© PHOENIX CONTACT 2015-07-143379_en_B FL MC 2000T… Data sheet 1D e s c r i p t i o n Media converters provide a high level of immunity to interference and long transmission range in industrial applications by converting the 10/100Base-Tx Ethernet interface to fiber optics (100 Mbps according to FX standard). The FL MC 2000T… provides a high level of diagnostics with remote alarm notification, and high performance with selectable latency. Compatible with legacy devices through configurable data rate and duplex options. Optional security frames restrict unauthorized access and cable changes. A wide temperature range allows it to be used in rugged as well as factory applications. The RJ45 port offers an auto crossing function, which means it is not necessary to make a distinction between 1:1 and crossover cables. 2F e a t u r e s The FL MC 2000T… converters offer the following features: – 10/100Base-Tx – -40°C to 75°C operating range – Auto crossing simplifies cabling – Link fault pass through and port diagnostics – Selectable pass through or store and forward operation for optimized performance and data integrity – Layer 1 security for the RJ45 port – Individual LEDs at each po rt indicate communication activity and data rate – Redundant power supply capable with local (LED) and remote (dry contact) alarms to indicate failure of one or both power supplies – Mounts on NS 35 DIN rails Make sure you always use the latest documentation. It can be downloaded at phoenixcontact.com/ This document is valid for all products listed in the “Ordering data” on page 2. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections
FL MC 2000T… 3379_en_B PHOENIX CONTACT 2/7 3O r d e r i n g d a t a
4 Technical data
Description Type Order No. Pcs./Pkt. Fiber optic converter, SC connection (1310 nm), for converting 10/ 100Base-Tx to multi-mode fiberglass FL MC 2000T SC 2891315 1 Fiber optic converter, ST connection (1310 nm), for converting 10/ 100Base-Tx to multi-mode fiberglass FL MC 2000T ST 2891316 1 Fiber optic converter, SC connection (1310 nm), for converting 10/ 100Base-Tx to single-mode fiberglass FL MC 2000T SM20 SC 2891317 1 Fiber optic converter, SC connection (1310 nm), for converting 10/ 100Base-Tx to single-mode fiberglass FL MC 2000T SM40 SC 2891318 1 Accessories Description Type Order No. Pcs./Pkt. Universal end clamp E/NS 35 N 0800886 50 Patch cable, CAT 5, pre-assembled, 0.3 m long FL CAT5 PATCH 0,3 2832250 10 Patch cable, CAT 5, pre-assembled, 0.5 m long FL CAT5 PATCH 0,5 2832263 10 Patch cable, CAT 5, pre-assembled, 1.0 m long FL CAT5 PATCH 1,0 2832276 10 Patch cable, CAT 5, pre-assembled, 1.5 m long FL CAT5 PATCH 1,5 2832221 10 Patch cable, CAT 5, pre-assembled, 2.0 m long FL CAT5 PATCH 2,0 2832289 10 Patch cable, CAT 5, pre-assembled, 3.0 m long FL CAT5 PATCH 3,0 2832292 10 Patch cable, CAT 5, pre-assembled, 5.0 m long FL CAT5 PATCH 5,0 2832580 10 Patch cable, CAT 5, pre-assembled, 7.5 m long FL CAT5 PATCH 7,5 2832616 10 Patch cable, CAT 5, pre-assembled, 10.0 m long FL CAT5 PATCH 10 2832629 10 General data Function Converter, Ethernet 10/100Base-Tx to fiber optic; conforms to standard IEEE 802.3 Housing dimensions (width x height x depth) 28 x 110 x 70 mm Weight, without connectors 315 g Operating temperature -40°C … 75°C Storage temperature -40°C … 85°C Degree of protection IP20, DIN 40050, IEC 60529 Protection class Class 3 VDE 0106; IEC 60536 Humidity (operation and storage) 5% to 95%, no condensation Air pressure (operation) 66 kPa … 108 kPa, 4850 m above sea level Air pressure (storage) 66 kPa … 108 kPa, 4850 m above sea level Mounting NS 35 (EN 60715) Preferred mounting position Perpendicular to a standard mounting rail Connection to protective earth ground Snapped onto a grounded mounting rail Latency (pass through mode) 865 ns
