Features
– Wide-range voltage input – Galvanic isolation – Reverse polarity protection – Preventive function monitoring – Reliable starting of difficult loads with POWER BOOST static power reserve – Fast tripping of standard ci rcuit breakers with dynamic SFB technology power reserve – High MTBF > 772,000 h (40°C) Flexible use – Dip coating enables use in oxidizing and sulfidizing atmospheres with humidities of up to 100 % – Adjustable output voltage – Can be used in Class I, Division 2, Groups A, B, C, D (Hazardous Location) ANSI-ISA 12.12 Make sure you always use the latest documentation. It can be downloaded from the product at phoenixcontact.net/products. 106467_en_00 2015-11-24
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 2 2T a b l e o f c o n t e n t s
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 3 Description Type Order No. Pcs./Pkt. Primary-switched QUINT DC/DC converter with wide range input for DIN rail mounting with SFB (selective fuse breaking) technology, input: 96 -
110 V DC, output: 24 V DC/10 A
QUINT-PS/96-110DC/24DC/10/CO 2905012 1 3O r d e r i n g d a t a Accessories Type Order No. Pcs./Pkt. Active QUINT redundancy module for DIN rail mounting with ACB technol- ogy (Active Current Balancing) and monitoring functions, input: 24 V DC, output: 24 V DC/2 x 10 A or 1 x 20 A, including mounted universal DIN rail adapter UTA 107/30 QUINT-ORING/24DC/2X10/1X20 2320173 1 Universal DIN rail adapter UTA 107/30 2320089 100 Universal wall adapter UWA 182/52 2938235 1 Assembly adapter for QUINT-PS... power supply on S7-300 rail QUINT-PS-ADAPTERS7/1 2938196 1 Thermomagnetic device circuit breaker, 1-pos., tripping characteristic SFB, 1 PDT contact, plug for base element. CB TM1 1A SFB P 2800836 1 Thermomagnetic device circuit breaker, 1-pos., tripping characteristic SFB, 1 PDT contact, plug for base element. CB TM1 2A SFB P 2800837 1 Thermomagnetic device circuit breaker, 1-pos., tripping characteristic SFB, 1 PDT contact, plug for base element. CB TM1 3A SFB P 2800838 1 Thermomagnetic device circuit breaker, 1-pos., tripping characteristic SFB, 1 PDT contact, plug for base element. CB TM1 4A SFB P 2800839 1 Thermomagnetic device circuit breaker, 1-pos., tripping characteristic SFB, 1 PDT contact, plug for base element. CB TM1 5A SFB P 2800840 1 Thermomagnetic device circuit breaker, 1-pos., tripping characteristic SFB, 1 PDT contact, plug for base element. CB TM1 12A SFB P 2800844 1 Thermomagnetic device circuit breaker, 1-pos., tripping characteristic SFB, 1 PDT contact, plug for base element. CB TM1 16A SFB P 2800845 1 Our range of accessories is being continually extended, our current range can be found in the download area.
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 4
4 Technical data
Nominal input voltage 96 V DC ... 110 V DC Input voltage range 67.2 V DC ... 154 V DC Current consumption 3.5 A (96 V DC)
3.1 A (110 V DC)
Inrush current limitation < 10 A (typical) I2t 0.37 A2s Power failure bypass > 10 ms (96 V DC) Protective circuit Transient surge protection Varistor Protection against polarity reversal ≤ 154 V DC Input fuse, integrated 10 A (internal (device protection)) Output data Nominal output voltage 24 V DC ±1 % Setting range of the output voltage 18 V DC ... 29.5 V DC (> 24 V constant capacity) Output current 10 A (-40 °C ... 60 °C) 12.5 A (with POWER BOOST, -40°C ... 40°C permanent, UOUT = 24 V DC)
60 A (SFB technology, 12 ms)
Magnetic circuit breaker tripping B2 / B4 / B6 Active current limitation 18 A Max. capacitive load Unlimited Control deviation < 1 % (change in load, static 10 % ... 90 %) < 2 % (change in load, dynamic 10 % ... 90 %) < 0.1 % (change in input voltage ±10 %) Efficiency > 92 % (UIN 96 V DC / UOUT 24 V DC) Rise time < 2 ms (U OUT (10 % ... 90 %)) Residual ripple < 20 mVPP Peak switching voltages < 10 mV PP (20 MHz) Connection in parallel Yes, for redundancy and increased capacity Connection in series Yes Protection against surge voltage on the output < 35 V DC Resistance to reverse feed 35 V DC Power consumption Maximum power dissipation in no-load condition 4 W (U IN 110 V DC) Power loss nominal load max. 22 W (UIN 110 V DC) Status and diagnostic indicator DC OK active Active switching output U OUT > 0.9 x UN: High signal Voltage 18 V DC ... 24 V DC Current < 20 mA (short-circuit resistant) Status display "DC OK" LED green Status and diagnostic indicator POWER BOOST, active Active switching output I OUT < IN: High signal Voltage 18 V DC ... 24 V DC Current < 20 mA (short-circuit resistant) Status display "BOOST" LED yellow/IOUT > IN : LED on
