Technical content
Features
– Two differential analog sign al inputs to connect current signals – Sensors are connected using 2-wire technology (active and passive sensors) – Two differential analog sign al inputs to connect current signals – Current measuring range: 4 mA ... 20 mA – By default, both channels are set to the measuring range 4 mA to 20 mA (IB IL format) – HART protocol transmission using PCP – Hand-held connection possible – Measured values can be repr esented in three different formats – 16-bit analog/digital converter –R e s o l u t i o n d e p e n d s o n t h e representation format and the measuring range – Diagnostic indication – Point-to-point and multi-drop connections possible – Approved for the use in potentially explosive areas (observe the notes on page 7) Inline Terminal With 2 Analog Input Channels and HART Functions This data sheet is only valid in association with the IL SYS INST UM E user manual or the Inline system manual for your bus system. A function block for easy terminal handling can be downloaded at www.download.phoenixcontact.com. Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com. A conversion table is available on the Internet at This data sheet is valid for the products listed on the following page: /G34 /G78
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 2 2T a b l e o f C o n t e n t s
15.6 Special Addressing and Connection
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 3 17.2 UNIQUE_IDENTIFIER_CHANNEL1_SLAVE1 ... 5 and 17.4 POLL/BURST_RESPONSE_CHANNEL1_SLAVE1 ... 5 and 3O r d e r i n g D a t a Products Description Type Order No. Pcs./Pkt. Inline terminal with 2 analog input channels with HART functions; complete with accessories (connectors and labeling fields) IB IL AI 2-HART-PAC 2861331 1 Inline Terminal with 2 analog input channels and HART functions; without accessories IB IL AI 2-HART 2860264 1 The connectors listed below are needed for the complete fitting of the IB IL AI 2-HART terminal. Accessories Description Type Order No. Pcs./Pkt. Inline shield connector for analog Inline terminals IB IL SCN-6 SHIELD 2726353 5 Connector for digital single-channel, two-channel or 8-channel Inline terminals IB IL SCN-8 2726337 10 Documentation Description Type Order No. Pcs./Pkt. "Automation Terminals of the Inline Product Range" user manual IL SYS INST UM E 2698737 1 "Configuring and Installing the INTERBUS Inline Product Range" user manual IB IL SYS PRO UM E 2743048 1 "INTERBUS Addressing" data sheet DB GB IBS SYS ADDRESS 9000990 1 "Inline Terminals for Use in Zone 2 Potentially Explosive Areas" application note AH EN IL EX ZONE 2 7217 1 "Peripherals Communication Protocol (PCP)" user manual IBS SYS PCP G4 UM E 2745169 1 "Startup of a HART-Compatible Device in AutomationXplorer+" application note AH EN AUTOMATIONXPLORER & HART 7603 1
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 4
4 Technical Data
Housing dimensions (width x height x depth) 48.8 mm x 120 mm x 71.5 mm Weight 134 g (without connectors), 206 g (with connectors) Operating mode Process data operation with 2 words and PCP operation with 2 words Transmission speed 500 kbps Connection method for sensors 2-wire technology Power supply of the sensors 24 V DC, provided by the terminal Permissible temperature (operation) -25°C … +55°C Permissible temperature (storage/transport) -25°C … +85°C Permissible humidity (operation/storage/transport) 10 % ... 95% according to DIN EN 61131-2 Permissible air pressure (operation/storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level) Degree of protection IP20 Class of protection Class III, IEC 61140 Connection data for Inline connectors Connection type Spring-cage terminals Interface Local bus Data routing Supply of the Module Electronics and I/O Through the Bus Terminal/Power Terminal Connection method Potential routing Power Consumption Communications power UL 7.5 V Current consumption from UL 95 mA (typical), 110 mA (maximum) I/O supply voltage UANA 24 V DC Current consumption at UANA 50 mA (typical), 150 mA (maximum) Total power consumption 1.9 W (typical) Analog Inputs Number 2 differential analog inputs Signals/resolution in the process data word (quantization) 0 mA ... 25 mA (PIO format) 0.381 µA/LSB 4 mA ... 20 mA (Standardized representation format) 1.000 µA/LSB 4 mA ... 20 mA (IB IL format) 0.533 µA/LSB Measured value representation in the following formats: IB IL 15 bits with sign bit (see also page 13) Standardized representation 15 bits with sign bit (see also page 13) PIO 16 bits without sign bit (see also page 14) Mean-value generation Using 4, 16, 32 measured values, 16 measured values by default Conversion time of the A/D converter 10 µs, approximately
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 5 Analog Input Stages of the Current Inputs Input resistance 250 Ω (shunt) Limit frequency (-3 dB) of the input filters 25 Hz Process data update of both channels Bus-synchronous Behavior on sensor failure Going to 0 mA or 4 mA Maximum permissible voltage between analog current inputs and analog reference potential ±10 V (corresponds 40 mA across the sensor resistances) Common mode rejection (CMR) 105 dB minimum Reference: current input signal, valid for permissible DC common mode voltage range 115 dB (typical) Permissible DC common mode voltage for CMR 40 V between current input and FE Maximum permissible current ±40 mA Tolerance Behavior and Temperature Response of the Current Inputs (The error indications refer to the measuring range final value.) TA = 23°C Measuring Range Absolute (Typical) Absolute (Maximum) Relative (Typical) Relative (Maximum) Measuring Range Absolute (Typical) Absolute (Maximum) Relative (Typical) Relative (Maximum) Additional Tolerances Influenced by Electromagnetic Fields Type of Electromagnetic Interference Typical Deviation of the Measuring Range Final Value (Current Input) Relative Electromagnetic fields; Field strength 10 V/m According to EN 61000-4-3/IEC 61000-4-3 < ±2% Conducted interference Class 3 (test voltage 10 V) According to EN 61000-4-6/IEC 61000-4-6 < ±1% Fast transients (burst) 4 kV supply, 2 kV input According to EN 61000-4-4/IEC 61000-4-4 < ±1% Safety Equipment Surge voltage Suppressor diodes in the analog inputs Electrical Isolation/Isolation of the Voltage Areas Common Potentials 24 V main power, 24 V segment voltage, and GND have the same potential. FE is a separate potential area. Separate Potentials in the System Consisting of Bus Terminal/Power Terminal and an I/O Terminal Test Distance Test Voltage 5 V supply incoming remote bus/7.5 V supply (bus logic) 500 V AC, 50 Hz, 1 min 5 V supply outgoing remote bus/7.5 V supply (bus logic) 500 V AC, 50 Hz, 1 min
