (1 byte) CRC (2 byte) Modbus RTU Telegram Start (3A )hex Address field (2 ASCII; 1 byte) CRC (2 ASCII) End (0D0A )hex Modbus ASCII Telegram Function code (2 ASCII; 1 byte) 6199A014 Data (0...56 byte) Data 0082 0020 00 CR 5FE0 00 3A Data AB C D A General representation of a write request B Mapped example call for 58 bytes of data C Transmitted data for Modbus RTU Data transmitted using the service is indicated by the color background and bold outline. CRC is only added to the Modbus device. D Transmitted data for Modbus ASCII Data transmitted using the service is indicated by the color background and bold outline. Start, CRC, and End are only added to the Modbus device.

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 20 INIT-TABLE object The terminal is configured by writing the INIT-TABLE object using a write service. Object description: Object INIT-TABLE Access Read, write Data type Array of unsigned 8 20 x 1 byte Index 5FFF hex Subindex 00 hex 01hex 02hex 03hex 04hex 05hex 06hex 07hex 08hex 09hex 0Ahex 0Bhex 0Chex 0Dhex 0Ehex 0Fhex 10hex 11hex 14hex Write all elements Protocol Baud rate Data width Reserved Reserved Error pattern First delimiter Second delimiter 3964R priority Output type Reserved Rotation switch XON pattern XOFF pattern Baud rate direct Basic baud rate direct Reserved Reserved Length (bytes) 14 hex subindex 00hex 01hex subindex 01hex to 14hex Data IB IL RS 485/422 terminal configuration

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 21 INIT-TABLE object elements: Element value range: Element Meaning Default setting Data type dec hex Code Meaning 1 1 Protocol 00hex Transparent Unsigned 8 2 2 Baud rate 07hex 9600 baud Unsigned 8 3 3 Data width 02hex 8 data bits, even parity, 1 stop bit Unsigned 8 4 4 Reserved 00hex Unsigned 8 5 5 Reserved 00hex Unsigned 8 6 6 Error pattern 24hex ($) Unsigned 8 7 7 First delimiter 0Dhex Carriage return (CR) Unsigned 8 8 8 Second delimiter 0Ahex Line feed (LF) Unsigned 8 9 9 3964R priority 00hex Low Unsigned 8

10 A Output type 01hex RS-485 Unsigned 8

11 B Reserved 00hex Unsigned 8

12 C Rotation switch 00hex No rotation Unsigned 8

13 D XON pattern 11hex Unsigned 8

14 E XOFF pattern 13hex Unsigned 8

15 F Baud rate direct 00hex Unsigned 8

16 10 Basic baud rate direct 00hex Unsigned 8 17 - 20 11 - 14 Reserved 00hex Unsigned 8 Set all reserved elements to 00hex. The options in bold are default settings. Protocol Code Meaning Representation in CMD/PC WorX 00hex Transparent Transparent 01hex End-to-end End-End 02hex Dual buffer Dual buffer 03hex 3964R 3964R 04hex XON/XOFF XON/XOFF 05hex Modbus RTU Modbus RTU 06hex Modbus ASCII Modbus ASCII Baud rate Code Value 00hex 110 01hex 300 02hex 600 03hex 1200 04hex 1800 05hex 2400 06hex 4800 07hex 9600 08hex 19200 09hex 38400 FFhex Direct

