Technical content

Features

– Wide-range version (MACX MCR-...-UP) up to 253 V AC/DC – 24 V DC version with additional supply via DIN rail con- nector – Input/output can be co nfigured via DIP switch – Operating state indication via LED NOTE: Correct usage in potentially explosive areas The module is a category 3 item of electrical equipment. It is absolutely vital to follow the instructions provided here during installation and observe the information in the "Safety regulations and installation notes". Make sure you always use the latest documentation. It can be downloaded from the product at phoenixcontact.net/products. This data sheet is valid for all products listed on the following page: 103161_en_02 2013-04-22

103161_en_02 PHOENIX CONTACT 2 2T a b l e o f c o n t e n t s

103161_en_02 PHOENIX CONTACT 3 Description Type Order No. Pcs. / Pkt. Current measuring transducer for 1 A and 5 A AC, the output signal 0...20 mA or 4...20 mA, can be configured using a DIP switch with an operating mode indication through an LED MACX MCR-SL-CAC- 5-I 2810612 1 Current measuring transducer for 1 A and 5 A AC, the output signal 0...20 mA or 4...20 mA, can be configured using a DIP switch with an operating mode indication through an LED MACX MCR-SL-CAC- 5-I-UP 2810625 1 3O r d e r i n g d a t a Accessories Type Order No. Pcs. / Pkt. DIN rail power supply unit, primary-switched mode, slim design, output: 24 V DC / 1.5 A MINI-SYS-PS-100-240AC/24DC/1.5 2866983 1 DIN rail power supply unit, primary-switched mode, slim design, output: 24 V DC / 1.5 A, ATEX approval MINI-PS-100-240AC/24DC/1.5/EX 2866653 1 DIN rail connector for current transducers, gold-plated contacts, for DIN rail mounting, 5-pos. ME 22,5 TBUS 1,5/ 5-ST-3,81 GN 2707437 50 DIN rail connector for DIN rail power supply unit, gold-plated contacts, for DIN rail mounting, 5-pos. ME 17,5 TBUS 1,5/ 5-ST-3,81 GN 2709561 10

4 Technical data

Configurable/programmable Via DIP switches Setting range for min. input current 0 A AC ... 1 A AC (configurable) Setting range for max. input current 0 A AC ... 5 A AC (configurable) Overload capacity 2 x IN (continuous) Surge strength 20 x I N (1 s) Nominal frequency fN 50 Hz Frequency measuring range 45 Hz ... 65 Hz Curve type Sine Operate threshold 0.3 % (1 A) 0.45 % (5 A) Signal input Voltage input signal ≤ 300 V AC Current input signal 0 A AC ... 0.001 A AC 0 A AC ... 0.005 A AC Input impedance < 50 m Ω Output Output description Current output Non-load voltage 15 V Current output signal 0 mA ... 20 mA (configurable) 4 mA ... 20 mA (configurable) Max. current output signal 25 mA Configurable/programmable Via DIP switches Ripple < 10 mVPP (for 500 Ω at 20 mA) Load/output load current output < 500 Ω (at 20 mA) Status display LED red (error), LED green (ready) Output description N o switching output

103161_en_02 PHOENIX CONTACT 4 Supply MACX MCR-SL-CAC- 5-I MACX MCR-SL-CAC- 5-I-UP Nominal supply voltage 24 V DC (-20%...+25%) Nominal supply voltage range 24 V AC/DC ... 230 V AC/DC Max. current consumption < 32 mA (at UB=24 V DC, IOUT=20 mA) < 30 mA (at UB=24 V DC, IOUT=20 mA) < 13 mA (at UB=230 V AC, IOUT=20 mA) Power consumption < 0.9 W (at U B=24 V DC, IOUT=20 mA) < 0.9 W (at U B=24 V DC, IOUT=20 mA) < 3.4 W (at UB= 230 V AC, IOUT=20 mA) Protection against polarity reversal Yes Yes General data Measuring principle True r.m.s. value measurement at 50 Hz Maximum transmission error ≤ 0.5 % (of nominal range value under nominal conditions) Additional error approx. 2 % (45 Hz) approx. 1 % (65 Hz) Temperature coefficient, typical < 0.015 %/K Maximum temperature coefficient < 0.02 %/K Step response (10-90%) max. 300 ms typ. 200 ms Protection against polarity reversal Yes Mounting position Any Degree of protection IP20 Surge voltage category II Pollution degree 2 Dimensions W / H / D 22.5 mm / 104 mm / 114.5 mm Type of housing Polyamide PA non-reinforced green Connection data Connection method Screw connection Conductor cross section AWG/kcmil 24 ... 14 Stripping length 8 mm Safe isolation MACX MCR-SL-CAC- 5-I MACX MCR-SL-CAC- 5-I-UP Safe isolation acc. to EN 61010 acc. to EN 61010 Test voltage input/output 4 kV (50 Hz, 1 min.) 4 kV (50 Hz, 1 min.) Test voltage output/power supply 1.5 kV (50 Hz, 1 min.) 2 kV (50 Hz, 1 min.) Surge voltage category II III Pollution degree 2 2 Ambient conditions Permissible humidity (operation) 10 % ... 95 % (no condensation) Maximum altitude for use above sea level 2000 m