7.5 V supply (bus logic), 24 V supply UANA / I/O 500 V AC, 50 Hz, 1 min
7.5 V supply (bus logic), 24 V supply UANA / functional earth ground 500 V AC, 50 Hz, 1 min
I/O / functional earth ground 500 V AC, 50 Hz, 1 min
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 6
5 Local Diagnostic Indicators and
Figure 1 IB IL AI 2-HART terminal with appropriate connectors
5.1 Local Diagnostic and Status Indicators
5.2 Function Identification
5.3 Terminal Point Assignment
6 Installation Instructions
High current flowing through potential jumpers UM and US leads to a temperature rise in the potential jumpers and inside the terminal. To keep the current flowing through the potential jumpers of the analog terminals as low as possible, always place the analog terminals after all the other terminals at the end of the main circuit (sequence of the Inline terminals: see also IL SYS INST UM E user manual or the Inline system manual for your bus system). Error Messages to the Higher-Level Control or Computer System Failure of the internal voltage supply Yes Peripheral fault/user error Yes, error message via the IN process data (see page 12) Approvals Des. Color Meaning D Green Diagnostics TR Green PCP communication status H1, H2 Yellow HART communication status /G54 /G52 /G48 /G31 /G44 /G41 /G49 /G32 /G2D /G48 /G41 /G52 /G54 /G48 /G32 /G36 /G37 /G35 /G38 /G42 /G30 /G30 /G33 /G31 /G32 /G31 /G32 /G33 /G34 /G31 /G32 /G33 /G34 /G31 /G2E /G31 /G31 /G2E /G32 /G31 /G2E /G33 /G31 /G2E /G34 /G32 /G2E /G31 /G32 /G2E /G32 /G32 /G2E /G33 /G32 /G2E /G34 /G31 /G32 /G31 /G32 /G33 /G34 /G31 /G32 /G33 /G34 /G31 /G2E /G31 /G31 /G2E /G32 /G31 /G2E /G33 /G31 /G2E /G34 /G32 /G2E /G31 /G32 /G2E /G32 /G32 /G2E /G33 /G32 /G2E /G34 /G31 /G34 Con- nectors Terminal Points Signal Assignment 1 1.1 +24 V 1 Sensor supply channel 1 1.2 +I1 Current input channel 1
1.3 AGND1 Analog ground channel 1
1.4, 2.4 FE Shield connection 2.2, 2.3 +I1 Hand-held operating device Connection channel 1 2 and 3 Not used 4 1.1 +24 V 2 Sensor supply channel 2 1.2 -I2 Current input channel 2
1.3 AGND2 Analog ground channel 2
1.4, 2.4 FE Shield connection 2.2, 2.3 +I2 Hand-held operating device Connection channel 2 Observe the connection notes on page 9.
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 7
7 Notes on Using the Terminal in Potentially Explosive Areas
Approval According to EC Directive 94/9 (ATEX) II 3G Ex nAC IIC T4 X This Inline terminal conforms to the requirements of protection type "n" and can be installed in a zone 2 potentially explosive area. This Inline terminal is a category 3G item of electrical equipment. Figure 2 Typical labeling of terminals for use in potentially explosive areas 1. When working on the Inline terminal, always disconnect the supply voltage. 2. The Inline terminal must only be installed, started up, and maintained by qualified specialist personnel. 3. Install the Inline terminals in a control cabinet or metal housing. The minimum requirement for both items is IP54 protection according to EN 60529. 4. The Inline terminal must no t be subject to mechanical strain and thermal loads, which exceed the limits specified in the product documentation. 5. The Inline terminal must no t be repaired by the user. Repairs may only be carried out by the manufacturer. The Inline terminal is to be replaced by an approved terminal of the same type. 6. Only category 3G equipment may be connected to Inline terminals in zone 2. 7. Observe all applicable stan dards and national safety and accident prevention regulations for installing and operating equipment. Restrictions WARNING: Explosion hazard Only use Inline terminals that are approved for use in potentially explosive areas. Before using an Inline terminal in a zone 2 potentially explosive area, check that the terminal has been approved for installation in this area. For a list of terminals approved for use in zone 2 potentially explosive areas, please refer to the AH EN IL EX ZONE 2 application note. Check the labeling on the Inline terminal and the packaging (see Figure 2). 5561C001INTERBUS GL UL xx Potential routing 4 A maximumPotential routing 4 A maximum for use in Ex areasfor use in Ex areas II 3G Ex nAC IIC T4 XII 3G Ex nAC IIC T4 X LISTED 31ZN Cl. I, Zn. 2, AEx nC IIC T5Cl. I, Zn. 2, AEx nC IIC T5 Cl. I, Zn. 2, Ex nC IIC T5Cl. I, Zn. 2, Ex nC IIC T5 IBx IL xx xx xIBx IL xx xx x Order-No.: xxxxxxxOrder-No.: xxxxxxx Module-ID: xx HW/FW XX/-Module-ID: xx HW/FW XX/- WARNING: Explosion hazard Before startup, ensure that the following points and instructions are observed. WARNING: Explosion hazard When using terminals in potentially explosive areas, observe the technical data and limit values specified in the corresponding documentation (user manual, data sheet, package slip). WARNING: Explosion hazard Restrictions regarding the Inline system Please make sure that the maximum permissible current of 4 A flowing through potential jumpers U M and US (total current) is not exceeded when using the Inline terminals in potentially explosive areas.
