Technical content

Power supply unit, primary switched-mode, single-phase, output: 48 V DC /10 A QUINT-PS-100-240AC/48DC/10 © PHOENIX CONTACT - 01/2007 Data Sheet INTERFACE QUINT POWER 48 DC is a universal power supply unit of 240 W ... 960 W. In case of a regulated and adjustable output voltage of 30 V DC ... 56 V DC, output currents of 5 A, 10 A and 20 A are available. The devices are built as primary switched-mode controllers and have a high degree of efficiency, due to which the heat loss is limited to a minimum. The high operational safety is guaranteed reliably in unstable global networks as well. QUINT POWER also functions in applications where static voltage dips, transient failures of the supply voltage unit or phase failure are to be expected. Generously dimensioned capacitors guarantee a mains buf- fering of more than 20 ms under full load. All three-phase QUINT POWER provide full output power, even in the event of a long-term phase failure. A reliable starting of complex loads is ensured by a power re- serve of up to 50% – the POWER BOOST. A preventive function monitoring diagnoses improper opera- ting states and minimizes downtimes in your system. For re- mote monitoring of this state, an active transistor switching output and a floating relay contact are available.

Description

Danger! Components with dangerously high voltage and high stored energy are located in the device! Never carry out work on live parts! Depending on the ambient temperature and the load, the housing can become very hot! Make sure you always use the the latest documentation. It can be downloaded at www.download.phoenixcontact.com. A conversion table is available on the Internet at www.download.phoenixcontact.com/general/7000_en_00.pdf – Universal power supply unit with an extensive product range, including special versions and accessories – Can be used worldwide in all industrial sectors due to a wide-range input and an international approval package – High operating safety due to long mains buffering under full load and high MTBF (> 500,000 h) – Reliable starting of heavy loads with high inrush currents through the POWER BOOST power reserve – High system availability of a ll three-phase devices, even if one phase fails permanently – Active function monitoring th rough switching output and preventive function monitoring through floating relay contact for remote diagnosis – Parallel connection possible for increased performance and redundancy – Simplified commissioning with LED function monitoring 102549_00_en

QUINT-PS-100-240AC/48DC/10 102549_00_en PHOENIX CONTACT 2 Description Type Order No. Pcs./Pkt. Power supply unit, primary switched-mode, single-phase, output: 48 V DC /10 A QUINT-PS-100-240AC/48DC/10 2938248 1 Accessories Type Order No. Pcs./Pkt. Universal wall adapter UWA 182/52 2938235 1 Input data Input nominal voltage range 100 V AC ... 240 V AC (wide range input) AC input voltage range 85 V AC ... 264 V AC DC input voltage range 90 V DC ... 350 V DC AC frequency range 45 Hz ... 65 Hz DC frequency range 0 Hz Current consumption 4.76 A (120 V AC)

2.3 A (230 V AC)

Inrush current limitation/I2t < 15 A (3.2 A2s) Power failure bypass > 30 ms Typical response time < 1 s Protective circuitry Transient surge protection Varistor Input fuse, integrated 12 A (slow-blow, internal) Recommended backup fuse for mains protection 10 A (characteristic B)

16 A (characteristic B)

Discharge current to PE < 3.5 mA Output data Nominal output voltage 48 V DC ±1% Setting range of the output voltage 30 V DC ... 56 V DC Output current 10 A (nominal value, up to 60°C)

13 A (with POWER BOOST)

Derating From +60°C 2.5% per Kelvin Output current limit 13 A (approx. IBOOST, for short circuit) Max. capacitive load Unlimited Control deviation < 1 % (change in load, static 10% ... 90%) < 5 % (change in load, dynamic 10% ... 90%) < 0.1 % (change in input voltage ±10%) Power loss nominal load max. 56 W Maximum power dissipation idling 5 W Efficiency > 90 % (for 230 V AC and nominal values) Ascent time < 2 ms (UOUT (10% ... 90%)) Residual ripple < 100 mV PP (with nominal values) Peak switching voltages < 100 mVPP Connection in parallel Yes, for redundancy and increased capacity Surge protection against internal surge voltages Yes, limited to approx. 60 V DC Resistance to reverse feed 60 V DC Order data Technical data