103161_en_02 PHOENIX CONTACT 5 Conformance with EMC Directive 2004/108/EC Noise immunity according to EN 61000-6-2 When being exposed to interference, there may be minimal deviations. Noise emission according to EN 61000-6-4 Conformance / approvals Conformance CE-compliant ATEX  II 3 G Ex nA IIC T4 Gc X UL, USA / Canada UL 508 Recognized

103161_en_02 PHOENIX CONTACT 6

5 Safety regulations and installation notes

5.1 Installation notes

– The device must be installed in a housing. – The device is designed for installation in zone 2 poten- tially explosive areas. – Installation, operation, an d maintenance may only be carried out by qualified electricians. Follow the installa- tion instructions described. When installing and operat- ing the device, the applicable regulations and safety directives (including national safety directives), as well as general technical regulations, must be observed. The technical data is provided in this package slip and on the certificates (conformity assessment, additional approvals where applicable). – It is not permissible to open or modify the device. Do not repair the device yourself but replace it with an equiva- lent device. Repairs may only be carried out by the man- ufacturer. The manufacturer is not liable for damage resulting from violation. – The IP20 degree of protection (IEC 60529/EN 60529) of the device is intended for use in a clean and dry environ- ment. Do not subject the device to any load that ex- ceeds the described limits. – The device is not designed for use in atmospheres with a danger of dust explosions. – The housing of the device provides a basic insulation against the neighboring devices, for 300 V eff. If several devices are installed next to each other, this has to be taken into account, and additional insulation has to be installed if necessary. If the neighboring device is equipped with basic insulation, no additional insulation is necessary. – Provide overcurrent protection (I ≤ 16 A) within the in- stallation.

5.2 Installation in the Ex area (zone 2)

– Observe the specified conditions for use in potentially explosive areas. – Install the device into a housing (control or distributor box) that meets the requirements of EN 60079-0 and EN 60079-15 and at least IP54 (EN 60529) degree of protection. – During installation and when connecting the supply and signal circuits, observe the requirements of EN 60079- 14. Devices may only be connected to circuits in zone 2 if they are suitable for operation in Ex zone 2 and for the prevailing conditions at the place of use. – In potentially explosive areas, terminals may only be snapped onto or off the DIN rail connector and wires may only be connected or disconnected when the pow- er is switched off. – The device must be stopped and immediately removed from the Ex area if it is damaged, has been subjected to an impermissible load, has been stored incorrectly, or if it malfunctions. – You can download the latest documents for these de- vices from www.phoenixcontact.net/products. The "attention symbol" on the device label means: Follow the installation instructions to avoid im- pairing the intended protection!

103161_en_02 PHOENIX CONTACT 7

6 Installation

6.1 Connection notes

6.2 Structure

  1. DIP switch 2. LEDs: diagnostics 3. Transparent cover 4. Output: Standard signals 5. Supply voltage 6. Input 7. Connection option for DIN rail connector

6.3 Block diagram

6.4 Power supply

Power supply via the power terminals The power of the current transducer is supplied via the con- Power supply via DIN rail connector The current transducer MACX MCR-SL-CAC-5-I can addi- tionally provide power supply via the DIN rail connector ME 22,5 TBUS (Order No. 2707437). Supply via the MACX MCR-SL-CAC-5-I module In the event of a total current consumption up to 1 A by the modules in series, power can be supplied directly at the con- nection terminal blocks of the MACX MCR-SL-CAC-5-I- module. We recommend connecting a 1.25 A fuse upstream. NOTE: electrostatic discharge! The device contains components that can be damaged or destroyed by electrostatic dis- charge. When handling the device, observe the necessary safety precautions against electrostatic discharge (ESD) according to EN 61340-5-1 and EN 61340-5-1.

32823 Blomberg, Germany

L(+)L(+)N(-) N(-) OUTI GND GND GND NC NOTE: Never connect the supply voltage directly to the DIN rail connector. It is not permitted to draw power from the DIN rail connector or from individual modules. OUT IN 4.1 3.1 1.1 4.2 3.2 1.2 4.3 3.3 1.3 4.4 3.4 1.4 GND L(+) OUT1 L(+) NC GND N(-) GND N(-)

103161_en_02 PHOENIX CONTACT 8

6.5 Assembly

Figure 3 Mounting and removing – Mount the module on a 35 mm DIN rail according to EN 60715. – When using the DIN rail connector, first place it into the DIN rail (see A – C). It is used to bridge the power sup- ply. It is also absolutely vital that you snap the module and the DIN rail connector into position in the correct di- rection: the snap-on foot should be at the bottom and the connector on the left.

6.6 Connecting the wires

Insert the wires in the corresponding connection terminal block. Use a screwdriver to tighten the screw in the opening above the connection terminal block. Figure 4 Connection of the cables A B C A B

103161_en_02 9PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany www.phoenixcontact.com

7 Configuration

The desired input/output signal configuration is selected using DIP switched. Figure 5 DIP switches DIP 1: Input current (input) –O F F = 1 A –O N = 5 A DIP 2: Output current (output) – OFF = 0 mA ... 20 mA – ON = 4 mA ... 20 mA

8 Application example

Figure 6 Current measurement L(+) L(+)N(-) N(-) OUTI GND GND GND NC DIP 24V 1000 A 0...20mA Mains voltage