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 8
8 Internal Circuit Diagram
Figure 3 Internal wiring of the terminal points Key: Protocol chip Microprocessor Supply unit with electrical isolation Electrically erasable programmable read- only memory Analog/digital converter Multiplexer Reference voltage Amplifier Optocoupler HART Modem Other symbols used are explained in the IL SYS INST UM E user manual. /G49 /G4E /G54 /G45 /G52 /G42 /G55 /G53 /G2B /G32 /G34 /G20 /G56 /G20 /G28 /G55 /G4D /G29 /G2B /G32 /G34 /G20 /G56 /G20 /G28 /G55 /G53 /G29 /G55 /G4C /G2B /G55 /G41 /G4E /G41 /G55 /G4C /G2D /G45 /G45 /G50 /G52 /G4F /G4D /G4F /G50 /G43 /G32 /G34 /G20 /G56 /G35 /G20 /G56 /G2B /G2D /G52 /G45 /G46 /G32 /G34 /G20 /G56 /G32 /G34 /G56 /G35 /G20 /G56 /G48 /G41 /G52 /G54 /G48 /G41 /G52 /G54 /G32 /G34 /G20 /G56 /G32 /G34 /G56 /G35 /G20 /G56 /GB5 /G50 /G4D /G55 /G58 /G36 /G37 /G35 /G38 /G41 /G30 /G30 /G37 OPC /GB5 /G50 /G78 /G78 /G78 /G58 /G58 /G58 /G45 /G45 /G50 /G52 /G4F /G4D /G4D /G55 /G58 /G52 /G45 /G46 /G48 /G41 /G52 /G54
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 9
9 Electrical Isolation
Figure 4 Electrical isolation of the individual function areas
10 Connection Notes
– Always connect analog sensors using shielded, twisted-pair cables. – Connect the shielding to th e terminal using the shield connection clamp. The clamp connects the shield to FE (functional earth ground) on the terminal side. Additional wiring is not necessary. – Insulate the shielding at the sensor or connect it with a high resistance and a capacitor to the PE potential. – Use a connector with shield connection when installing the sensors. Figure 5 and Figure 6 show the connection schematically (without a shield connection). Connection of the HART Devices Please note that the connections of the HART field devices (slaves) to the Inline-HART terminal differs for point-to-point and multidrop connections (see 10.1 and 10.2). Analog input 1 Local bus (IN) Bus interface OPC Local bus (OUT) UL UANA ULµC ±5 V +24 V +5 V +24 V +5 V ADC HART 1 HART 2 HART 1 HART 2 6758B004 24 V UANA Analog input 2 A B Electrical isolation between areas A and B ATTENTION: Do not connect voltages above ±10 V to a current input. This damages the module electronics as the maximum permissible current of ±40 mA is exceeded. The information can be found in Section "HART Operating Mode (Polling/Burst) for Point-to-Point Connections and Multidrop Networks" on page 16.
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 10
10.1 Connection of the HART Devices For a Point-to-Point Connection
Figure 5 Connection of active sensors (slaves) in 2-wire technology with shield connection Figure 6 Connection of passive sensors (slaves) in 2- wire technology with shield connection (Loop power)
10.2 Connection of the HART Devices in a Multidrop Network
Figure 7 Connection of sensors (s laves) in a multidrop network 1 2 6758C005 IN Address 0 6758C006 IN 24 V 1 2 Address 0 Slave 5 Slave 1 Slave 2 Slave 3 24 V 24 V Slave 5 Slave 4 1 2 1 2 1 2 1 2 Slave 3 Slave 2 Slave 1 Slave 4 Address 1 Address 2 Address 3 Address 4 Address 5 Address 6 Address 7 Address 8 Address 9 Address 10 6758C012
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 11
11 Programming Data/C onfiguration Data
Local Bus (INTERBUS) Other Bus Systems
12 Process Data
12.1 Assignment of the Terminal Points to the Input Data (See page 12)
ID code DC hex (220dec) Length code 02 hex Input address area 2 words Output address area 2 words Parameter channel (PCP) 2 words Register length (bus) 4 words For the programming/configuration data of other bus systems, please refer to the corresponding electronic device data sheet (e.g., GSD, EDS). For the assignment of the illustrated (byte.bit) view to your INTERBUS control or computer system, please refer to the DB GB IBS SYS ADDRESS data sheet. (Word.bit) view Word Word 0 B i t 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 (Byte.bit) view Byte Byte 0 Byte 1 B i t 7654321076543210 Channel 1 (connector 1) Signal Terminal point 1.2 Signal reference Terminal point 1.3 Shield (FE) Terminal point 1.4 (Word.bit) view Word Word 1 B i t 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 (Byte.bit) view Byte Byte 0 Byte 1 B i t 7654321076543210 Channel 2 (connector 4) Signal Terminal point 1.2 Signal reference Terminal point 1.3 Shield (FE) Terminal point 1.4
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 12
12.2 Process Data Input Words (IN)
The measured value 1 (main measured value) is transmitted, per channel, to the controller board or the computer by means of the IN process data input words. Figure 8 Sequence of the process input data words and display of the bits of the first process data word in the different formats Key The "IB IL" and "standardized representation" process data formats support extended diagnostics. The following error codes are possible: Please observe that the content of the IN process data input words 1 and 2 is relevant for point-to- point connections only. In multidrop mode, a current value of 4 mA is indicated. Channel 1 MSB LSB Channel 2 Process data word 1 Process data word 2 014 13 12 11 10 9 8 7 6 5 4 3 2 115 SB AV 014 13 12 11 10 9 8 7 6 5 4 3 2 115 OR0/4 OCSB AV ST IL, Standardized representation Format: 5564A009 SB Sign bit AV Analog value MSB Most significant bit LSB Least significant bit Code (hex) Error
8001 Overrange
8002 Open circuit
8004 Measured value invalid/
no valid measured value available
8010 Invalid configuration
8040 Terminal faulty
8020 Supply voltage not present
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 13
13 Formats for the Representation of
13.1 "IB IL" Format The "IB IL" format enables high-resolution representation of measured values in the 4 mA ... 20 mA measuring range. The measured value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit. This format supports extended diagnostics. Values >8000hex and <8100hex indicate an error. The error codes are listed on page 12. Measured value representation in "IB IL" format (15 bits) This format is the default format. To ensure that the terminal can be operated in previously used data formats, the measured value representation can be switched to other formats. Significant Measured Values Measuring range 4 mA ... 20 mA 13.2 "Standardized Representation" Format The measured values are represented in bits 14 through 0. An additional bit (bit 15) is available as a sign bit. The overrange limits and the open circuit threshold in the higher- level control system can be freely defined. In this format, data is standardized to the measuring range and represented in such a way that it indicates the corresponding value without conversion. In this format one bit has the value of 1 µA. This format supports extended diagnostics. Values >8000hex and <8100hex indicate an error. The error codes are listed on page 12. Error messages occur according to the "IB IL" format. Open circuit and short-circuit limits can be set with the PCP object called INIT_TABLE. Measured value representation in "standardized representation" format (15 bits) Significant Measured Values Measuring range 4 mA ... 20 mA Please note that the measured values shown are only relevant for a point-to-point connection. In multidrop mode a constant value is always displayed. 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 SB AV SB Sign bit AV Analog value Some codes are used for diagnostic functions. Therefore, the resolution is not 15 bits, but exactly calculated 14.9886847 bits. Input Data Word (Two's Complement) 4 mA ... 20 mA IInput hex dec mA 8001 Overrange > +21.339733 7F00 32512 +21.3397 7530 30000 +20.0 0001 1 +4.000533 0000 0 +4.0 to 3.2 8002 Open circuit < +3.2 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 SB AV SB Sign bit AV Analog value Input Data Word (Two's Complement) 4 mA ... 20 mA IInput hex dec mA 8001 Overrange > +22.5 (default, value can be defined) 4E20 20000 +20.0 8002 Open circuit <3.2 (default, value can be defined)
