700-SK ALLEN-BRADLEY

Document overview

  • PDF pages: 5

Technical content

Page 1

Overview/Product Selection

PDF page 1 diagram

Product Selection

Input/Sensor Module

Input-to-Output Isolation Method LED Indicator Response Speed Logic Level Rated Input Sensor Voltage Cat. No. Factory-stocked item (Single Pack)
Supply Voltage Supply Current
Photocoupler Yes 10 Hz 4…32V DC 0.1…100 mA 100…240V AC 700-SKICA18 ✔
High-speed (1 kHz) 12…24V DC 700-SKICZ24 ✔

Output/SSR Module

Input-to-Output Isolation Method Zero Cross Function LED Indicator Rated Output (Load) Max. Current and Voltage Range Rated Input Control Voltage Cat. No. Factory-stocked item (Single Pack)
Phototriac Yes Yes 2 A at 100…240V AC 5…24V DC 700-SKOZ2Z25 ✔
No 700-SKON2Z25 ✔
Photocoupler N/A 2 A at 5…48V DC 700-SKOC2Z25 ✔
1.5 A at 48…200V DC 700-SKOC1Z25 ✔

Page 2

Accessories

Description Pcs./Pkg. Cat. No. Factory-stocked Item
Cat No. 700-HN121 Screw Terminal Socket — Panel or DIN Rail Mounting Order must be in multiples of ten 10 700-HN121 ✔
Cat No. 199-DR1 DIN Rail Mounting Pack Standard 35 x 7.5 mm DIN Rail, 1 meter long, 10 rails per package. Order must be for 10 rails or multiples of 10. 10 199-DR1 ✔
Pre-printed identification tags — contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays. 10 700-N40
Blank identification tags — contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays. 10 700-N41

Page 3

Specifications

Input Sensor Module

Input Sensor Ratings

Cat, No. Rated Input Voltage Operating Voltage Range Input Current Pick-up Voltage Drop-out Voltage
700-SKICZ24 12…24V DC 6.6…32V DC 8 mA max. 6.6V DC max. 3.6V DC min.
700-SKICA18 100…240V AC 60…264V AC 15 mA max. 60V AC max. 20V AC min.

Output Logic Ratings

Cat. No. Logic Level Supply Voltage Logic Level Supply Current Draw
700-SKICZ24 700-SKICA18 4…32V DC 0.1…100 mA

Characteristics

Cat. No. 700-SKICA18 700-SKICZ24
Pick-up time 20 ms max. 0.1 ms max.
Drop-out time 20 ms max. 0.1 ms max.
Response frequency 10 Hz 1 kHz
Output ON voltage drop 1.6 V max.
Leakage current 5 µA max.
VDRM VCEO (V) 80 (ref. value) 80 (ref. value)
Output di/dt (A/uS) — —
Output dv/dt (V/uS) — —
Output I2t (A2S) — —
Output Tj (°C) Max. 150 150
Insulation resistance 100 MΩ min. between input and output
Dielectric strength 4,000V AC, 50/60 Hz for 1 min. between input and output
Vibration resistance (max.) 10…55 Hz, 1.5 mm double amplitude (10 G)
Shock resistance (max.) 1,000 m/s2 (100 G)
Operating Ambient temperature Storage –30…80°C (–22…176°F) with no icing or condensation –30…100°C (–22…212°F) with no icing or condensation
Standards UL 508 CSA C22.2 CE, TÜV
Ambient humidity Operating 45…85% (No condensation)
Weight Approx. 18 g

Output SSR Module

Control/Input Ratings

Cat. No. Rated Control Voltage Operating Control Voltage Range Impedance➊ Pick-up Voltage Drop-out Voltage
700-SKOZ2Z25 5…24V DC 4…32V DC 15 mA max. at 25°C (77°F) 4V DC max. 1V DC min.
700-SKON2Z25
700-SKOC2Z25 8 mA max.
700-SKOC1Z25

Load/Output Ratings

Cat. No. Rated Load Voltage Load Voltage Range Continuous Load Current (Resistive) Max. Inrush Current➋
— — — Min. Max.➌ —
700-SKOZ2Z25 100…240V AC 75…264V AC 0.05 A 2 A 30 A (@50/60 Hz, 1 cycle)
700-SKON2Z25
700-SKOC2Z25 5…48V DC 4…60V DC 0.01 A 2 A 8 A (10 ms)
700-SKOC1Z25 48…200V DC 40…200V DC 0.01 A 1.5 A 8 A (10 ms)

➊ With a constant current input system. SSR impedance varies with a change in input voltage. ➋ If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to the “Inrush Current Resistivity” graphs on page 61 for more details. ➌ Refer to "Load Current Versus Ambient Temperature Characteristics" graphs on page 61 for additional details.

Page 4

Specifications, Continued

Output Module, Continued

Characteristics

Cat. No. 700-SKOZ2Z25 700-SKON2Z25 700-SKOC2Z25 700-SKOC1Z25
Load Switching Method/Device Triac Transistor
Pick-up time 1/2 of load power source cycle + 1 ms max. 1 ms max.
Drop-out time 1/2 of load power source cycle + 1 ms max. 2 ms max.
Response frequency 20 Hz 100 kHz
Output ON voltage drop 1.6 V max. 2.5V max.
Leakage current 1.5 mA max. 1 mA max.
VDRM VCEO (V) 600 (ref.value) 600 (ref.value) 80 (ref.value) 400 (ref.value)
Output di/dt (A/uS) 30 30 — —
Output dv/dt (V/uS) 300 300 — —
Output I2t (A2S) 10.4 10.4 — —
Output Tj (°C) Max. 125 125 150 150
Insulation resistance 100 MΩ min. between input and output
Dielectric strength 4,000V AC, 50/60 Hz for 1 min. between input and output
Vibration resistance (max.) 10…55 Hz, 1.5 mm double amplitude (10 G)
Shock resistance (max.) 1,000 m/s2 (100 G)
Operating Ambient temperature Storage –30…80°C (–22…176°F) with no icing or condensation –30…100°C (–22…212°F) with no icing or condensation
Standards UL 508 CSA C22.2, CE TÜV
Ambient humidity Operating 45…85% (no condensation)
Weight Approx. 18 g

Load Current vs. Ambient Temperature Characteristics

For 2 A Versions

PDF page 4 diagram
PDF page 4 diagram
PDF page 4 diagram

Inrush Current Resistivity➊

➊ Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.

Page 5

Approximate Dimensions

All units are in millimeters unless otherwise indicated. Dimensions are not to be used for manufacturing purposes. Note: The input module (700-SKI) and output module (700-SKO) are compatible with the 700-HN121 socket.

PDF page 5 diagram

Application Considerations of Bulletin 700-SK

Connection For DC load switching, Bulletin 700-SK SSR will operate properly if the load is connected to either the positive or negative SSR load terminal. The load can be connected to either positive or negative output terminals of the SSR.

Protective Element (to extend SSR life) Since the SSR does not incorporate a surge absorption component, be sure to connect a surge absorption component when using the SSR to control an inductive load. For additional details applying solid-state relays, refer to pub. number 700-AT001A-EN-E, "Solid-State Relay Application Guide." Document available at www.theautomationbookstore.com.