1461304 PHOENIX
Document overview
- Manufacturer or author: Provided By digicamel.com
- PDF pages: 9
Technical content
Please be informed that the data shown in this PDF document is generated from our Online Catalog. Please find the complete data in the user documentation. Our General Terms of Use for Downloads are valid. High-performance, spark gap-based non-pluggable lightning current arrester / surge protective device for 3-phase power supply networks with separate N and PE (5-conductor system: L1, L2, L3, N, PE), for lightning protection levels I and II, with remote signaling. Your advantages Maximum performance in the smallest installation space• Safe system operation due to reliable protection in the event of lighting currents and surge voltages Superior system availability due to innovative, powerful spark gap technology Space-saving and inexpensive installation, thanks to the slim design Information concerning the status of protection is always available by means of visual, mechanical status indicator and optional remote indication contact Commercial Data Item number 1461304 Packing unit 1 pc Minimum order quantity 1 pc Product Key CL11D2 GTIN 4063151851767 Weight per Piece (including packing) 603 g Weight per Piece (excluding packing) 565 g Country of origin CN Type 1+2+3 combined lightning current and surge arresters - FLT-MB-T1-264/25-3+1-UT-R 1461304 https://www.phoenixcontact.com/us/products/1461304 Nov 16, 2022, 5:25 AM Page 1 (9)
T1 + T2 + T3IEC test classification I + II + III EN type T1 + T2 + T3 Type DIN rail module, one-piece Product type Combination type Surge protection fault message Optical, remote indicator contact Insulation characteristics IV (between the main and auxiliary circuit)Overvoltage category II (Auxiliary circuit) Pollution degree 2 Electrical properties Nominal frequency fN 50 Hz (60 Hz) Indicator/remote signaling Connection name Remote fault indicator contact Switching function Changeover contact 12 V AC ... 250 V ACOperating voltage
125 V DC (200 mA DC)
10 mA AC ... 0.5 A ACOperating current
0.5 A DC (30 V DC)
Connection method Screw connection Screw thread M5 3 Nm (2,5 mm² ... 16 mm²)Tightening torque 4.5 Nm (25 mm² ... 35 mm²) Stripping length 18 mm Conductor cross section flexible 2.5 mm² ... 25 mm² Conductor cross section solid 2.5 mm² ... 35 mm² Conductor cross section AWG 13 ... 2 Connection method Fork-type cable lug Conductor cross section flexible 2.5 mm² ... 25 mm² Remote fault indicator contact Connection method Plug-in/screw connection via COMBICON Screw thread M2 Type 1+2+3 combined lightning current and surge arresters - FLT-MB-T1-264/25-3+1-UT-R 1461304 https://www.phoenixcontact.com/us/products/1461304 Nov 16, 2022, 5:25 AM Page 2 (9)
Conductor cross section AWG 24 ... 12 Dimensions Dimensional drawing Width 72 mm Height 99.7 mm Depth 76.6 mm (incl. DIN rail 7.5 mm) Horizontal pitch 4 Div. Material specifications Color light grey RAL 7035 Flammability rating according to UL 94 V-0 CTI value of material 600 Insulating material PBT Material group I Housing material PBT Mechanical properties Mechanical data Open side panel No Protective circuit L-N L-PE Mode of protection N-PE 240/415 V AC (TN-S)Nominal voltage UN 240/415 V AC (TT) Nominal frequency fN 50 Hz (60 Hz) Maximum continuous voltage UC 264 V AC Rated load current IL 80 A (< 55 °C) Residual current IPE ≤ 0.01 mA Nominal discharge current In (8/20) µs (L-N) 25 kA Nominal discharge current In (8/20) µs (L-PE) 25 kA Nominal discharge current In (8/20) µs (N-PE) 100 kA Combination wave UOC 6 kV Impulse discharge current (10/350) µs (L-N), charge 12.5 As Impulse discharge current (10/350) µs (L-N), specific energy 156 kJ/Ω Type 1+2+3 combined lightning current and surge arresters - FLT-MB-T1-264/25-3+1-UT-R 1461304 https://www.phoenixcontact.com/us/products/1461304 Nov 16, 2022, 5:25 AM Page 3 (9)