QUINT-PS-100-240AC/48DC/10 102549_00_en PHOENIX CONTACT 3 Signal output DC OK active Output description U OUT > 0.9 x UN: High signal Continuous current ≤ 40 mA Output voltage +24 V DC Status display "DC OK" LED green U OUT < 0.9 x UN: LED flashing Signal output DC OK floating Output description Relay contact, U OUT > 0.9 x UN: Contact closed Continuous current ≤ 0.5 A Output voltage ≤ 60 V AC/DC Status display "DC OK" LED green UOUT < 0.9 x UN: LED flashing Standards Electrical Equipment for Machinery EN 60204 Safety transformers for power supply units EN 61558-2-17 Electrical safety (of information technology equipment) EN 60950/VDE 0805 (SELV) UL/C-UL Recognized UL 60950 CB-Scheme Industrial control equipment UL/C-UL Listed UL 508 Shipbuilding German Lloyd, ABS Electronic equipment for use in electrical power installations EN 50178/VDE 0160 (PELV) SELV EN 60950 (SELV) EN 60204 (PELV) Safe isolation DIN VDE 0100-410 DIN VDE 0106-1010 Protection against electric shock DIN 57100-410 Protection against electric shock, basic requirements for safe isolation in electrical equipment DIN VDE 0106-101 Limitation of mains harmonic currents EN 61000-3-2 Device safety GS (tested safety) Approvals Granted approvals U u j

QUINT-PS-100-240AC/48DC/10 102549_00_en PHOENIX CONTACT 4 General data Insulation voltage input/output 4 kV AC (type test) 2 kV AC (routine test) Insulation voltage input / PE 3.5 kV AC (type test) 2 kV AC (routine test) Insulation voltage output / PE 500 V DC (routine test) Installation position Horizontal DIN rail NS 35, EN 60715 Degree of protection IP20 Class of protection I, with PE connection MTBF > 500 000 h in acc. with IEC 61709 (SN 29500) Housing version AluNox (AlMg1) Width 157 mm Height 130 mm Depth 125 mm Width with alternative assembly 122 mm Height with alternative assembly 130 mm Depth with alternative assembly 160 mm Weight 2.5 kg Climatic data Ambient temperature (operation) -25 °C ... 70 °C (> 60°C derating) Ambient temperature (storage/transport) -40 °C ... 85 °C Max. permissible relative humidity (operation) 95 % (at 25°C, no condensation) Vibration (operation) < 15 Hz, amplitude ±2.5 mm in acc. with IEC 60068-2-6 Shock 30g in all directions in acc. with IEC 60068-2-27 Pollution degree in acc. with EN 50178 2 Climatic class 3K3 (in acc. with EN 60721) Conformance with EMC directive 89/336/EEC Immunity to interference in acc. with EN 61000-6-2 Discharge of static electricity in acc. with EN 61000-4-2 Housing Level 4 Contact discharge 8 kV Discharge in air 15 kV Comments Criterion B Electromagnetic HF field in acc. with EN 61000-4-3 Housing Level 3 Frequency range 80 MHz ... 1000 MHz Field intensity 10 V/m Comments Criterion A Fast transients (burst) in acc. with EN 61000-4-4 Input 4 kV (level 4 - asymmetrical: conductor to ground) Output 2 kV (level 3 - asymmetrical: conductor to ground) Signal 1 kV (level 1 - asymmetrical: conductor to ground) Comments Criterion B

QUINT-PS-100-240AC/48DC/10 102549_00_en PHOENIX CONTACT 5 Surge voltage capacities (surge) in acc. with EN 61000-4-5 Input 4 kV (inst. class 4 - asymmetrical: conductor to ground) 2 kV (inst. class 4 -symmetrical: conductor to conductor) Output 0.5 kV (level 1 - asy mmetrical: conductor to ground) 0.5 kV (level 1 - symmetrical: conductor to conductor) Signal 1 kV (level 2 - asymmetrical: conductor to ground) Comments Criterion B Conducted disturbance in acc. with EN 61000-4-6 Input/Output/Signal Level 3 - asymmetrical Frequency range 0.15 MHz ... 80 MHz Voltage 10 V Comments Criterion A Voltage dips in acc. with EN 61000-4-11 Input (mains buffering > 20 ms) Comments Criterion B Emitted interference in acc. with EN 61000-6-3 Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential Note: Criterion A: Normal operating behavior within the defined limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself EN 55011 corresponds to CISPR11 / EN 55022 corresponds to CISPR22 EN 61000 corresponds to IEC 1000 Conformance with EMC directive 89/336/EEC Immunity to interference in acc. with EN 61000-6-2 L (+) N (-) PE DC OK PFC active Block diagram