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 5 Status and diagnostic indicator UIN OK, active Active switching output U IN > 19.2 V: High signal Voltage 18 V DC ... 24 V DC Current ≤ 20 mA (short-circuit resistant) Status and diagnostic indicator DC OK floating Active switching output Relay General data Insulation voltage input/output 1.5 kV (type test) 1 kV (routine test) MTBF (IEC 61709, SN 29500) > 772000 h (40°C) Normal mounting position horizo ntal DIN rail NS 35, EN 60715 Dimensions W/H/D (normal mounting position/delivered condition) 48 mm / 130 mm / 125 mm Dimensions W / H / D (X-axis rotated 270°) 122 mm / 130 mm / 51 mm Weight 0.9 kg Housing Degree of protection IP20 Type of housing Aluminum (AlMg3) Hood version Galvanized sheet st eel, free from chrome (VI) Input connection data Connection method Plu ggable screw connection Conductor cross section AWG/kcmil 24 ... 12 Stripping length 8 mm Screw thread M3 Connection data, output/signals Connection method Plu ggable screw connection Conductor cross section AWG/kcmil 24 ... 12 Stripping length 7 mm Screw thread M3 Ambient conditions Protection class I Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) Ambient temperature (start-up type tested) -40 °C Ambient temperature (storage/transport) -40 °C ... 85 °C Max. permissible relative humidity (operation) 100 % (at 25 °C, non-condensing) Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) Shock 30g in each direction, according to IEC 60068-2-27 Pollution degree in acc. with EN 50178 2 Climatic class 3K3 (in acc. with EN 60721)
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 6 Approvals UL approvals UL/C-UL listed UL 508 UL/C-UL Recognized UL 60950 Current approvals/permissions for the product can be found in the download area under phoenixcontact.net/products.
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 7 Conformance with EMC Directive 2004/108/EC Noise immunity according to EN 61000-6-2 EN 61000-6-2 requirement Tested Electrostatic discharge EN 61000-4-2 Housing contact discharge 4 kV (Test Level 2) 8 kV (Test Level 4) Housing air discharge 8 kV (Test Level 3) 15 kV (Test Level 4) Comments Criterion B Criterion A Electromagnetic HF field EN 61000-4-3 Test field strength 10 V/m (Test Level 3) 20 V/m (Test Level 3) Test field strength 3 V/m (Test Level 2) 20 V/m (Test Level 3) Test field strength 1 V/m (Test Level 1) 10 V/m (Test Level 3) Comments Criterion A Criterion A Fast transients (burst) EN 61000-4-4 Input 2 kV (Test Level 3 - asymmetrical) 4 kV (Test Level 4 - asymmetrical) Output 2 kV (Test Level 3 - asymmetrical) 2 kV (Test Level 3 - asymmetrical) Signal 1 kV (Test Level 3 - asymmetrical) 2 kV (Test Level 4 - asymmetrical) Comments Criterion B Criterion A Surge current loads (surge) EN 61000-4-5 Input 0.5 kV (Test Level 1 - symmetrical) 0.5 kV (Test Level 1 - asymmetrical) 2 kV (Test Level 4 - symmetrical) 4 kV (Test Level 4 - asymmetrical) Output 0.5 kV (Test Level 1 - symmetrical) 0.5 kV (Test Level 1 - asymmetrical) 1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal 1 kV (Test Level 2 - asymmetrical) 1 kV (Test Level 2 - asymmetrical) Comments Criterion B Criterion A Conducted interference EN 61000-4-6 Input/Output/Signal asymmetrical asymmetrical Voltage 10 V (Test Level 3) 10 V (Test Level 3) Comments Criterion A Criterion A Emitted interference in acc. with EN 61000-6-3 Radio interference voltage in acc. with EN 55011 EN 55011 (EN 5 5022) Class B, area of application: Industry and residential Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential All technical specifications are nominal and refer to a room temperature of 25 °C and 70% relative humidity at 2000 m above sea level.