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 14 13.3 "PIO" Format PIO format enables high-resolution representation of measured values in the 0 mA ... 25 mA current measuring range. In this format, the measuring range of 0 mA ... 25 mA is divided into 2 16quantization steps (65 536 steps). Thus, unipolar measured currents with a resolution of 0.38 µA/ LSB can be represented. Signals between 0 mA ... 25 mA can be aquired. Measured value representation in "PIO" format (16 bits) Significant Measured Values Measuring range 0 mA ... 25 mA
13.4 Examples for Measured Value Representations
Measured value representation in various data formats. Process data input word Please note that error messages cannot be displayed in this format. 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 AV AV Analog value Input Data Word (Two's Complement) PIO IInput hex dec mA F5C2 62914 +24.0 CCCD 52429 +20.0 6666 26214 +10.0 0A3D 2621 +1.0 0001 1 +0.3815 µA 0000 0 +0 Measured value: 10 mA Format hex Value dec Value Meas- ured Value Measuring Range IB IL 3A98 15 000 10 mA 4 mA ... 20 mA PIO 6666 26 214 10 mA 0 mA ... 25 mA Standardized representation 2710 10 000 10 mA 4 mA ... 20 mA
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 15
14 HART Functions of the IB IL AI 2-HART (-PAC) Terminal
14.1 Recommendations For Its Use
The following table contains notes on the use of the terminal depending on your requirements for the application:
14.2 HART Communication
Data between masters and field devices is transmitted by superimposing an encoded digital signal on the 4 mA ... 20 mA current loop. Thanks to the encoding without mean value, simultaneous transmission of the analog signal is not affected. In accordance with the HART specification, operating devices (masters) send a voltage signal. Field devices (slaves) send their messages via load-independent currents. The current signals are converted to voltage signals at the internal resistance (i.e., its load) of the receiver. The signals are exchanged in accordance with the HART protocol specified by the HART foundation. In accordance with this master/slave procedure, the master initiates any communication activity. Slaves only start transmission upon request (see Figure 9). Figure 9 Exchanging HART commands The HART commands are transmitted as telegrams that are structured as follows: Application Recommendation – A HART slave – A measured value per HART slave Please use the process data input words (see Section 12 on page 11). These process data input words contain a 16-bit measured signal value ranging from 4 mA ... 20 mA. – A HART slave – Several measured values per HART slave Use polling mode (see 14.3 on page 16). The terminal cyclically requests measured value from the HART slave using HART communication. These measured values are provided by the terminal. They can be read with a PCP service. – A HART slave – Several measured values per HART slave – Fastest possible update of the measured value Use burst mode (see Section 14.3 on page 16). The HART slave continuously sends measured values using HART communication. These measured values are provided by the terminal. They can be read with a PCP service. – Several HART slaves – Each HART slave offers the same number of measured values Use the polling mode (see 14.3 on page 16). The terminal cyclically requests measured values from each HART slave using HART communication. These measured values are provided by the terminal. They can be read with a PCP service. – Unrestricted access to a HART slave Use the PASS_THROUGH mechanism (see Section 17.3 on page 23) to directly communicate with each HART device using HART communication. Please note that the HART telegram needs to be imbedded into the PCP telegram. The HART specification allows for two masters, i.e. usually the HART operating device as primary master and a hand-held operator panel as secondary master. Master Slave Master command with data, if req. Slave response telegram with data 6758C024
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 16 The HART Telegram Structure Key: Structure of the AD Address for Long Addresses: Long address (5 bytes) Further information on the HART topic can be downloaded from the homepage of the HCF user organization (HART COMMUNICATION FOUNDATION) at www.hartcomm.org The HART protocol can be implemented by any manufacturer and it can be freely used by any user. This open communication protocol between operating and field device is supported by the HART Communication Foundation (HCF). The HCF also provides technical support for the user. Among other things, the HCF monitors the openness of the protocol and manages device descriptions of all devices approved for operation. HART and HCF logo
14.3 HART Operating Mode (P olling/Burst) for Point-
to-Point Connections and Multidrop Networks Point-to-Point Connection (PTP) For a point-to-point connection, connect a HART field device (slave) to the HART operating device (master). The master communicates with precisely one HART device via one pair of wires. For this reason, the device address "0" must be set for the HART field device (cf. Figure 5 and Figure 6 on page 10). Multidrop Network In a multidrop network, the HART operating device communicates with up to 5 HART field devices being connected in parallel to the master via an individual wire pair each (cf. Figure 7). The device address of each slave determines which slave is addressed by the master. This device address is to be preset according to the range from 1 to 15. Please make sure – NOT to set the device address "0" for slaves – NOT to assign device addresses twice. Burst Mode Operation Burst mode operation is only possible for point-to-point connections. Here the slave is requested by the master to send a standard HART response telegram (burst telegram). This burst telegram is sent continuously by the HART slave until the master cancels the request. The command number of the response is variable and is transmitted via the CONTROL object. This command number is sent to the HART slave via command 108. After this, burst mode operation is enabled via command 109. The current response can be read via the POLL/ BURST_RESPONSE_CHANNEL_x_SLAVE_1 object. In this operating mode a timeout is maintained: If no response telegram is received within 800 ms, the object length is set to 0. When sending the burst command number or the burst enter command, the first status byte of the response is checked. If the HART device responds negatively to commands 108 or 109, the response is made available in Preamble SC AD HC BC ST DA CS x 1 byte bytes byte byte bytes xx xxx Preamble: The preamble is used to synchronize the HART devices. SC: Start byte The start byte indicates the sender (master, slave, slave in burst mode) and whether a long or a short address is used. AD: Address Length: 5 bytes = long address 1 byte = short address Via this address the two masters are distinguished, burst telegrams and field devices are identified. HC: HART command The HART command encodes the master's commands. BC: Byte count = ST + DA This byte indicates the number of transmitted status and data bytes. ST: Status The response message of a HART slave contains two status bytes. It indicates whether the data was received without errors (= 0) and the current field device status. DA: Data The maximum data length is 26 bytes, depending on the HART command. CS: Checksum of the entire telegram. Master Burst Bit 31, 30, 29, ...0
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 17 the POLL/BURST_RESPONSE_CHANNEL_x_SLAVE_1 object and the 'Burst trouble' bit is set in the STATUS object. This can be the case when the HART slave does not support burst mode operation. Polling Mode Operation In polling mode operation the Inline-HART terminal automatically sends HART commands to all HART slaves present at the same channel. Only HART commands 1, 2, and 3 are permitted. The current polling response can be read in the POLL_RESPONSE_CHANNEL_x_SLAVE_x object. If a slave sends a faulty HART response to the master, the corresponding slave is polled once again. A total of two polling trials are admissible. After the third faulty response, the object length is set to 0 and the next slave is polled. The HART Command Scope The scope of possible HART commands depends on the HART field device used. For a list of commands supported by your HART field device, please refer to the device- specific documentation of the device manufacturer.
