UE10-2FG2D0 SICK

Document overview

  • Manufacturer or author: Provided By www.digicamel.com(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 5

Technical content

A B C D E F H I J K L M N O P Q R S T UE10-2FG2D0 | UE10-2FG SAFETY RELAYS Illustration may differ

Ordering information

Type Part no. UE10-2FG2D0 1043915 Other models and accessories www.sick.com/UE10-2FG Detailed technical data Safety-related parameters Safety integrity level SIL3 (IEC 61508) 1) SILCL3 (EN 62061) 1) Category Category 4 (EN ISO 13849) 1) Performance level PL e (EN ISO 13849) 1) B10d parameter 1 x 105 switching cycles (AC-15, 230 V, I = 2 A) 2.5 x 105 switching cycles (AC-15, 230 V, I = 1 A) 5.4 x 105 switching cycles (DC-13, 24 V, I = 0.5 A) 1 x 107 switching cycles (DC-13, 24 V, I ≤ 2 A) PFHD (mean probability of a dangerous fail- ure per hour) 7.0 x 10-10 (EN ISO 13849) TM (mission time) 20 years (EN ISO 13849) 1) If the feedback current path Y1 - Y2 (external device monitoring) is monitored using an appropriate main unit. Interfaces Connection type Fixed screw terminals Number of enable current (N/O) contacts 2, relevant for safety Number of contactor monitoring (N/C) con- tacts Electrical data Operating data Voltage supply B1/A2, B2/A2 Output circuit > 25 V AC / 60 V DC PELV Output circuit ≤ 25 V AC / 60 V DC PELV or SELV Residual ripple (≤ 2.4 Vpp) 1) Power consumption (≤ 2 W (DC)) 1) In DC operation, within the limits of VS.

2 SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK Online data sheet | 2018-09-11 15:13:28

Subject to change without notice

UE10-2FG2D0 | UE10-2FG SAFETY RELAYS Overvoltage category II Rated insulation voltage Ui 300 V AC Rated impulse withstand voltage Uimp 4 kV Test voltage 1.2 kV (50 Hz) (EN 60439-1) 1) In DC operation, within the limits of VS. Input circuits: B1, B2 Input current ≤ 50 mA Reset time ≤ 30 ms Test pulse width ≤ 1 ms Electrical output circuits: 13/14, 23/24, Y1/Y2 Response time (≤ 10 ms) Number of enable current (N/O) contacts 2, relevant for safety Number of contactor monitoring (N/C) con- tacts 1, external device monitoring (EDM) Contact type Positively driven Contact material Silver alloy, gold flashed Switching voltage Enable current contact 10 V AC/DC ... 250 V AC/DC Contactor monitoring contact 0.1 V AC/DC ... 60 V AC/DC Current-carrying capacity per OSSD Enable current contact 10 mA ... 6 A Contactor monitoring contact 1 mA ... 300 mA Switching capacity ≤ 1,500 VA (AC) ≤ 200 W (DC) Usage category AC-15/DC-13 (EN 60947-5-1) Rated operating current (voltage) 3 A (230 V AC)

4 A (24 V DC)

Mechanical life (relay contacts) 1 x 107 switching cycles Electrical life (relay contacts) 1 x 105 switching cycles Mechanical data Dimensions (W x H x D) 17.8 mm x 89.8 mm x 70.8 mm Weight 91 g Classifications ECl@ss 5.0 27371990 ECl@ss 5.1.4 27371990 ECl@ss 6.0 27371819 ECl@ss 6.2 27371819 ECl@ss 7.0 27371819 ECl@ss 8.0 27371819 ECl@ss 8.1 27371819 ECl@ss 9.0 27371819 2018-09-11 15:13:28 | Online data sheet Subject to change without notice SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK 3

A B C D E F H I J K L M N O P Q R S T UE10-2FG2D0 | UE10-2FG SAFETY RELAYS ETIM 5.0 EC001449 ETIM 6.0 EC001449 UNSPSC 16.0901 41113704 Dimensional drawing (Dimensions in mm (inch)) (0.7) (2.79) 17.8 70.8 (3.54) 89.8 Connection diagram 13 2414 Y1 2313 A2 23B2 Channel 2 Channel 1 B2 A2 Y2Y1 Y2 2414

4 SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK Online data sheet | 2018-09-11 15:13:28

Subject to change without notice

SICK AG | Waldkirch | Germany | www.sick.com SICK At A GlAnCe SICK is one of the leading manufacturers of intelligent sensors and sensor solutions for industrial applica- tions. A unique range of products and services creates the perfect basis for controlling processes securely and efficiently, protecting individuals from accidents and preventing damage to the environment. We have extensive experience in a wide range of industries and understand their processes and require- ments. With intelligent sensors, we can deliver exactly what our customers need. In application centers in Europe, Asia and North America, system solutions are tested and optimized in accordance with customer specifications. All this makes us a reliable supplier and development partner. Comprehensive services complete our offering: SICK lifetime Services provide support throughout the ma- chine life cycle and ensure safety and productivity. For us, that is “Sensor Intelligence.” WOrldWIde preSenCe: Contacts and other locations – www.sick.com