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 8
5 Safety regulations and installation
Before startup please ensure: – Only professionals may install, start up, and operate the device. – Observe the national safety and accident prevention regulations. NOTE: Danger if used improperly – The device is a built-in device. – The IP20 degree of protection (IEC 60529/EN 60529) of the device is in- tended for use in a clean and dry environ- ment. Do not subject the device to any load that exceeds the described limits. – Do not subject the device to mechanical and/or thermal loads that exceed the specified limits. – Installation and startup may only be car- ried out by qualified personnel. The rele- vant country-specific regulations must be observed. – It is not permissible to open or modify the device. Do not repair the device yourself but replace it with an equivalent device. Repairs may only be carried out by the manufacturer. The manufacturer is not li- able for damage resulting from violation. CAUTION: Before startup please ensure: – Connection must be performed by spe- cialist personnel and protection against electric shock ensured. – It must be possible to switch off the de- vice outside the power supply according to the regulations in EN 60950-1 (e.g., by line protection on the primary side). – All feed lines are sufficiently protected and dimensioned! – All output lines are dimensioned accord- ing to the maximum output current of the device or separately protected! – Sufficient convection is guaranteed! EXPLOSION HAZARD! Only remove equipment when it is discon- nected and not in the potentially explosive area. DANGER Never carry out work on live parts! The housing can become very hot, depending on the ambient temperature and load!
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 9
6 Basic circuit diagram
Figure 1 Basic circuit diagram
7 Structure
Figure 2 Function elements
1 DC input
2 DC output
3 Potentiometer 18 ... 29.5 V DC
4 LED "UIN < 0,8 x UN", yellow
5 "DC OK" LED, green
6 LED "BOOST", yellow
7 UIN > 0.8 x UN, active switching output
8 I < IIN, active switching output
9 DC OK, active switching output
10 DC OK relay contact 13/14
11 SFB switch (left: SFB activated, right: SFB deactivated)
12 Strain relief for connecting cables
13 DIN rail adapter
8 Installation
U > 0.8 x UIN N I<IN + + Input DC 96-110V Output DC A 24V 10 18-29.5V DC OK Boost IN U <0.8xU IN N 0.8xU N ON OFF SFB – To enable sufficient convection, we rec- ommend a minimum vertical spacing of 50 mm from other devices. Lateral spac- ing of 5 mm, or 15 mm for active compo- nents, must be observed in order to ensure correct device function of the DC/ DC converter. – The housing can become very hot de- pending on the ambient temperature and load of the DC/DC converter. The DC/DC converter can be snapped onto all DIN rails according to EN 60715 and should be mounted in the normal mounting position (connection terminal blocks on top and bottom). Input DC 96-110V Output DC A 24V 10 18-29.5V DC OK Boost IN U <0.8xU IN N 0.8xU N
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 10
9 Dimensions and mounting positions
Possible mounting positions: Normal mounting position, installation depth 125 mm (+ DIN rail) (delivery state) Rotated mounting position, 270° Y-axis, installation depth: 51 mm (+ DIN rail) 130 1225 5 115 230 Output DC 24V 10A Boost DC OK 18-29.5 V U <0.8xUIN N Input DC 96-110V QUINT POWER 13 14 19.2V >INU
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 11
10 Mounting on DIN rails
10.1 Normal mounting position
Assembly: Position the DC/DC converter with the DIN rail guide on the top edge of the DIN rail and snap it in by pushing downward. Removing: Pull back the snap-on catch using a screwdriver and detach the DC/DC converter from the bottom edge of the DIN rail.