14.4 HART Device Addresses
Setting the Device Address There are several ways of setting the device addresses: – Use the AutomationXplorer+ or PC WorX software offered by Phoenix Contact or – Set the device addresses with a hand-held operating device (cf. Figure 10) or – Contact the manufacturer of the HART field devices used. The default setting of the device addresses of the field devices is always "0". Therefore the devices are preset to point-to-point operation. For setting the device addresses of a HART field device connect a hand-held operating device to terminal points 2.2 and 2.3: Figure 10 Connecting a hand-held operating device for address modification 1 2 6758B013 IN
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 18
15 Introduction Into FDT Technology
15.1 General Informat ion About FDT/DTM
FDT (Field Device Tool) is the name of the software specification that standardizes the fieldbus-independent configuration, parameterization, and diagnostics of devices in an automation network. The device manufacturer provides device-specific drivers, the DTMs (Device Type Managers). The DTM of a device contains the device description and a device-specific user interface, for example. The DTM is used to integrate a device into the automation network using an FDT framework application (also known as FDT container software). Phoenix Contact is a member of the FDT Group (www.fdt-group.org). Compatibility of the DTM provided by Phoenix Contact for the IB IL AI 2-HART Inline terminal with FDT specification 1.2 has been tested and certified.
15.2 FDT and AutomationXplorer+
The AutomationXplorer+ software is an FDT framework application, in which DTMs from various manufacturers can be integrated. Point-to-point communication, even beyond network boundaries, enables user-friendly parameterization and diagnostics of devices and sensors/actuators via, e.g., Ethernet, INTERBUS, Profibus, HART, and in future PROFINET IO or IO Link protocol. Figure 11 shows on the left-hand side (Project Tree) the bus structure with the communication, gateway and device DTMs installed. The DTM for the Inline-Profibus bus coupler is shown in the middle part. The Inline-Profibus bus coupler and the Inline station are configured and diagnosed in this part. The DTM catalog is displayed on the right-hand side, sorted by device manufacturers as shown. Figure 11 AutomationXplorer+
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 19
15.3 FDT and PC WorX
FDT function have been integrated into the PC WorX software, the standard IEC-61131 programming environment for control systems from Phoenix Contact. This allows to integrate DTMs from various manufacturers, and to easily parameterize and diagnose devices and sensors/ actuators, e.g. via Ethernet, INTERBUS, HART and PROFINET IO and in future even via the IO Link protocol. The following figure shows the representation of a HART device in the PC WorX software. Figure 12 HARTdevice in PC WorX
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 20
15.4 Internet
AutomationXplorer+ can be downloaded at www.automationxplorer.phoenixcontact.com. Additional information about the software is also provided here. Device-specific DTMs can be downloaded at www.automationxplorer.phoenixcontact.com or www.download.phoenixcontact.com. For DTMs for devices from other manufacturers, please contact the relevant manufacturer.
15.5 Documentation
The "Startup of a HART-Compatible Device in AutomationXplorer+" application note uses an example to show how a HART-compatible device is handled in the AutomationXplorer+ software (see "Ordering Data" on page 3).
15.6 Special Addressi ng and Connection
(e.g., Using a Hand-Held Operating Device) In the PC WorX software, you do not need to program devices that you integrated into a bus structure using FDT/ DTM technoloy. These devices only need to be configured.
16 Reading Data Using the HART
In point-to-point operating mode, the main value of the field devices is transmitted as an analog signal (4 mA ... 20 mA) using process data. To read additional data you may use communications via the HART protocol. In the local bus and in the INTERBUS system, this protocol is implemented using PCP. When using a control system from Phoenix Contact and/or FDT communication: For communications via the HART protocol you can use a function block that supports both, point-to-point as well as multidrop mode. The function block can be downloaded at www.download.phoenixcontact.com . It takes over PCP communication completely. You do not have to read Section 17 „PCP Communication“ . When using other control systems: Create a function block for communications via the HART protocol. Use the information on PCP communication in Section 17.
17 PCP Communication
You only need to read this section if you want to create your own function block for the use of HART communication (see also Section 16). By default upon delivery, the terminal is configured for data transmission according to the parameters on page 30. You can configure the terminal to meet the requirements of your application. The terminal is configured in PCP mode using the INIT_TABLE object. For further information on PCP communication, please refer to the IBS SYS PCP G4 UM E user manual. Here you will also find more detailed information on error messages during PCP operation. The programs IBS CMD and Config+ (for standard controller boards) as well as PC WorX (for Field Controllers (FC) and Remote Field Controllers (RFC) and embedded controllers (ILC 3xx)) are available for the configuration and parameterization of your INTERBUS system. For more detailed information, please refer to the following user manuals: IBS CMD SWT G4 UM E, UM QS EN CONFIG+, and UM QS EN PC WORX.