QUINT-PS-100-240AC/48DC/10 102549_00_en PHOENIX CONTACT 6 Output DC 48V 10A + + – – DCOK DC OK Adjust 30.0-56.0V Input AC 100-240V NL QUINT POWER 14 U INDUSTRIAL CONTROL EQUIPMENT 43KA LISTED APPROVALS Read in stallation in structions before c onnectin g to m ain s www.interface.phoenixcontact.com - 25 … + 70 °C - 13 … + 158 °F (>60°C/140°F Derating) –25 EN 60950 EN 60204 EN 61558-2-17 B EN 61000-6-2 EN 61000-6-3 V 10A – – Output DC 48V 1 + + DC OK DC OK Structure

1 AC input

2 DC output

3 DC OK output active

4 DC OK output, floating

5 Potentiometer (covered) 30 V DC ... 56 V DC

6 DC OK control lamp

7 DIN rail adapter

[mm2] AWG [Nm] solid stranded Torque Input 0.2 - 6 0.2 - 4 24 - 10 0.5 - 0.6 Output 0.5 - 16 0.5 - 10 20 - 6 1.2 - 1.5 S i g n a l 0 . 5-1 6 0 . 5-1 0 2 0-6 1 . 2-1 . 5 Input data Input nominal voltage range 100 V AC ... 240 V AC (wide range input) AC input voltage range 85 V AC ... 264 V AC DC input voltage range 90 V DC ... 350 V DC AC frequency range 45 Hz ... 65 Hz DC frequency range 0 Hz Input fuse, integrated 12 A (slow-blow, internal) Recommended backup fuse for mains protection 10 A (characteristic B) Type of connection Screw connection Stripping length 7 mm Output data Nominal output voltage 48 V DC ±1% Setting range of the output voltage 30 V DC ... 56 V DC Output current 10 A (nominal value, up to 60°C) Type of connection Screw connection Stripping length 7 mm

QUINT-PS-100-240AC/48DC/10 102549_00_en PHOENIX CONTACT 7 Safety and warning notes The power supply units are built-in devices. The device may only be installed and put into operation by qua- lified personnel. The corresponding national regulations (e.g. VDE, DIN) must be observed. Danger! Components with dangerously high voltage and high stored energy are located in the device! Never carry out work on live parts! Depending on the ambient temperature and the load, the housing can become very hot! Before startup please ensure: The mains connection has been carried out by a competent person and protection against electric shock is guaranteed! The device can be disconnected outside the power supply unit in accordance with the regulations as in EN 60950 (e.g. through primary side line protection)! The ground conductor is connected! All feed lines are sufficiently protected and dimensioned! All output lines are dimensioned according to the maximum output current of the device or separately protected! Sufficient convection is guaranteed! Installation In order to guarantee sufficient convection, we recommend observing the following minimum distance to other modules: 5 cm in a vertical di- rection and 0 cm in a horizontal direction. The power supply unit can be snapped onto all DIN rails in acc. with EN 60715. They must be horizontal (connecting terminal blocks below). Output DC 24V 20A + + – – DCOK DC OK Adjust 30.0-56.0V Input AC 100-240V NL QUINT POWER 14 U INDUSTRIAL CONTROL EQUIPMENT 43KA LISTED APPROVALS Read in stallation instru ctio ns before connectin g to m ain s www.interface.phoenixcontact.com - 25 … + 60 - 13 … + 14 0 °F –25 EN 60950 EN 60204 EN 61558-2-17 BEN 61000-6-2 EN 50081-1

QUINT-PS-100-240AC/48DC/10 102549_00_en PHOENIX CONTACT 8 Output DC 24V 20A + + – –DC OK13 DC OK Adjust 30.0-56.0V InputAC 100-240V NL5 QUINT PO WER 157 122 230 130 115 Installation position Slim-style installation: Installation depth 125 mm (+ DIN rail) Low-profile installation: Installation depth 160 mm (+ DIN rail) (condition at the time of delivery) Low-profile installation: Assembly Position the module with the DIN rail guide on the upper edge of the DIN rail, and snap it in with a downward motion. Dismantling Pull the snap lever open with the aid of a screwdriver and slide the module out at the lower edge of the DIN rail.

