Page 1

Control block CPX-CEC

Part number: 567346

PDF page 1 diagram

Data sheet

Feature Value
Dimensions W x L x H 50 mm x 107 mm x 55 mm
Type code CPX
Device-specific diagnostics Channel-oriented and module-oriented diagnostics Undervoltage/short circuit of modules Diagnostic memory
CPU data 32 MB flash 32 MB RAM 400 MHz processor
Configuration support CODESYS V2.3
Parameterization CODESYS V2.3
Additional functions Diagnostic functions RS232 communication function
Control elements Rotary switch for RUN/Stop
Programming, operating language DE, EN
Programming, file handling support yes
Baud rate 10/100 bit/s as per IEEE 802.3 (10BaseT) or 802.3u (100BaseTx)
Processing time Approx. 200 µs/1 k instruction
Data interface RS232 interface Sub-D, 9-pin, socket 9.6 ... 230.4 kBit/s Galvanically isolated
Intrinsic current consumption at nominal operating voltage Typ. 85 mA
IP address setting DHCP Via CODESYS Via MMI
Function blocks Read CPX module diagnostics CPX diagnostic status Copy CPX diagnostic trace and others
Flag 30 kB remanent data 8 MB global data memory CODESYS variable concept
Nominal operating voltage DC load voltage Without pneumatics: 18 ... 30V 24 V With midi/maxi pneumatic valves types: 21.6 ... 26.4 V With pneumatic type CPA: 20.4 ... 26.4 V With pneumatics type MPA: 18 ... 30 V
Nominal operating voltage DC 24 V
Power failure buffering 10 ms
Programming software CODESYS provided by Festo V2.3

6/14/21 - Subject to change - Festo AG & Co. KG

1/2

Page 2

Feature Value
Programming language as per IEC 61131-3 KOP AWL ST FUP AS Additionally CFC
Program memory 4 MB user program
Corrosion resistance class (CRC) 2 - Moderate corrosion stress
Storage temperature -20 °C ... 70 °C
Relative air humidity 95 % Non-condensing
Degree of protection IP65 IP67
Ambient temperature -5 °C ... 50 °C
Product weight 155 g
Ethernet, number 1
Ethernet, data transmission speed 10/100 Mbit/s
Ethernet, supported protocols TCP/IP, EasyIP, Modbus® TCP
Ethernet, connector plug RJ45 Socket 8-pin
Protocol CODESYS level 2 EasyIP Modbus® TCP TCP/IP
Ethernet interface RJ 45 (socket, 8-pin)
LED display (bus-specific) TP: link/traffic
LED display (product-specific) ERR: PLC runtime error M: modify/forcing active PL: load supply PS: electronics supply, sensor supply RUN: PLC status SF: system fault STOP: PLC status
Note on materials RoHS-compliant
Housing material PA-reinforced PC

6/14/21 - Subject to change - Festo AG & Co. KG