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 21
17.1 Object Dictionary
Index Data Type N L Meaning Object Name Rights 0080hex String Var of Octet String 1 12 UNI QUE_IDENTIFIER_CHANNEL1_SLAVE1 rd 0081hex String Var of Octet String 1 12 UNI QUE_IDENTIFIER_CHANNEL1_SLAVE2 rd 0082hex String Var of Octet String 1 12 UNI QUE_IDENTIFIER_CHANNEL1_SLAVE3 rd 0083hex String Var of Octet String 1 12 UNI QUE_IDENTIFIER_CHANNEL1_SLAVE4 rd 0084hex String Var of Octet String 1 12 UNI QUE_IDENTIFIER_CHANNEL1_SLAVE5 rd 008Fhex String Var of Octet String 1 58 HART_PASS_THROUGH_CHANNEL1 rd/wr 0090hex String Var of Octet String 1 12 UNI QUE_IDENTIFIER_CHANNEL2_SLAVE1 rd 0091hex String Var of Octet String 1 12 UNI QUE_IDENTIFIER_CHANNEL2_SLAVE2 rd 0092hex String Var of Octet String 1 12 UNI QUE_IDENTIFIER_CHANNEL2_SLAVE3 rd 0093hex String Var of Octet String 1 12 UNI QUE_IDENTIFIER_CHANNEL2_SLAVE4 rd 0094hex String Var of Octet String 1 12 UNI QUE_IDENTIFIER_CHANNEL2_SLAVE5 rd 009Fhex String Var of Octet String 1 58 HART_PASS_THROUGH_CHANNEL2 rd/wr 00A0hex String Var of Octet String 1 40 POLL/ BURST_RESPONSE_CHANNEL1_SLAVE1 rd 00A1hex String Var of Octet String 1 40 P OLL_RESPONSE_CHANNEL1_SLAVE2 rd 00A2hex String Var of Octet String 1 40 P OLL_RESPONSE_CHANNEL1_SLAVE3 rd 00A3hex String Var of Octet String 1 40 P OLL_RESPONSE_CHANNEL1_SLAVE4 rd 00A4hex String Var of Octet String 1 40 P OLL_RESPONSE_CHANNEL1_SLAVE5 rd 00B0hex String Var of Octet String 1 40 POLL/ BURST_RESPONSE_CHANNEL2_SLAVE1 rd 00B1hex String Var of Octet String 1 40 P OLL_RESPONSE_CHANNEL2_SLAVE2 rd 00B2hex String Var of Octet String 1 40 P OLL_RESPONSE_CHANNEL2_SLAVE3 rd 00B3hex String Var of Octet String 1 40 P OLL_RESPONSE_CHANNEL2_SLAVE4 rd 00B4hex String Var of Octet String 1 40 P OLL_RESPONSE_CHANNEL2_SLAVE5 rd 00C0hex Array of Unsigned 16 2 2 Analog values PROCESS_DATA_VALUE rd 00C1hex Array of Unsigned 16 2 2 STATUS rd 00C2hex Array of Unsigned 16 2 2 Settings (rescan, polling and burst mode) CONTROL rd/wr 00C3hex Array of Unsigned 16 14 2 Terminal configuration INIT_TABLE rd/wr N: Number of elements rd: Read access permitted L: Element length in bytes wr: Write access permitted
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 22 17.2 UNIQUE_IDENTIFIER_CHA NNEL1_SLAVE1 ... 5 and UNIQUE_IDENTIFIER_CHANNEL2_SLAVE1 ... 5 Objects The UNIQUE_IDENTIFIER_CHANNEL1/2_SLAVE1 ... 5 objects contain the manufacturer's indentification data of the slaves connected to the HART terminal. Object Description The objects with the indices 0080hex-0084hex and 0090hex-0094hex all have the same structure. For every possible HART slave there is a unique identifier object. All 008xhex indices are valid for channel 1, all 009xhex indices are valid for channel 2. With every object, the unique identifiers of the corresponding HART slaves can be read. After power-up, these unique identifiers are read from the HART terminal to all present HART slaves. During this process, the "Scan Active" status bit is set. Byte Assignment of the UNIQUE_IDENTIFIER_CHANNELx_SLAVE1 ... 5 Objects Figure 13 Byte assignment of the UNIQUE_IDENTIFIER_CHANNELx_SLAVE1 ... 5 objects Error Message of This Object Parameters: Objects UNIQUE_IDENTIFIER_CHANNEL1_SLAVE1 ... 5 UNIQUE_IDENTIFIER_CHANNEL2_SLAVE1 ... 5 Access Read Data type String Var of Octet String Index 0080 hex - 0084hex (Channel 1, Slave 1...5) 0090hex - 0094hex (Channel 2, Slave 1...5) Subindex 00 hex Length (bytes) 12 bytes Data Device identification Error_Class Error_Code Additional_Code Meaning 08hex 00hex 0021hex A Read service was received. The data is not yet available because the terminal still is in "Scan Active" mode. Please wait until the "Scan Active" bit is set to 0 (see Figure 16 on page 28) 8765432191011 0 Manufacturer Identification Code 254 = FEdez hex Universal Command Revision Device ID Number Device ID Number Device ID Number Device Function Flags Device Type Code Number of Preambles Transmitter-spec CMD Revision Software Revision Hardware Revision 6758B027
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 23
17.3 HART_PASS_THROUGH_CHANNEL1 / 2 Object
The HART_PASS_THROUGH_CHANNEL1 / 2 objects map the data of a PCP service to a HART telegram. In this way HART devices can receive HART telegrams directly. Object Description Error Messages of This Object During Write Access Parameters: The error message "(08, 00, 0022)hex" can be disabled int he INIT_TABLE object. It ensures that a Write service to the HART_PASS_THROUGH_CHANNELx object is always followed by a Read service. In case, that two different applications use the HART_PASS_THROUGH_CHANNELx object of the terminal, the service sequence is to prevent response telegrams being overwritten before they have been read. For example, it is to be prevented that application 2 generates a HART telegram the response telegram of which overwrites the response telegram of the HART telegram of application 1 before application 1 has read it. There are two exceptions for which no error message is generated: 1. The preceding Write confirmation contains a negative result. 