1159038 PHOENIX

Document overview

  • Manufacturer or author: Provided By digicamel.com
  • PDF pages: 19

Technical content

Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user documentation. Our general terms of use for downloads are valid. Primary-switched power supply unit, TRIO POWER, Push-in connection, DIN rail mounting, input: 1-phase, output: 24 V DC / 10 A, adjustable from 24 V DC ... 28 V DC Product description All TRIO POWER power supplies feature smart diagnostics with multicolor LEDs and a collective alarm contact. This is used to signal all relevant states such as DC OK, overload, and short circuit. Devices with integrated multi-channel device protection and an IO-Link interface for diagnostics and parameterization are optionally available. The compact devices reduce the installation work, space requirements in the control cabinet, and material costs. TRIO POWER power supplies therefore provide power reliability in one device. Your advantages Space-saving due to its low overall width and capability of being mounted side by side• Robust and reliable due to dynamic boost with a powerful output characteristic curve Easy handling with Push-in connection technology Smart diagnostics with multicolor LEDs and collective relay contact for a clear status display, with optional IO-Link High system availability: power reliability in one device due to the integrated compact multi-channel circuit breaker Commercial data Item number 1159038 Packing unit 1 pc Minimum order quantity 1 pc Sales key CM29 Product key CMPD13 GTIN 4063151165925 Weight per piece (including packing) 780 g Weight per piece (excluding packing) 711 g Customs tariff number 85044095 Country of origin CN TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 1 (19)

Supply system configuration Star network (TN, TT, IT (PE)) Nominal input voltage range 100 V AC ... 240 V AC 115 V AC ... 240 V AC ±10 % (UL) < 100 V AC (1 %/V)Derating 2.5 %/K, > 60 °C

120 V ACTypical national grid voltage

230 V AC

Voltage type of supply voltage AC Inrush current < 17 A (25 °C) Inrush current integral (I2t) < 0.5 A2s Frequency range (fN) 50 Hz ... 60 Hz ±10 % typ. 27 ms (120 V AC)Mains buffering time typ. 28 ms (230 V AC)

2.6 A (100 V AC)

2.2 A (120 V AC)

1.2 A (230 V AC)

1.1 A (240 V AC)

Protective circuit Transient protection; Varistor Power factor (cos phi) 0.95 (230 V AC) Device mains fuse 6.3 A internal (device protection) Recommended breaker for input protection 6 A ... 16 A (Characteristic B, C, D, K or comparable) Discharge current to PE < 3.5 mA DC operation 100 V DC ... 240 V DC ±10 %Input voltage range 160 V DC ... 240 V DC ±10 % (UL) Derating < 140 V DC (1 %/V)

2.7 A (100 V DC)Current consumption

1.1 A (240 V DC)

typ. 94.5 % (120 V AC)Efficiency typ. 95.5 % (230 V AC) Nominal output voltage 24 V DC Setting range of the output voltage (USet) 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) Nominal output current (IN) 10 A Dynamic Boost (IDyn.Boost) max. 15 A (5 s) Short-circuit-proof yes TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 2 (19)

Derating 60 °C ... 70 °C typ. 1.75 (120 V AC)Crest factor typ. 1,7 (230 V AC) Output power (PN) 240 W Output power (PDyn. Boost) max. 360 W (5 s) Connection in parallel yes, for increased efficiency and redundancy Connection in series yes, for increased output voltage (observe SELV limit) Feedback voltage resistance ≤ 35 V DC Protection against overvoltage at the output (OVP) ≤ 35 V DC Residual ripple typ. 50 mVPP (with nominal values) < 1 % (change in load, static 10 % ... 90 %) < 3 % (change in load, dynamic 10 % ... 90 %) Control deviation < 0.1 % (change in input voltage ±10 %) Rise time ≤ 1 s (UOut = 10 % ... 90 %) Minimum no-load power dissipation < 1.2 W (120 V AC) Maximum no-load power dissipation < 1.3 W (230 V AC) Minimum nominal load power dissipation < 14.5 W (120 V AC) Power loss nominal load max. < 12 W (230 V AC) Integrated fuse protection no Connection data Input Position 1.x Connection technology Position marking 1.1 (L/+), 1.2 (N/-), 1.3 () Conductor connection Connection method Push-in connection 0.2 mm² ... 4 mm²rigid 1.5 mm² (recommended) 1.5 mm² (recommended) 1.5 mm² (recommended) 1.5 mm² (recommended) 24 ... 12 (Cu)AWG 16 (recommended) Stripping length 10 mm (Rigid/flexible/ferrule) Output Position 2.x TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 3 (19)