10.2 Rotated mounting position (270° Y-axis)
A rotated mounting position can be achieved for the DC/DC converter by mounting the device on the DIN rail at a 270° angle. Mount the DIN rail adapter (UTA 107/30) as shown in the figure. No additional mounting material is required. torque). Figure 5 Rotated mounting position (270° Y-axis)
11 Input
Connection to the input voltage is established via the screw connectors on the DC input screw connection. The DC/DC converter converts a DC voltage of 67 ... 154 V into adjustable, regulated, and electrically isolated output voltage. Figure 6 Input
11.1 Protection of the primary side
Installation of the DC/DC converter must correspond to EN 60950 regulations. An internal fuse is provided for device protection. Additional device protection is not required. The connecting cables on the primary side should have large cross sections to keep the voltage drops in the cables as low as possible. Other mounting positions are also possible. Always observe position-dependent derating. A B B A NOTE: Device may be damaged If an internal fuse trips, this is due to a device fault. In this case, the DC/DC converter must be inspected in the factory. Input DC 96-110V Output DC A 24V 10 18-29.5V DC OK Boost IN U <0.8xU IN N 0.8xU N Input DC 96-110V U <0.8xU IN N
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 12
12 Output
Connection of the output voltage is established via the screw connectors on the DC output screw connection. The output voltage can be set on the potentiometer. Figure 7 Output
12.1 Protection of the secondary side
The DC/DC converter is electronically short-circuit-proof and idling-proof. In the event of an error, the output voltage is limited. It must be ensured that all output cables are di- mensioned accordingly for the maximum output current or have separate protection. The connecting cables on the secondary side should have large cross sections to keep the voltage drops in the cables as low as possible.
13 Output characteristic curve
The DC/DC converter works with the POWER BOOST power reserve as shown in the U/I characteristic curve in the figure. At ambient temperatures < 40°C, I BOOST is perma- nently available. It is also available at higher temperatures for a few minutes. In the event of a secondary-side short circuit or overload, the output current is limited to IBOOST. In this case, the DC/DC converter does not switch off but supplies output current continuously. The secondary voltage is then reduced until the short circuit is eliminated. The U/I characteristic curve with the POWER BOOST power reserve ensures that high inrush currents of capacitive loads in the primary circuit can be supplied reliably. Figure 8 Output characteristic curve N = 24 V –I N = 10 A –I BOOST = 12.5 A – SFB Technology = 60 A (for 12 ms) N = 240 W –P BOOST = 300 W Input DC 96-110V Output DC A 24V 10 18-29.5V DC OK Boost IN U <0.8xU IN N 0.8xU N Output DC A 24V 10 IN 0.8xU N I [A]OUT U [V] OUT UN IN I<I N <60 °C U < 0,9xU N I>I N <40 °C IBOOST
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 13
14 SFB technology
SFB (Selective Fuse Breaking) technology reliably switches off faulty current paths in the event of a short circuit. In this case, it supplies up to six times the nominal current for 12 ms. SFB technology therefore reliably triggers standard cir- cuit breakers. Faults are located reliably and important sys- tem parts remain in operation.
14.1 Circuit breaker tripping characteristics
Typically, a circuit breaker trips within 3 ... 5 ms. Fast enough to avoid voltage drops of parallel connected loads. Figure 9 Quick tripping of circuit breakers with SFB technology
14.2 Installation notes
To use the SFB technology of the QUINT DC/DC converter, you must observe the following requirements: – When designing the secondary side, consider the con- figuration matrix that describes the maximum cable lengths depending on the performance class of the DC/ DC converters, the conductor cross section, and the cir- cuit breaker. – Make sure that the source to be supplied is able to de- liver a corresponding current pulse to supply the DC/DC converter. For example, this can be achieved by up- stream connection of a QUINT SFB power supply (see accessories) or suitable battery capacity. – Ensure the lowest possible cable impedance at the in- put of the DC/DC converter by using short cable lengths and large cable cross sections.
14.3 Deactivating SFB technology
The DC/DC converter is equipped with an additional SFB switch which can be used to deactivate SFB technology. The SFB switch is located on the top side of the housing and is accessible for suitable tools, such as a small screwdriver through the vents. Figure 10 Position of the SFB switch The current configuration matrix can be found in the product download area. t I [A] 6x IN IBOOST IN 3-5 ms Observe the maximum distance between the source to be supplied and the DC/DC convert- er. (see also SFB configuration) If conditions cannot be observed, SFB tech- nology can be deactivated. Switch position SFB technology status left ON (defau lt setting) right OFF Activating/deactivating SFB technology must only be performed when the DC/DC converter is switched off. 14 _ OK DC IN OK O IN Output DC 24V 10A Boost DC OK 18-29.5 V U <0.8x U IN NInput DC 96-110V QUINT P OWER 0.8x UN <IN U ON OFF SFB -S1
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 14
14.4 SFB configuration
Maximum distance from the source to be supplied and the load (l2) The following parameters are the basis for calculation: – Circuit breaker from Siemens, B and C characteristics – B characteristic: electromagnetic tripping of the circuit breaker at the latest at (5-fold rated current) x (correc- tion factor 1.2 at 0 Hz) = 6-fold rated current – C characteristic: electromagnetic tripping of the circuit breaker at the latest at (10-fold rated current) x (correc- tion factor 1.2 at 0 Hz) = 12-fold rated current – Ambient temperature: +20 °C – The internal resistances of the circuit breakers are con- sidered. – In addition to short circuit current, the relevant power supply unit supplies half of the nominal current for paths connected in parallel. l1 l2 Supplying Source Load DC/DC Converters Cross section [2mm] 0.75 1.0 1.5 2.5 Distance l2 with C2 circuit breaker [m] 14 19 29 49 Distance l2 with C4 circuit breaker [m] 4 5 8 14 Distance l2 with B6 circuit breaker [m] 9 12 18 30
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 15
15 Signaling
The active DC OK signal output, the active POWER BOOST signal output, and the active UIN OK signal output are avail- able for function monitoring. In addition, the DC OK LED, BOOST LED, and UIN < 0.8 x UN LED enable function eval- uation of the DC/DC converter directly at the installation lo- cation. Figure 12 Signal outputs Due to permanent monitoring of input voltage, output volt- age and output current, critical operating states are reported before errors occur.