2. Between the first and the second Writ e service more than 30 seconds elapse. The time of 30 seconds is to prevent the error message "(08, 00, 0022)hex" in the following case: An application sends a Write service and crashes. After the restart it sends a Write service again. If between these two Write services a time of 30 seconds elapsed, the application is processed without an error message. There is a restriction with regard to the HART response transmission: The master address bit and the burst mode bit from the address field are always set to zero. Object HART_PASS_THROUGH_CHANNEL1 / 2 object Access Read, Write Data type String Var of Octet String Index 008F hex (channel 1) / 009Fhex (channel 2) Subindex 00 hex Length (bytes) 58 bytes, maximum Data Mapping the PCP user data to a HART telegram Error_Class Error_Code Additional_Code Meaning 08hex 00hex 0020hex – Polling or burst mode operation active – The message is to activate burst operating mode on a HART slave (command = 109 and data = 1) hex 00hex 0022hex A second Write service was received, without the HART response having been collected by a Read service. 08hex 00hex 0024hex HART timeout, the addressed HART slave did not answer 08hex 00hex 0025hex HART communication error 06hex 02hex 0000hex HART supply voltage not present
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 25 17.4 POLL/BURST_RESPONSE_CHANNEL1_SLAVE1 ... 5 and POLL/BURST_RESPONSE_CHANNEL2_SLAVE1 ... 5 Object The objects contain response telegrams of the HART devices that – during polling mode operation responded to a request telegram by the master or – are operated in burst mode. Object Description The objects with the indices 00A0hex-00A4hex and 00B0hex-00B4hex all have the same structure. For every possible HART slave there is a response object. All 00Axhex indices are valid for channel 1, all 00Bxhex indices are valid for channel 2. With every object, the unique identifiers of the corresponding HART slaves can be read. Since burst mode operation is only admissable for point-to-point connection, a burst response can only be read with index 00A0hex for channel 1 and index 00B0hex for channel 2. The HART response to be read comprises the complete HART telegram format, however without preamble and checksum. In this way, the object has the same format as the PASS_THROUGH object. For an example of a HART response. please refer to page 26. Error Message of This Object Parameters: Object POLL/BURST_RESPONSE_CHANNEL1_SLAVE1 ... 5 POLL/BURST_RESPONSE_CHANNEL2_SLAVE1 ... 5 Access Read Data type String Var of Octet String Index 00A0 hex - 00A4hex (Channel 1, Slave 1...5) 00B0hex - 00B4hex (Channel 2, Slave 1...5) Subindex 00 hex Length (bytes) 40 bytes, maximum Data Measured data Error_Class Error_Code Additional_Code Meaning 06hex 02hex 0030hex HART supply voltage not present Check the voltage supply of the Inline HART terminal. Please observe that the measured data structure depends on the polling mode set. For further information, please refer to the HART command overview of the HART Communication Foundation HCF.
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 26 Example of a HART Response The following example only deals with the response telegram in polling mode operation. Here, only the 3 HART commands 1, 2 or 3 can be selected. The response telegram is structured according to the selected command. The data of a HART response telegram between preamble and checksum are made available as user data in the PCP read confirmation. The object is read with a PCP read request. The content of a read confirmation depends on the selected HART command. Structure of the PCP read confirmation: Byte Meaning Command 1 Command 2 Command 3 PCP header 1 Message code 1st byte 80 80 80
2 Message code 2nd byte 81 81 81
3 Parameter count 1st byte 00 00 00
4 Parameter count
hex = 11dec 0Chex = 12dec 14hex = 20dec
5 Invoke ID xx xx xx
6 Comm. reference xx xx xx
7 Result 1st byte 00 00 00
8 Result 2nd byte 00 00 00
9 Not used -- -- --
10 Length 0F
hex = 15dec 12hex = 18dec 22hex = 34dec HART part 11 Start character 86 hex 86hex 86hex
12 Address 1st byte xx xx xx
13 Address 2nd byte xx xx xx
14 Address 3rd byte xx xx xx
15 Address 4th byte xx xx xx
16 Address 5th byte xx xx xx
17 Command 01 02 03
18 Byte count 07 A
hex = 10dec 1Ahex = 26dec
19 Status 1st byte 00 00 00
20 Status 2nd Byte 00 00 00
21 Data PV units code Current 1st byte Current 1st byte
22 Data PV 1st byte Current 2nd byte Current 2nd byte
23 Data PV 2nd byte Current 3rd byte Current 3rd byte
24 Data PV 3rd byte Current 4th byte Current 4th byte
25 Data PV 4th byte Percent of range 1st byte PV units code
26 Data Percent of range 2nd byte PV 1st byte
27 Data Percent of range 3rd byte PV 2nd byte
28 Data Percent of range 4th byte PV 3rd byte
29 Data PV 4th byte
30 Data SV units code
31 - 34 Data (4 bytes) SV 1st to 4th byte
35 Data TV units code
36 - 39 Data (4 bytes) TV 1st to 4th byte
40 Data FV units code
41 - 44 Data (4 bytes) FV 1st to 4th byte
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 27
17.5 PROCESS_DATA_VALUE Object
This object provides measured values that are also contained in the IN process data (see Section 12.2 on page 12). Object Description This object is only relevant for a point-to-point connection. Object PROCESS DATA VALUE Access Read Data type Array of Unsigned 16 2 x 2 bytes Index 00C0 hex Subindex 00 hex 01hex 02hex Both channels Channel 1 Channel 2 Length (bytes) For subindex 0, the length is 4 bytes. For subindex >0, the length is 2 bytes. Data 1st word for channel 1 2nd word for channel 2 Please observe that the data read out with this object depends on the addressed HART field device.