FL MC 2000T… 3379_en_B PHOENIX CONTACT 3/7 Supply voltage (US) Connection type Removable, screw-clamp connector Wire size (solid/stranded/AWG) 0.2 … 2.5 mm² / 0.2 … 2.5 mm² / 24 … 12 AWG Recommended PE wire size 2.5 mm 2 Nominal power supply 24 V DC, 48 V DC Permissible ripple 3.6 V pp within the permissible voltage range Permissible voltage range 12 V DC … 57 V DC Current consumption, typical 75.5 mA @ 24 V DC Inrush current at 48 V DC 8.4 A (400 µs) Test voltage 500 V AC for one minute Protection against polarity reversal Present Interfaces Properties of RJ45 port Total number of RJ45 Ethernet interfaces 1 Connection format RJ45 female Connection medium Twisted-pair cable with a conductor cross section of 0.14 mm2 to 0.22 mm2 Cable impedance 100 Transmission speed 10/100 Mbps Maximum network segment length 100 m MDI/MDIx switchover Automatic (auto MDI/MDIX) Properties of fiber optic port Total number of FO ports 1 Connection format SC-duplex, ST Wavelength 1310 nm Transmission speed 100 Mbps Transmission length FL MC 2000T SC, FL MC 2000T ST FL MC 2000T SM40 SC FL MC 2000T SM20 SC 8 km with F-G 62.5/125 0.7 dB/km F1000 3.3 km with F-G 62.5/125 2.6 dB/km F600 9.6 km with F-G 50/125 0.7 dB/km F1200 5.3 km with F-G 62.5/125 1.6 dB/km F800 2 km with HCS GI fiber with F-GK 200/230 40 km with F-G 9/125.0 0.36 dB/km 36 km with F-G 9/125.0 0.4 dB/km 29 km with F-G 9/125.0 0.5 dB/km 20 km with F-G 9/125.0 0.36 dB/km Alarm contacts Voltage, maximum 250 V AC Current carrying capacity, maximum 1 A (including inrush) Mechanical tests Vibration resistance according to IEC 60068-2 10 … 150 Hz, 5g Shock test according to IEC 60068-2 30g, 11 ms Free fall according to IEC 60068-2-32 100 cm Conformance IEC 61000-6.2 Approvals General c ROHS WEEE 2002/96/EC
FL MC 2000T… 3379_en_B PHOENIX CONTACT 4/7
5 Dimensions
Figure 1 Housing dimensions 6O v e r v i e w Figure 2 Connectors and LEDs
6.1 Diagnostic and status indicators
Depth = 70 mm Des. Color Status Meaning US1 and US2 green On Supply voltage (US) in the tolerance range Off Supply voltage (US) too low Alarm red On US1 or US2 is too low or missing Port link failure Off Normal operation LEDs Power and alarm connector RJ45 port FO port DIP switch
FL MC 2000T… 3379_en_B PHOENIX CONTACT 5/7
6.2 Data transmission LEDs
7 Installation
Install the module on a clean NS 35 rail. To avoid contact resistance use only clean, corrosion-free rails that meet the EN 60715 standard. End clamps can be mounted on both sides of the module to stop the modules from slipping on the rail.
7.1 Assembly
- Place the module onto the rail from above. The upper holding keyway must be hooked onto the top edge of the rail. 2. Push the module from the front towards the mounting surface. 3. Once the module has been snapped on properly, check that it is fixed securely on the rail.
7.2 Removal
- Insert a suitable tool (e.g., screwdriver) into the arresting latch and pull it down. 2. Pull the module slightly away from the mounting surface. 3. Lift the module from the rail.
7.3 Power connection
The device is designed for SELV and PELV operation at +24 V DC according to IEC 61140/EN 61140. Only SELV and PELV according to the defined standards may be used for supply purposes. Snapping the device onto a grounded rail connects it to the ground potential. Figure 3 Power connections for redundant power supply Figure 4 Power connections for single power supply Use power conductors between 0.2 - 2.5 mm² (24 -12 AWG). Torque connection screws to 0.5 - 0.6 Nm (5 - 7 lb-in.). LED Status Meaning LNK/ACT On Indicates an electrical link Flashing Data transmission is in process (RJ45 port only) On Port is operating at
100 Mbps
10 Mbps
LNK/ACT LED: ON: indicates an electrical link Flashing: indicates network traffic (at high data rates the blinking is in a constant rate) CAUTION: Only qualified personnel may start up and operate this device. Qualified personnel are persons authorized to start up, ground and mark devices, systems and equipment according to the standards of safety technology. NOTE: The FL MC 2000T… module is designed for SELV and PELV operation according to IEC 61140/EN 61140. NOTE: Connect the mounting rail to protective earth ground using a grounding terminal block. The modules are grounded when they are snapped onto the rail. Connect protective earth ground with low impedance.