15.1 Active switching output “DC OK”
During normal operation of the DC/DC converter, the DC OK output signal (UOUT > 0.9 x UN) is between connection ter- minal blocks “DC OK” and “-” and can carry a maximum of 20 mA. The DC OK signal output indicates an output voltage underrange of more than 10 % by switching from “active high” to “low”. The DC OK signal is decoupled from the power output. This makes it impossible for devices connected in parallel to act as an external power supply.
15.2 Active switching output “I < I
During normal operation of the DC/DC converter, the boost output signal (I < IN) is between connection terminal blocks “I < IN” and “-” and can carry a maximum of 20 mA. The boost signal output indicates that the nominal current has been exceeded and that boost mode has been entered by switching from “active high” to “low”. 15.3 Active switching output “U IN > 0.8 x UN” During normal operation of the DC/DC converter, the UIN > 0.8 x UN output signal is between connection terminal blocks "UIN > 0.8 x UN” and “-” and can carry a maximum of 20 mA. The UIN > 0.8 x UN signal output indicates a low input voltage by switching from “active high” to “low”. I < IN I > IN U < 0.9 x UN DC OK LED, green lit lit Flashing Boost LED, yel- low OFF lit lit "DC OK" active switching output high high low "I < IN" active switching output high low low DC OK 13/14 relay contact closed closed opened Meaning Normal operation POWER BOOST, active Overload UIN > 0.8 x UN UIN < 0.8 x UN "UIN < 0.8 x UN" LED, yellow OFF lit "UIN OK" active switch- ing output high low Meaning U IN OK U IN low Input DC 96-110V Output DC A 24V 10 18-29.5V DC OK Boost IN U <0.8xU IN N 0.8xU N Output DC A 24V 10 IN 0.8xU N 18 ... 24 V DC 20 mA DC OK PLC Digital Input 18 ... 24 V DC 20 mA I<I N PLC Digital Input 18 ... 24 V DC 20 mA U >0,8xU IN N PLC Digital Input
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 16
15.4 Floating relay contact “DC OK” 13/14
The floating relay contact is located between connection ter- minal blocks 13 and 14 and can be loaded with max. 100 mA at max. 30 V AC/DC. The relay contact signal- izes a drop of output voltage of more than 10% by opening the N/O contact. The relay contact is decoupled from the power output. This makes it impossible for devices connected in parallel to act as an external power supply.
15.5 Set 96/110 V DC for signaling (bottom of de-
vice) The nominal input voltage of the DC/DC converter can be adjusted. Activate the signal threshold via the switch on the bottom of device. The following settings can be made: –9 6 V DC signal threshold activated, switch setting: back – 110 V DC signal threshold activated (factory setting), switch position: forward Figure 13 Signal threshold switch 96/110 V DC (bottom of device)
16 Derating
16.1 Temperature-dependent derating
With an ambient temperature of up to +40°C, the device supplies the continuous output current of IBOOST. The de- vice can supply a nominal output current of IN with ambient temperatures of up to +60°C. In the case of ambient temper- atures above +60°C, the output current must be reduced by 2.5% per Kelvin increase in temperature. The device does not switch off at ambient temperatures of +70°C or thermal overload. The output capacity is reduced as far as neces- sary to provide device protection. After it has cooled down, the output capacity is increased again.
