62T1806 BELDEN

Document overview

  • Manufacturer or author: Provided By digicamel.com
  • PDF pages: 2

Technical content

Product: 62T1806 Inst PVC/PVC, 6 Tri #18 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, TC NPLF 90C Dry 75C Wet Product Description UL Instrumentation, 6 Triad 18AWG (7x26) Bare Copper, PVC-NYL Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, Black PVC Outer Jacket, TC NPLF 90C Dry 75C Wet SUN RES DIR BUR Technical Specifications Physical Characteristics (Overall) Conductor AWG Stranding Material Nominal Diameter 18 7x26 BC - Bare Copper 0.045 in Conductor Count: 18 Total Number of Triads: 2 Insulation Material Nominal Diameter PVC/Nylon - Polyvinyl Chloride + Nylon 0.088 in Color Chart Number Color Triad 1 Black, White and Red Numbered 1 Triad 2 Black, White and Red Numbered 2 Inner Shield Type Material Material Trade Name Coverage [%] Drainwire Material Drainwire Diameter Drainwire AWG Tape Bi-Laminate (Alum+Poly) Beldfoil® 100% TC - Tinned Copper 0.029 in 22 Outer Shield Type Material Material Trade Name Coverage [%] Drainwire Material Drainwire Diameter Drainwire AWG Tape Bi-Laminate (Alum+Poly) Beldfoil® 100% TC - Tinned Copper 0.029 in 22 Outer Jacket Material Nominal Diameter Nominal Wall Thickness PVC - Polyvinyl Chloride 0.470 in 0.047 in

Electrical Characteristics

5.86 Ohm/1000ft

Max. Recommended Current [A]

4.8 Amps per Conductor at 30ºC

UL Temp Rating: 90°C Dry/75°C Wet Operating Temperature Range: -25°C To +90°C Mechanical Characteristics Bulk Cable Weight: 252 lbs/1000ft Max. Pull Tension: 134 lbs Min Bend Radius (Overall): 4.75 in Standards NEC Articles: Article 336 NEC/(UL) Compliance: NPLF, TC-ER IEEE Compliance: 1202 Applicable Environmental and Other Programs EU Directive 2000/53/EC (ELV): Yes EU Directive 2011/65/EU (RoHS 2): Yes EU Directive 2012/19/EU (WEEE): Yes EU Directive 2015/863/EU (RoHS 2 amendment): Yes EU Directive Compliance: EU Directive 2003/11/EC (BFR) EU CE Mark: Yes CA Prop 65: Yes Suitability Suitability - Indoor: Yes Suitability - Outdoor: Yes Suitability - Sunlight Resistance: Yes Flammability, LS0H, Toxicity Testing CSA/C(UL) Flammability: FT4 UL voltage rating: 600 V RMS (Type TC) Related Part Numbers Variants Item # Put-Up Type 62T1806 0105500 Reel History Update and Revision: Revision Number: 0.39 Revision Date: 04-14-2023 © 2023 Belden, Inc All Rights Reserved. Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without notice, and the listing of such information and specifications does not ensure product availability. Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein. All sales of Belden products are subject to Belden's standard terms and conditions of sale. Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden's knowledge, information and belief at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the product.