FL MC 2000T… 3379_en_B PHOENIX CONTACT 6/7
7.4 Alarm contact
The FL MC 2000T… provides contacts (R1, R2) for a remote alarm if a failure is detected. The alarm is triggered if one or both power supplies fail. An alarm can be triggered if a port link fails. Individual port alarms can be enabled via a DIP switch located on the bottom of the device. The alarm relay is a normally closed type. When there are no faults, the contact is held open. When a fault occurs, the relay is de-energized to close the contact.
7.5 Ethernet interface
The FL MC 2000T… has one Ethe rnet port on the front in RJ45 format to which a twisted-pair cable with an impedance of 100 can be connected. The data transmission speed is 10/100 Mbps. This port has an auto crossing function: it is not necessary to make a distinction between 1:1 or crossover Ethernet cables.
- Connect the twisted-pair cable to the RJ45 connector.
- Ensure the connection is secure by gently pulling it.
7.6 Fiber optic interface
- Connect the fiber optic cable to the SC-duplex or ST plug-in connector for the transmit and receive channel. Make sure the keying is in the correct position.
- Ensure the connection is secure by gently pulling it. 8C o n f i g u r a t i o n A seven-position DIP switch on the bottom surface of the FL MC 2000T… allows configuration of operating characteristics. Figure 5 DIP switch
8.1 Link fault pass through (DIP 1)
Link fault pass through is a function that allows diagnostics from one port to pass through to the other port. The link status of the RJ45 port is always forwarded to the fiber optic port. However, link fault pass through from the fiber optic port to the RJ45 port is selectable (via DIP 1). When link fault pass through is disabled, devices may not be able to detect that the fiber optic network connection is interrupted. The connected device either doesn’t know it is not communicating (diagnostics cannot be generated) or it continually attempts to re-establish communication, increasing the network load and application response time. When enabled, a link loss at the fiber optic port is forwarded to the RJ45 port, so both ports of the converter are disabled. DIP 1 can be used to enable link fault pass through (LFPT), which allows faults to propagate globally through the system, or stay local to each link segment. In addition to the remote alarm, failure is also indicated by turning the alarm LED on. WARNING: During operation, do not look directly into transmitter diodes or use visual aids to look into the glass fibers. The infrared light is not visible. NOTE: Do not remove dust protection caps until just before the plug-in connectors are connected. They prevent contamination of the transmit and receive elements. NOTE: Observe the cable manufacturer’s technical data when handling the various fiber optic cables. In order for the communication path to be immune to interference, the permissible values for bending radius, tensile force and pressure force must not be exceeded. Link fault pass through should only be used when two media converters are connected in series. DIP Position Function
1 ON LFPT enabled (global): in the event of a
fault, the entire connection is disabled. OFF LFPT disabled (local): in the event of a fault, only the interrupted part is disabled. This is useful during startup and in the event of an error.
FL MC 2000T… 3379_en_B 7/7PHOENIX CONTACT GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany phoenixcontact.com
8.2 Alarm enabling
The alarm contacts are configurable on a port basis. DIP 5 controls port X1 (fiber optic) and DIP 6 controls port X2 (RJ45).
8.3 Security frames
The RJ45 port accepts security frames. FL PLUG GUARD… security frames lock the RJ45 cable in place, reducing the chance of an unauthorized change or network access. In pass through mode with link fault pass through enabled, the media converter boot-up time is 26 s. The time to transmit the TX port link status from the first converter, through the fiber optic cable to the TX port of the second converter is 3 µs. In pass through mode with link fault pass through disabled, the media converter boot-up time is less than 2 s. DIP Position Function
2 ON X1 port mode is in auto-negotiation mode
OFF X1 port mode is set by DIP switches 3 and 4
3 ON X1 port data rate set to 10 Mbps
OFF X1 port data rate set to 100 Mbps
4 ON X1 port is set to half duplex
OFF X1 port is set to full duplex
5 ON In the event of a fault on the X1 port, the
alarm LED lights and the alarm relay is closed, generating a remote alarm OFF Faults are not monitored on the X1 port
6 ON In the event of a fault on the X2 port, the
alarm LED lights and the alarm relay is closed, generating a remote alarm OFF Faults are not monitored on the X2 port
7 ON Pass-through (The X1 port rate is fixed at
100 Mbps and the settings from DIP
switches 2, 3, and 4 are ignored) OFF Enables store and forward mode