16.2 Voltage-dependent derating
max. 30 V AC/DC 100 mA 13 14 PLC Digital Input 14 _ OK DC IN OK O IN Output DC 24V 10A Boost DC OK 18-29.5 V U <0.8x U IN NInput DC 96-110V QUINT P OWER 0.8x UN <IN U 110 -S2 There is no voltage-dependent derating. -25 40 6020 IBOOST IN Ambient temperature [°C] Output curre nt[A]
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 17
16.3 Position-dependent derating
The DC/DC converter can be snapped onto all DIN rails ac- cording to EN 60715 and should be mounted in the normal mounting position (connection terminal blocks on top and bottom). When installing in a different mounting position, derating should be adhered to. The characteristic curve can be used to determine the max- imal output power to be drawn for each ambient temperature for different mounting positions. Normal mounting position Rotated mounting position 90° X-axis Z X Y Input DC 96-110V Output DC A 24V 10 18-29.5V DC OK Boost IN U <0.8xU IN N 0.8xU N 100 125 150 175 [°C] -25 30 2010 40 50 60 70 80 100 125 150 175 [°C] -25 30 2010 40 50 60 70 80 Z X Y Input DC 96-110V Output DC A 24V 10 18-29.5V DC OK Boost U IN U <0.8xU IN N 0.8xU N
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 18 Rotated mounting position 180° X-axis Rotated mounting position 270° X-axis Z X Y Input DC 96-110V Output DC A 24V 10 18-29.5V DC OK Boost > U IN U <0.8xU IN N 0.8xU N 100 125 150 175 [°C] -25 30 2010 40 50 60 70 80 Input DC 96-110V Output DC A 24V 10 18-29.5V DC OK Boost U IN U <0.8xU IN N 0.8xU N Z X Y 100 125 150 175 [°C] -25 30 2010 40 50 60 70 80
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 19 Rotated mounting position 90° Z-axis Rotated mounting position 270° Z-axis Z X Y 100 125 150 175 [°C] -25 30 2010 40 50 60 70 80 Z X Y Input DC 96-110V Output DC A 24V 10 18-29.5V DC OK Boost IN U <0.8xU IN N 0.8xU N 100 125 150 175 [°C] -25 30 2010 40 50 60 70 80
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 PHOENIX CONTACT 20
17 Operating modes
17.1 Series operation
Two DC/DC converters can be connected in series to dou- ble the voltage. Only devices of the same performance class should be connected in series. Series connection should al- ways be used if the output voltage of the module is not suffi- cient. For example, DC/DC converters with 24 V DC nomi- nal output voltage each supply 48 V DC in series. Depending on the specification of the PE connection, output voltages of +48 V or -48 V as well as ±24 V DC can also be made available. Figure 14 Series operation
17.2 Parallel operation
DC/DC converters of the same type can be connected in parallel to increase both redundancy and power. No further adjustments to the default setting are necessary. To ensure symmetrical load distribution, it is recommended that all cable connections from the DC/DC converters to the busbar are the same length and have the same conductor cross section. Depending on the system, a protective circuit should be in- stalled at each individual device output (e.g. decoupling diode or DC fuse) for parallel connection of more than two DC/DC converters. This prevents high return currents in the event of a secondary device fault.
17.3 Redundant operation
Redundant circuits are suitable for supplying systems, which place particularly high demands on operational safety. If a fault occurs in the primary circuit of the first power supply unit, the second device automatically takes over the complete power supply without interruption, and vice versa. For this purpose, the power supply units to be connected in parallel must be large enough to ensure that the total current requirements of all loads can be fully met by one power sup- ply unit. External decoupling diodes are required for 100% redundancy! Optimization of redundancy can be achieved by decoupling and monitoring. Phoenix Contact offers a comprehensive product range for this purpose (e. g., QUINT-DIODE or QUINT-ORING). Example: diode module Example: QUINT ORING +48 V -48 V +24 V -24 V+ IN − + IN Σ =I N IN − + IN Σ = IN IN − + IN Σ = IN
QUINT-PS/96-110DC/24DC/10/CO 106467_en_00 21PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany phoenixcontact.com
17.4 Increasing power
The output current can be increased to n x IN in the case of n parallel connected DC/DC converters. Parallel connection for increasing power is used when extending existing sys- tems. Parallel connection is recommended if the DC/DC converter does not cover the current consumption of the most powerful load. Otherwise, the loads should be distrib- uted between individual devices that are independent of one another. IN − + IN Σ = 2x IN