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 22 If the baud rate contains the value FFhex, direct baud rate programming is selected. Thus the baud rate can be freely assigned. Element 15 indicates the desired baud rate. Element 16 indicates the basic baud rate. Data width Code Meaning Representation in CMD/PC WorX Data bits Parity Stop bits 00hex 7E v e n1 7 data bits, even parity, 1 stop bit 01hex 7O d d1 7 data bits, odd parity, 1 stop bit 02hex 8E v e n1 8 data bits, even parity, 1 stop bit 03hex 8O d d1 8 data bits, odd parity, 1 stop bit 04hex 8N o n e1 8 data bits, without parity, 1 stop bit 05hex 7N o n e1 7 data bits, without parity, 1 stop bit 06hex 7E v e n2 7 data bits, even parity, 2 stop bits 07hex 7O d d2 7 data bits, odd parity, 2 stop bits 08hex 8E v e n2 8 data bits, even parity, 2 stop bits 09hex 8O d d2 8 data bits, odd parity, 2 stop bits 0Ahex 8N o n e2 8 data bits, without parity, 2 stop bits 0Bhex 7N o n e2 7 data bits, without parity, 2 stop bits Error pattern Code Meaning 24hex $ xxhex Any character First delimiter Code Meaning 0Dhex Carriage return (CR) xxhex Any character Second delimiter Code Meaning 0Ahex Line feed (LF) xxhex Any character 3964R priority Code Meaning Representation in CMD/PC WorX 00hex Low priority Low priority 01hex High priority High priority Output type Code Meaning 00hex Invalid 01hex RS-485 02hex RS-422 Rotation switch Code Meaning Representation in CMD/PC WorX 00hex No rotation No rotation 01hex Rotation Rotation XON pattern Code Meaning 11hex xxhex Any character (not the same as XOFF pattern) Baud rate direct Code Meaning 00hex Baud rate = Basic baud rate xxhex n = (Basic baud rate/baud rate) - 1 XOFF pattern Code Meaning 13hex xxhex Any character (not the same as XON pattern) Basic baud rate direct Code Meaning 00hex 500 kbaud 01hex 62.5 kbaud 02hex 15625 baud

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 23 Example: When element 16 is written, direct baud rate programming takes effect. In theory, direct baud rate programming supports a maximum value of 500 kbaud. Correct operation of the module is tested and ensured up to 38,400 baud. Operation at a higher baud rate depends on the application. The error pattern contains the character that is written to the FIFO if a character was received with errors (this does not apply to the 3964R protocol). This can, for example, be the result of parity errors, exceeded value ranges or noise interference. In the transparent and XON/XOFF protocols, this pattern is also used if the receive FIFO is full and additional characters are received. The first delimiter and the second delimiter contain the end characters for the dual buffer and the end-to-end protocols. The value in the 3964R priority element defines the priority of a device if there is an initialization conflict (several devices attempting to send data simultaneously). The device with priority level 1 has priority over the device with priority level 0. The rotation switch determines how the buffer is re-written when it is full and the two end characters (delimiters) have not been detected. No rotation: Only the new data is available in the overwritten buffer, i.e., any existing data from the previous cycle is rejected. Rotation: The buffer is re-written character by character. If the two delimiters are detected, the new characters and the remaining characters from the previous cycle are available in the overwritten buffer. XON pattern and XOFF pattern contain the control characters for the XON/XOFF protocol. The characters must not be the same. In the case of the INIT-TABLE object, if one of the elements is written, the transmit and receive buffers of the affected channel are set to empty. This means that all transmit and receive data that has not yet been processed will be lost. Error messages for the INIT-TABLE object – If an element with an invalid value is written during a write service, the service will be acknowledged with a negative confirmation. Here, the parameters are: The high byte of the Additional_Code (xx) contains the number of the affected element. If several elements are affected, the highest number is given. If, for example, the output type element is written with the value 0, an error message with the Additional_Code 0A30hex will be displayed, because the 10th element is faulty. – For a write request with the subindex 0 (write entire table) in which the XON/XOFF protocol is to be set and the XON pattern is the same as the XOFF pattern, an error message will be generated. Here, the parameters are: – If a reserved element is writ ten, the value must equal 0, otherwise an error message is generated. Here, the parameters are: The baud rate should be 25,000 baud Element 2 = FFhex 500 kbaud is selected as the basic baud rate Element 16 = 00hex n = (500,000 baud/25,000 baud) - 1 = 19 = 13 hex Element 15 = 13hex If at least one element of the INIT-TABLE object is written, the pointers for the transmit and receive FIFOs will be reset. This means that all transmit and receive data that has not yet been processed will be lost. Error_Class: 8 Error_Code: 0 Additional_Code: xx30hex Meaning: Value is out of range Error_Class: 8 Error_Code: 0 Additional_Code: 0E30hex Meaning: Parameterization error Error_Class: 8 Error_Code: 0 Additional_Code: xx30hex Meaning: Parameterization error

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 24

12.3 Error messages in PCP mode

The terminal error messages have the parameters: Error_Class = 8 (device-specific error) and Error_Code = 0 (no communication error). The exact error cause is indicated by the Additional_Code. The low byte of the Additional_Code indicates the error cause. The high byte of the Additional_Code (xx) contains the number of the affected element. If several elements are affected, the highest number is given. The following Additional_Codes can occur on this terminal: 0022hex No character of the serial data will be accepted from this service. xx30hex Value is out of range or parameterization error 0000hex Hardware fault For additional information about error messages in PCP mode, please refer to the IBS SYS PCP G4 UM E PCP manual and the user manual for your controller board.

