61T1401 BELDEN

Document overview

  • PDF pages: 2

Technical content

Page 1

PDF page 1 diagram

Product: 61T1401

TC VN/PVC, 1 Tri #14 Str BC, PVC-NYL Ins E1, OS, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Product Description

UL Type TC (1277) VN/PVC, 1 Triad 14AWG (7x22) Bare Copper, PVC-NYL Insulation E1 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket,

600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Technical Specifications

Physical Characteristics (Overall)

Conductor

Element AWG Stranding Material No. of Triads
Conductor(s) 14 7x22 BC - Bare Copper 1
Conductor Count: 3

Insulation

Material Nominal Diameter
PVC/Nylon - Polyvinyl Chloride + Nylon 0.116 in

Color Chart

Number Color

1 Black

2 White

3 Red

Outer Shield

Type Material Material Trade Name Coverage [%] Drainwire Material Drainwire AWG
Tape Bi-Laminate (Alum+Poly) Beldfoil® 100% TC - Tinned Copper 18

Outer Jacket

Material Nominal Diameter Nominal Wall Thickness
PVC - Polyvinyl Chloride 0.348 in 0.047 in

Electrical Characteristics

Conductor DCR

Nominal Conductor DCR

2.52 Ohm/1000ft

Current

Max. Recommended Current [A]

25 Amps per Conductor at 30ºC

Voltage

UL Description UL Voltage Rating Voltage Rating [V]
TC 600 V RMS (Type TC) 600 V RMS (Type TC)
NPLF 150 V RMS (NPLF)

Page 2

Temperature Range

UL Temp Rating:

75°C Wet, 90°C Dry

Operating Temperature Range:

-30°C To +90°C

Mechanical Characteristics

UV Resistance:

Yes

Bulk Cable Weight:

75 lbs/1000ft

Max. Pull Tension:

97 lbs

Min. Bend Radius/Minor Axis:

3.48 in

Standards

NEC/(UL) Compliance:

NPLF, TC-ER, THHN, THWN

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV):

Yes

EU Directive 2011/65/EU (RoHS 2):

Yes

EU Directive 2012/19/EU (WEEE):

Yes

EU Directive 2015/863/EU (RoHS 2 amendment):

Yes

EU Directive Compliance:

Yes

EU CE Mark:

Yes

Suitability

Suitability - Burial:

Yes

Suitability - Indoor:

Yes

Suitability - Outdoor:

Yes

Suitability - Sunlight Resistance:

Yes

Flammability, LS0H, Toxicity Testing

UL Flammability:

UL 1685 UL Loading

IEEE Flammability:

1202

UL voltage rating:

600 V RMS (Type TC)

Plenum/Non-Plenum

Plenum (Y/N):

No

Related Part Numbers

Variants

Item # Put-Up Type

61T1401 0105000 Reel

History

Update and Revision:

Revision Number: 0.45 Revision Date: 11-27-2023

© 2024 Belden, Inc All Rights Reserved. Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without notice, and the listing of such information and specifications does not ensure product availability. Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,

negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein. All sales of Belden products are subject to Belden's standard terms and conditions of sale. Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden's knowledge, information and belief at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product

Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the product.