QUINT-PS-100-240AC/48DC/10 102549_00_en PHOENIX CONTACT 9 Slim-style installation: Slim-style installation can be achieved by mounting the device at right-angles to the DIN rail. Mount the DIN rail adapter (UTA 107) as described in the figure. No additional mounting material is required. Fixing screws: Torx T10 (torque 0.8 - 0.9 Nm). +LN – QUINT PE+LN – QUINT PE+LN – QUINT PE+LN – QUINT PE N PE PEN N +LN – QUINT PE+LN – QUINT PE L N PE L PEN L N +LN – QUINT PE TN-S TN-C TT iT Connection, network forms 100...240 V AC networks The 100-...240 V AC connection is established using the L, N and PE screw connections. The device can be connected to 1-phase AC networks or to two of the phase conductors of three-phase systems (TN, TT or IT networks in acc. with VDE 0100-300/IEC 60364-3) with nominal voltages of 100 V AC ...240 V AC. For operation on two of the phase conductors of a three-phase system, an isolating facility for all poles must be provided.

QUINT-PS-100-240AC/48DC/10 102549_00_en PHOENIX CONTACT 10 Input Protection of the primary side The device must be installed in acc. with the regulations as in EN 60950. It must be possible to disconnect the device using a suitable isolating facility outside the power supply. The primary side line protection, for example, is suitable. For device protection, there is an internal fuse. Additional device protection is not necessary. Recommended backup fuse for mains protection Power circuit breaker 10 A or 16 A, characteristic B (or iden- tical function). In DC applications, a suitable fuse must be wired in upstream. If an internal fuse is triggered, there is most probably a malfunction in the device. In this case, the device must be inspected in the factory! Output DC 48V 10A + + – – DC OK DC OK Adjust 30.0-56.0V Input AC 100-240V NL QUINT POWER 14 U INDUSTRIAL CONTROL EQUIPMENT 43KA LISTED APPROVALS Read in sta llatio n in structio ns before c onnectin g to m ains www.interface.phoenixcontact.com - 25 … + 70 °C - 13 … + 1 58 °F (>6 0°C/140°F Dera ting –25 EN 60950 EN 60204 EN 61558-2-17 B EN 61000-6-2 EN 61000-6-3

QUINT-PS-100-240AC/48DC/10 102549_00_en PHOENIX CONTACT 11 Output DC 48V 10A + + – – DCOK DC OK Adjust 30.0-56.0V Input AC 100-240V NL QUINT POWER 14 U INDUSTRIAL CONTROL EQUIPMENT 43KA LISTED APPROVALS Read in stallation in structions before c onnecting to m ain s www.interface.phoenixcontact.com - 25 … + 70 °C - 13 … + 158 °F (>60°C/140°F Derating) –25 EN 60950 EN 60204 EN 61558-2-17 B EN 61000-6-2 EN 61000-6-3 V 10A – – Output DC 48V 1 + + DC OK DC OK Output Make sure that all output lines are dimensio- ned according to the maximum output current or are separately protected. The cables on the secondary side must have sufficiently large cross sections in order to keep the voltage drops on the lines as low as possible. The connection is established using screw connections on the screw connection of the DC output: 48 V DC: "+" and "–"; DC OK switching output active: "DC OK" and "–"; DC OK output floating: "13" and "14". The set output voltage is 48 V DC at the time of delivery. The output voltage can be set on the potentiometer. Protection of the secondary side The device is electronically protected against short circuit and idling. In the event of a malfunction, the output voltage is limited to 60 V DC. Make sure that all output lines are dimensioned according to the maximum output current or are sepa- rately protected! The cables on the secondary side should have large cross sections in order to keep the voltage drops on the lines to a minimum. Signaling An active signal output and a floating signal contact are provided to monitor the function. The DC OK LED also enables the evaluation of function of power supply directly on the operation site. DC OK LED ON Flashing OFF Active DC OK switching out- put U = +24 V (in reference to "–") U = 0 V (in reference to "–") U = 0 V (with reference to "–") Floating DC OK output Closed Open Open Voltage at the output Outpu t voltage > 90% of the set voltage Output voltage < 90% of the set voltage No voltage at the output Meaning Output voltage and output current OK QUINT POWER is in opera- tion, but there is a fault in the consumer, the current con- sumption is greater than I BOOST or the output is short circuited. QUINT POWER is out of operation because there is no mains voltage, the fuse on the primary side has tripped, or the device is faulty.