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 25

13 Process data

13.1 Assignment of the process data output word (~control word)

13.2 Format of the process data output word (~control word)

Figure 11 Format of the process data output word For the assignment of the (word.bit) or (byte.bit) view illustrated under 13.1 and 13.3 to your INTERBUS control or computer system, please refer to the DB GB IBS SYS ADDRESS data sheet. (Word.bit) view Word Word 0 Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 (Byte.bit) view Byte Byte 0 Byte 1 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Assignment Reserved Reserved Reserved Reserved Reserved Execute re-initialization Reset transmit error Reset receive error Reserved Set all reserved bits to 0. PCP channel PCP channel Process data channel Re-initialization Transmit error Receive error No action No action Reset receive error Reset transmit error No action Execute re-initialization

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 26 If the control word contains 3C00hex, then the status word returns the firmware version and the module ID. Example: Using the module ID, it is possible to clearly identify different terminals with the same ID code.

13.3 Assignment of the pr ocess data input word (~status word)

Status word (hex) 1 2 0 7 Firmware Version 1.20 Module ID Terminal ID code Module ID IB IL RS 485/422 DChex (220dec) 7 IB IL RS 232 DChex (220dec) 8 (Word.bit) view Word Word 0 B i t 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 (Byte.bit) view Byte Byte 0 Byte 1 B i t 7654321076543210 Assignment Number of received characters Reserved Transmit buffer not empty Transmit buffer full Receive buffer full Re-initialization executed Transmit error Receive error Receive buffer not empty

IB IL RS 485/422 ... 6878_en_04 PHOENIX CONTACT 27

13.4 Format of the process data input word (~status word)

Figure 12 Format of the process data input word PCP channel Only for transparent and XON/XOFF protocol: Number of characters received If value = FFhex, the number of characters is >= 255 Not full Empty Not empty Empty No error Error No error Error No re-initialization Re-initialization executed Not empty Full Not full Full Reserved Transmit buffer Receive buffer Transmit error Re-initialization Receive error Transmit buffer Receive buffer PCP channel Process data channel

IB IL RS 485/422 ... 6878_en_04 28PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00 PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300 www.phoenixcontact.com Bit/status Effect Protocol Bit 0 = '1' The receive buffer is not empty, characters to be read are available. All Bit 1 = '1' Receive error In the case of the 3964R protocol, this bit indicates that a telegram could not be received without error after six transmit attempts by the serial peer or after the block waiting time had elapsed. For Modbus RTU and Modbus ASCII, this bit indicates that the checksum comparison was faulty. 3964R, Modbus RTU, Modbus ASCII Bit 2 = '1' Transmit error In the case of the 3964R protocol, this bit indicates that a telegram could not be transmitted by the terminal to the serial peer after six transmit attempts. The telegram was rejected. For Modbus RTU and Modbus ASCII, this bit indicates that the timeout of 2.5 s elapsed without any response being received. 3964R, Modbus RTU, Modbus ASCII Bit 3 = '1' A re-initialization was executed; the transmit and receive buffers are now empty. All Bit 4 = '1' The receive buffer is full: Residual capacity: < 15 characters Transparent, XON/XOFF Residual capacity: None End-to-end, 3964R, Modbus RTU, Modbus ASCII Bit 5 = '1' The transmit buffer is full: Residual capacity: ≤ 30 characters Transparent, XON/XOFF, end-to-end, dual buffer Residual capacity: None 3964R, Modbus RTU, Modbus ASCII Bit 6 = '1' The transmit buffer is not empty, characters to be sent are available. All Bit 7 = '1' Reserved Both error bits (bit 1 and 2) are not automatically reset. They can only be reset by the process data output word.