Connection method Push-in connection 0.2 mm² ... 4 mm²rigid 1.5 mm² (recommended) 1.5 mm² (recommended) 1.5 mm² (recommended) 1.5 mm² (recommended) 24 ... 12 (Cu)AWG 16 (recommended) Stripping length 10 mm (Rigid/flexible/ferrule) Signal Position 3.x Connection technology Position marking 3.1 (13), 3.2 (14) Conductor connection Connection method Push-in connection 0.5 mm² (recommended) 0.5 mm² (recommended) 0.5 mm² (recommended) 0.5 mm² (recommended) 24 ... 16 (Cu)AWG 20 (recommended) Stripping length 10 mm (Rigid/flexible/ferrule) Signaling LED signaling Types of signaling LED DC OK – signal state operation (UN = 24 V DC, IOut = IN) Function Visual operating state display Color red, yellow, green (multicolor LED) LED off Supply voltage input AC not present (Off) LED on (green), DC OK UOut > 21 V DC and IOut < 0.9 x IN (On (green), DC OK) LED on (yellow), IOut > 90% UOut > 21 V DC and IOut > 0.9 x IN (On (yellow), IOut > 90% ) TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 4 (19)

LED on (red), ISHORT UOut < 21 V DC and IOut > 0.9 x IN (On (red), ISHORT) LED on (flashing red) OVP UOUT > OVP (Over voltage protection) (On (flashing red)) Signal output DC OK Position 3.x Type of signaling DC OK switch contact - signal state operation (UN = 24 V DC, IOut = IN) Position marking 3.1 (13), 3.2 (14) Function Operating state forwarding Switch contact (floating) OptoMOS Switching voltage max. 30 V DC (SELV) Current carrying capacity max. 100 mA UOut > 21 V DC and IOut < 0.9 x IN (Contact closed)State condition UOut < 21 V DC or IOut > 0.9 x IN (averaging over 60 s) (Contact open) Electrical properties Number of phases 1.00 3 kV AC (type test)Insulation voltage input/output 3.1 kV DC (routine test) Product properties Product type Power supply Product family TRIO POWER > 2300000 h (25 °C) > 1300000 h (40 °C) MTBF (IEC 61709, SN 29500) > 610000 h (60 °C) RoHS Directive 2011/65/EU WEEE Environmental protection directive Reach Insulation characteristics Protection class I Degree of pollution 2 Dimensions Item dimensions Width 40 mm Height 135 mm 132 mmDepth 125 mm (Device depth (DIN rail mounting)) Installation dimensions Installation distance right/left 0 mm / 0 mm Installation distance top/bottom 50 mm / 50 mm TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 5 (19)