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 28
17.6 STATUS Object
The STATUS object indicates the operating state of each channel of the terminal. Object Description Description of an Element/Bit Assignment Figure 16 Assignment of an elemen t of the STATUS object (00C1hex) These two supply voltage error bits are reset after voltage is restored. If the Burst Trouble bit is set, you can set it via an error- free write access onto the CONTROL object. Object STATUS Access Read Data type Array of Unsigned 16 2 x 2 bytes Index 00C1 hex Subindex 00 hex 01hex 02hex Both channels Channel 1 Channel 2 Length (bytes) For subindex 0, the length is 4 bytes. For subindex >0, the length is 2 bytes. Data 1st word (element) for channel 1 2nd word (element) for channel 2 – The polling modes can be selected depending on the HART field devices used. – The data read out with this object de pend on the addressed HART field device. Number of HART-Slaves 3789101112131415 6758B022 Scan Active Burst Mode Active Poll Mode Active Analog Supply Fail HART Supply Fail Burst Trouble 1 02456
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 29
17.7 CONTROL Object
Set the polling mode or burst mode via this object for each channel of the terminal. Object Description Description of an Element/Bit Assignment Figure 17 Assignment of an elemen t of the CONTROL object (00C2hex) Please observe that burst and polling mode cannot be active simultaneously (see also "HART Operating Mode (Polling/ Burst) for Point-to-Point Connections and Multidrop Networks" on page 16). Re-Scan The HART interface is re-initialized via the Re-Scan bit. The UNIQUE_IDENTIFIER... objects are deleted and the scan process is introduced again. In this way, all connected slaves on the affected HART channel are detected. During this process, the Scan Active bit is reset in the STATUS object. The Re-Scan bit is cannot be read back in this object. Object CONTROL Access Read, Write Data type Array of Unsigned 16 2 x 2 bytes Index 00C2 hex Subindex 00 hex 01hex 02hex Both channels Channel 1 Channel 2 Length (bytes) For subindex 0, the length is 4 bytes. For subindex >0, the length is 2 bytes. Data 1st word (element) for channel 1 2nd word (element) for channel 2 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 Re- Scan Poll command 0: Polling mode not active 1, 2, 3 allowed Burst command 0: Burst mode not active
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 30 Error Message of This Object:
17.8 INIT_TABLE Object
Writing the INIT_TABLE object with a Write service configures the terminal. Object Description Error_Class Error_Code Additional_Code Meaning 06hex 02hex 0000hex HART supply voltage not present 08hex 00hex 2020hex No HART slave found at the channel and polling or burst-command <> 0. 08hex 00hex 2022hex Scan phase active and (polling command <> 0 or burst-command <> 0). 08hex 00hex 2030hex Polling and burst command (both) <> 0. 08hex 00hex 2130hex Polling command > 3. 08hex 00hex 2230hex Re-Scan bit set and polling command <> 0 or burst-command <> 0. 08hex 00hex 2330hex A bit of the reserved bits 12, 13 or 14 is set. 08hex 00hex 2040hex Polling command <> 0 and burst mode still active. 08hex 00hex 2043hex Burst command <> 0 and polling mode still active. 08hex 00hex 2047hex Burst mode is to be enabled for multidrop environment. Object INIT_TABLE Access Read, Write Data type Array of Unsigned 16 14 x 2 bytes Index 00C3 hex Subindex 00 hex 01hex 02hex 03hex 04hex 05hex 06hex 07hex 0Ehex Write all elements Analog configuration Limit value for open circuit Limit value for overrange Reserved Reserved System settings Reserved Reserved Length (bytes) For subindex 0, the length is 28 bytes. For subindex >0, the length is 2 bytes. Data IB IL AI 2-HART terminal configuration
IB IL AI 2-HART (-PAC) 6758_en_01 PHOENIX CONTACT 31 Element Description (Subindex) Analog Configuration Element Figure 18 Assignment of the analog configuration element (index 00C3, hex, subindex 1hex) Open Circuit Element In the "Standardized representation" format this element is used to determine the limit value for open circuit. If the current falls below the limit value the error message open circuit 8002hexis indicated in the IN process data. By default, the value is 3200dec, which corresponds to 3.2 mA. Overrange Element In the "Standardized Representation" format this element is used to determine the limit value for overrange. If the current is above the limit value the Overrange error message 8001hexis indicated in the IN process data. By default, the value is 22500dec, which corresponds to 22.5 mA. System Settings Element Figure 19 Assignment of the system settings element (index 00C3, hex, subindex 06hex) The Peripheral Fault that can be switched off, relates to the response of a supply voltage interrupt. Error Messages of This Object If a Write service writes an invalid value to an element, the service will be aborted with a negative confirmation. Here, the parameters are the following: The high byte of the ADDITIONAL_CODE (xx) contains the number of the affected element. If several elements are affected, the highest number is given. If, for example, the "analog configuration" element is written with the value 0001hex, an error message with the ADDITIONAL_CODE 0130hex will be displayed, because the first element is faulty. 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 Filter Format The options in bold are default settings. Code Filter 0 16-fold mean value
1 No mean-value generation
24 - f o l d m e a n v a l u e 3 32-fold mean value Code Format 0 IB IL 4 mA ... 20 mA
1 Standardized representation
3 Reserved
Error_Class Error_Code Additional_Code Meaning 08hex 00hex xx30hex Value is out of range 014 13 12 11 10 9 8 7 6 5 4 3 2 1 6758D010 Peripheral Fault: 1: disable 0: enable Error message 08, 00, 0022 with PASS_THROUGH objects 1: disable 0: enable
IB IL AI 2-HART (-PAC) 6758_en_01 32PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00 PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300 www.phoenixcontact.com
18 Start Behavior
After power-up, the terminal searches both HART channels for possible slaves. To do this, the HART command 0 at the short addresses 0 up to 15 are sent in ascending order. If the slave already responds to short address 0, the search process is aborted. If not, the search process continues until either the short address 15 is reached or the number of slaves detected equals five. For a command to short address 0, 6 different attempts have been executed where normally only 1 attempt takes place. During this process being executed in parallel on both channels of the Inline HART terminal, the Scan Active bit is set. From the detected slaves, the UNIQUE_IDENTIFIER_CHANNEL1/2_SLAVE1...5 objects are read and can then be read via the 008xhex and 009xhex object indices. Among others the UNIQUE_IDENTIFIERx object contains the unique 38-bit address of the HART slave. The UNIQUE_IDENTIFIERx objects are distributed onto the objects in the order in which they are found during the search process. Example: A multidrop network at the HART channel 1 comprises the short addresses 1, 3, 7, 12, and 14. Distribution of the UNIQUE_IDENTIFIER1 objects: The number of detected slaves can be read via the STATUS (00C1hex) object. After the search process, the Inline HART terminal waits for 4 seconds for a HART slave to send a burst telegram, if required. This case is possible because some HART slaves save there settings in a non-volatile memory. If a slave is in active burst mode, it contiunes to send burst telegrams after the voltage interrupt. After having received a burst telegram, the Inline HART terminal sends a request telegram to the slave in question in order to switch off burst mode. Only then a search process starts. Duration of the Scan Process For the Worst Case (no HART device present): Index (hex) Distribution Description
0080 UNIQUE_IDENTIFIER_
CHANNEL1_SLAVE1 Slave with short address 1
0081 UNIQUE_IDENTIFIER_
CHANNEL1_SLAVE2 Slave with short address 3
0082 UNIQUE_IDENTIFIER_
CHANNEL1_SLAVE3 Slave with short address 7
0083 UNIQUE_IDENTIFIER_
CHANNEL1_SLAVE4 Slave with short address 12
0084 UNIQUE_IDENTIFIER_
CHANNEL1_SLAVE5 Slave with short address 14 Burst waiting time 4 seconds 6 messages to addresses 0 6 * 330 ms = approx. 2 seconds 1 messages to addresses 1-15 15 * 330 ms = approx. 5 seconds Total approx. 11 seconds