QUINT-PS-100-240AC/48DC/10 102549_00_en PHOENIX CONTACT 12 Floating contact The floating signal contact opens and indicates that the set output voltage has undershot by more than 10%. Signals and ohmic loads of up to a maximum of 60 V and currents of up to a maximum of 0.5 A can be connected. A suitable protec- tive circuit (e.g. free-wheeling diode) is necessary for heavily inductive loads such as a relay. DC OK + + – – DC OK13 14 max. 60 V AC/DC, 0.5 A Active signal output The 24 V DC signal is applied between the "DC OK" and "–" connecting terminal blocks and can carry up to 40 mA. This signal output signalizes when the output voltage is more than 10% below the output voltage by switching from "active high" to "low". The DC OK signal is decoupled from the power output. It is thus not possible for parallel switched devices to provide ex- ternal supply. The 24 V DC signal can be directly connected to a logic input for evaluation. DC OK +DC OK -1413 -+

24 V DC

Monitoring two devices: Use the active signal output of de- vice 1 and loop in the floating signal output of device 2. In the event of malfunctioning, a common alarm is output. Any number of devices can be looped in. This signal combination saves wiring costs and logic inputs. DC OK24 V DC 40 mA + + – – Output 24V DC DC OK13 14 + + – – Output 24V DC DC OK13 14 Device 1 Device 2

QUINT-PS-100-240AC/48DC/10 102549_00_en PHOENIX CONTACT 13 Function Output characteristic curve At ambient temperatures Tamb < +40°C, the device can con- tinuously provide current IBOOST at nominal voltage. In the event of a higher load, the operating point follows the U/I characteristic curve depicted in the figure. In the event of a short circuit or overload, the output current is limited to IBOOST. Thereby, the device does not switch off, but rather supplies a continuous output current. The secondary voltage is reduced until the short circuit on the secondary side has been remedied. The U/I characteristic curve ensures that the heavily capaci- tive loads and the consumers with DC/DC converters in the input circuit can be fed without problems using QUINT PO- WER. Downstream fuses are triggered reliably. Selectivity in the design of your system is guaranteed at all times. U N = 48 V IN = 10 A IBOOST = 13 A PN = 480 W PBOOST = 625 W U [V] OUT IOUT [A] UN IBOOSTIN <6 0° C <4 0° C Thermal behavior With an ambient temperature of up to +40°C, the device sup- plies the continuous output current of IBOOST. The device can supply a nominal output current of IN with ambient tempera- tures of up to +60°C. In the case of ambient temperatures above +60°C, the output current must be reduced by 2.5% per Kelvin increase in temperature. The device does not switch off at ambient temperatures of +70°C or thermal over- load. The output capacity is reduced as far as necessary to provide device protection. After it has cooled down, the out- put capacity is increased again. Ambient temperature [°C] Output current [A] IN 20 40 60 IBOOST

QUINT-PS-100-240AC/48DC/10 102549_00_en 14PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany www.phoenixcontact.com Parallel operation Devices of the same type can be connected in parallel to en- able both redundancy and an increase in efficiency. No other alignment is necessary when in the state of delivery. If the output voltage is adjusted, a uniform distribution of power is guaranteed by setting all parallel operated power supply units to exactly the same output voltage. To ensure symme- trical distribution of power, we recommend designing all cable connections from the power supply unit to a busbar of the same length and with the same conductor cross section. The system makes it advisable to install a protective circuit at the output of each device when more than two power sup- ply units are connected in parallel (e.g. decoupling diode or DC fuse). This prevents high reverse feed currents in the event of a secondary device fault. IN − + IN Σ =I N Redundant operation Redundant circuits are suitable for the supply of systems which make especially high requirements on the operational safety. If a fault occurs in the primary circuit of the first power supply unit, the second device automatically takes over the entire power supply, without interruption, and vice versa. For this reason, the power supply units to be connected in paral- lel are dimensioned in such a way that the total current re- quirement of all consumers can be completely covered by one power supply unit. 100% redundancy makes external decoupling diodes necessary (QUINT-DIODE/40, Order No. 2938963)! IN − + IN Σ =2xI N Increased performance For n parallel connected devices, the output current can be increased to n x IN. Parallel connection to increase efficiency is used for the expansion of existing systems. It is advisable to use parallel connection if the power supply unit does not cover the current requirement of the most powerful consu- mer. Otherwise the consumers should be spread among in- dividual devices independent of one another. A maximum of five devices can be connected in parallel!