Mounting type DIN rail mounting Assembly note alignable: 0 mm horizontally, 30 mm vertically Mounting position horizontal DIN rail NS 35, EN 60715 With protective coating no Material specifications Flammability rating according to UL 94 V0 (Housing, terminal blocks) Hood version Polycarbonate Side element version Aluminum Environmental and real-life conditions Ambient conditions Degree of protection IP20 Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) Ambient temperature (storage/transport) -40 °C ... 85 °C Ambient temperature (start-up type tested) -40 °C Maximum altitude ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing) Shock (operation) 18 ms, 30g, per spatial direction (IEC 60068-2-27) 10 Hz ... 50 Hz, amplitude ±0.2 mm (IEC 60068-2-6)Vibration (operation) Temp code T4 (-25 ... +70 °C; > 60 °C, Derating: 2,5 %/K) Standards and regulations Overvoltage category III (≤ 2000 m)EN 61010-1 II (≤ 5000 m) Overvoltage category III (≤ 2000 m)EN 61010-2-201 II (≤ 5000 m) Safety of power supply units up to 1100 V (insulation distances) Standard designation Safety of power supply units up to 1100 V (insulation distances) Standards/specifications DIN EN 61558-2-16 Electrical safety Standard designation Electrical safety Standards/specifications IEC 61010-2-201 (SELV) Safety for measurement, control, and laboratory equipment Standard designation Safety for equipment for measurement, control, and laboratory use Standards/specifications IEC 61010-1 TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 6 (19)

Protective extra-low voltage Standard designation Protective extra-low voltage IEC 61010-1 (SELV)Standards/specifications IEC 61010-2-201 (PELV) Safe isolation Standard designation Safe isolation IEC 61558-2-16Standards/specifications IEC 61010-2-201 Limitation of harmonic line currents Standard designation Limitation of harmonic line currents Standards/specifications EN 61000-3-2 Mains variation/undervoltage Standard designation Mains variation/undervoltage SEMI F47Standards/specifications EN 61000-4-11 Approvals UL Identification UL/C-UL Listed UL 61010-1 UL Identification UL/C-UL Listed UL 61010-2-201 ANSI/UL 121201 PROCESS CONTROL EQUIPEMENT FOR HAZARDOUS LOCATIONS (EN)  This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, Hazardous Locations, or non-hazardous locations only. (FR)  Cet appareil convient uniquement pour une utilisation en atmosphères explosibles de classe I, division 2, groupes A, B, C et D ou en atmosphères non explosibles. (EN)  WARNING: Explosion Hazard - Do not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous. (FR)  AVERTISSEMENT : risque d'explosion - ne pas connecter ou déconnecter les équipements sauf si l'alimentation a été coupée ou si la zone est réputée non dangereuse. (EN)  If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. (FR)  Si l'équipement est utilisé d'une manière non spécifiée par le fabricant, la protection fournie par cet équipement peut être altérée. Identification TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 7 (19)

(EN)  This equipement must be installed in a suitable, tool secured/key locked enclosure. (FR)  Cet équipement doit être installé dans un boîtier approprié, verrouillé par une clé ou dont l'ouverture nécessite l'utilisation d'un outil. EMC data Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC Interference emission Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) Noise immunity Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial) EN 55016Conducted noise emission EN 61000-6-3 (Class B) EN 55016Noise emission EN 61000-6-3 (Class B) Harmonic currents EN 61000-3-2Standards/regulations EN 61000-3-2 (Class A) Frequency range 0 kHz ... 2 kHz Flicker EN 61000-3-3Standards/regulations EN 61000-3-3 Frequency range 0 kHz ... 2 kHz Electrostatic discharge Standards/regulations EN 61000-4-2 Electrostatic discharge Contact discharge 6 kV (Test Level 3) Discharge in air 8 kV (Test Level 3) Comments Criterion B Electromagnetic HF field Standards/regulations EN 61000-4-3 Electromagnetic HF field Frequency range 80 MHz ... 1 GHz Test field strength 10 V/m (Test Level 3) Frequency range 1 GHz ... 6 GHz Test field strength 10 V/m (Test Level 3) Comments Criterion A Fast transients (burst) Standards/regulations EN 61000-4-4 TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 8 (19)