Impulse discharge current (10/350) µs (L-N), peak current value Iimp 25 kA Impulse discharge current (10/350) µs (L-PE), charge 12.5 As Impulse discharge current (10/350) µs (L-PE), specific energy 156 kJ/Ω Impulse discharge current (10/350) µs (L-PE), peak current value Iimp 25 kA Impulse discharge current (10/350) µs (N-PE), charge 50 As Impulse discharge current (10/350) µs (N-PE), specific energy 2500 kJ/Ω Impulse discharge current (10/350) µs (N-PE), peak current value Iimp 100 kA Total discharge current Itotal (10/350) µs 100 kA Follow current quenching capacity Ifi (L-N) 25 kA Follow current interrupt rating Ifi (N-PE) 100 A Short-circuit current rating ISCCR 25 kA Voltage protection level Up (L-N) ≤ 1.5 kV Voltage protection level Up (L-PE) ≤ 2.5 kV Voltage protection level Up (N-PE) ≤ 1.5 kV ≤ 1.5 kV (at In) ≤ 1.3 kV (at 12.5 kA) ≤ 1.1 kV (at 5 kA) Residual voltage Ures (L-N) ≤ 1 kV (at 2.5 kA) ≤ 1.7 kV (at In) ≤ 1.5 kV (at 12.5 kA) ≤ 1.3 kV (at 5 kA) Residual voltage Ures (L-PE) ≤ 1.2 kV (at 2.5 kA) ≤ 1.5 kV (at In) ≤ 1.3 kV (at 50 kA) ≤ 1.1 kV (at 20 kA) Residual voltage Ures (N-PE) ≤ 1 kV (at 10 kA)
457 V AC (5 s / withstand mode)TOV behavior at UT (L-N)
457 V AC (120 min / withstand mode)
TOV behavior at UT (N-PE) 1200 V AC (200 ms / withstand mode) Response time tA ≤ 100 ns Max. backup fuse with V-type through wiring 80 A (gG) Max. backup fuse with branch wiring 315 A (gG) Environmental and real-life conditions Ambient conditions Degree of protection IP20 (Installed) Ambient temperature (operation) -40 °C ... 85 °C Ambient temperature (storage/transport) -40 °C ... 85 °C ≤ 2000 m (operating voltage remote contact ≤ 250 V)Altitude ≤ 5000 m (operating voltage remote contact ≤ 150 V) Type 1+2+3 combined lightning current and surge arresters - FLT-MB-T1-264/25-3+1-UT-R 1461304 https://www.phoenixcontact.com/us/products/1461304 Nov 16, 2022, 5:25 AM Page 4 (9)
Permissible humidity (operation) 5 % ... 95 % Shock (operation) 2g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) Vibration (operation) 0,5g (9 … 200 Hz / 2.5 h / X, Y, Z) Standards and regulations Standards/specifications IEC 61643-11 Standards/specifications EN 61643-11 Mounting Mounting type DIN rail: 35 mm Type 1+2+3 combined lightning current and surge arresters - FLT-MB-T1-264/25-3+1-UT-R 1461304 https://www.phoenixcontact.com/us/products/1461304 Nov 16, 2022, 5:25 AM Page 5 (9)
99,7 69,1 76,6 7289,8 Circuit diagram PE N L2L1 L3 12 14 11 FM Type 1+2+3 combined lightning current and surge arresters - FLT-MB-T1-264/25-3+1-UT-R 1461304 https://www.phoenixcontact.com/us/products/1461304 Nov 16, 2022, 5:25 AM Page 6 (9)
IECEE CB Scheme Approval ID: NL-84247 CCA Approval ID: NTR-NL 7959 Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2 - - KEMA-KEUR Approval ID: 71-125930 Type 1+2+3 combined lightning current and surge arresters - FLT-MB-T1-264/25-3+1-UT-R 1461304 https://www.phoenixcontact.com/us/products/1461304 Nov 16, 2022, 5:25 AM Page 7 (9)
ECLASS-9.0 27130805 ECLASS-10.0.1 27130805 ECLASS-11.0 27130805 ECLASS-12.0 27171202 Type 1+2+3 combined lightning current and surge arresters - FLT-MB-T1-264/25-3+1-UT-R 1461304 https://www.phoenixcontact.com/us/products/1461304 Nov 16, 2022, 5:25 AM Page 8 (9)
Marker pen - B-STIFT - 1051993 https://www.phoenixcontact.com/us/products/1051993 Marker pen, for manual labeling of unprinted Zack strips, smear-proof and waterproof, line thickness 0.5 mm Marker strip Marker strip - TML (EX6)RL - 1026829 https://www.phoenixcontact.com/us/products/1026829 Marker strip, Roll, white, unlabeled, can be labeled with: THERMOMARK E.300 (D)/600 (D), THERMOMARK ROLL 2.0, THERMOMARK ROLL, THERMOMARK ROLL X1, THERMOMARK ROLLMASTER 300/600, THERMOMARK X1.2, mounting type: adhesive, for terminal block width: 150000 mm, lettering field size: 150000 x 6 mm, Number of individual labels: 1 Phoenix Contact 2022 © - all rights reserved https://www.phoenixcontact.com Phoenix Contact USA