Fast transients (burst) Input asymmetrical 2 kV (Test Level 3) Output asymmetrical 2 kV (Test Level 3) Signal asymmetrical 1 kV (Test Level 3) Comments Criterion A Surge voltage load (surge) Standards/regulations EN 61000-4-5 Surge voltage load (surge) symmetrical 1 kV (Test Level 3)Input asymmetrical 2 kV (Test Level 3) symmetrical 0.5 kV (Test Level 2)Output asymmetrical 1 kV (Test Level 2) Signal asymmetrical 1 kV (Test Level 2) Comments Criterion B Conducted interference Standards/regulations EN 61000-4-6 Conducted interference I/O/S asymmetrical Frequency range 0.15 MHz ... 80 MHz Comments Criterion A Voltage 10 V (Test Level 3) Voltage dips Standards/regulations EN 61000-4-11 Voltage 230 V AC Frequency 50 Hz Voltage dip 70 % Number of periods 25 periods Additional text Class 3 Comments Criterion A Voltage dip 40 % Number of periods 10 periods Additional text Class 3 Comments Criterion A Voltage dip 0 % Number of periods 1 period Additional text Class 3 Comments Criterion A Criteria Criterion A Normal operating behavior within the specified limits. Temporary impairment to operational behavior that is corrected Criterion B TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 9 (19)

by the device itself. Criterion C Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 10 (19)

0,5 0,0 0 5 6 7 8 9 10 1,0 1,5 2,0 2,5 3,0 IOut [A] = UIn: 120 V AC/UOut: 24 V DC = UIn: 230 V AC/UOut: 24 V DC IIn [A] 4321 Input current/output current Diagram 1 % 60 70 Dynamic Boost P P N Dyn -25 [°C] 100% 125% 75% t≥5 s Temperature-dependent derating TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 11 (19)

P P N Dyn H m[ ] 100% 1 %50 120% 70% 50004000300020001000 = PN 100% 60°C = P 150% 60°CDyn Altitude-dependent derating TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 12 (19)

63,5 Device dimensions (dimensions in mm) Diagram 0,4 0,3 0 10 0,5 0,6 0,7 0,8 0,9 1,0 IOut [A] = UIn: 120 V AC/UOut: 24 V DC = UIn: 230 V AC/UOut: 24 V DC Power Factor 8642 Power factor TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 13 (19)

Device dimensions (dimensions in mm) TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 14 (19)

B A C D F E Housing Test sections, insulation voltage TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 15 (19)

IOut [A] = UIn: 120 V AC/UOut: 24 V DC = UIn: 230 V AC/UOut: 24 V DC Eta [%] 4321 Efficiency Block diagram 1.3 1.2 1.1L/+ N/− +2.1 2.2 2.3 2.4 Input AC Output DC UVP OVP OTP OCP SCP Functions User Interface Signal Filteractive PFCFilter DC OKUOut IOut>90% SHORT 2.5 3.1 13 143.2 Block diagram TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 16 (19)

To download certificates, visit the product detail page: https://www.phoenixcontact.com/us/products/1159038  cULus Listed Approval ID: E123528-20220128 DNV Approval ID: TAA00000BM  cULus Listed Approval ID: E199827-20220207 TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 17 (19)

ECLASS-11.0 27040701 ECLASS-12.0 27040701 ECLASS-13.0 27040701 ETIM ETIM 9.0 EC002540 TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 18 (19)

Environmental product compliance EU RoHS Fulfills EU RoHS substance requirements Yes Exemption 7(a), 7(c)-I China RoHS EFUP-25Environment friendly use period (EFUP) An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. EU REACH SVHC REACH candidate substance (CAS No.) Lead(CAS: 7439-92-1) SCIP e286cf8b-568e-4d85-a492-2a06c9541686 EF3.0 Climate Change CO2e kg 20.95 kg CO2e Phoenix Contact 2024 © - all rights reserved https://www.phoenixcontact.com Phoenix Contact USA

586 Fulling Mill Road

Middletown, PA 17057, United States (+717) 944-1300 info@phoenixcon.com TRIO3-PS/1AC/24DC/10 - Power supply unit 1159038 https://www.phoenixcontact.com/us/products/1159038 Dec 20, 2024, 5:16 AM Page 19 (19)