102051 PHOENIX

Document overview

  • Manufacturer or author: Provided By digicamel.com
  • PDF pages: 8

Technical content

MINI POWER provides: Extra narrow design with widths of 22.5 mm, Global use due to a wide-range input A high level of operational safety in complex global networks Reliable startup of heavy loads due to POWER BOOST The reliability of a power supply unit determines the availability of individual components in a system and whether complex systems can function safely. The globalization of markets increases the demands placed on the power supply unit. A wide-range input and a high level of availability are required. These requirements are met by MINI POWER. 1. Short Description MINI POWER is the extra narrow power supply unit, which is available in widths of 22.5 mm, 45 mm, and In addition to a 24 V version with output currents of

1 A, 2 A, and 4 A, special voltages are also available

with 5 V/3 A, +/-15 V/1 A, and 10 - 15 V/2 A for connection to single-phase AC networks or to two external conductors in three-phase networks with nominal voltages of 100 - 240 V AC. Two DC/DC converters convert low direct voltages into an adjustable and regulated 24 V output voltage. With the DIN rail bus connector, the MINI-SYS-PS can be connected in parallel to supply other modules in the same system with a regulated 24 V DC voltage. Reliable startup of heavy loads is ensured by a power reserve of up to 100% – the POWER BOOST. The high level of operational safety is also ensured in complex global networks. MINI POWER also operates in applications where static voltage dips or transient power supply failures. Powerful capacitors ensure mains buffering of more than 20 ms at full load. 2. Area of Application MINI POWER can be used globally due to the consistent provision of a wide-range input. In this way, your entire system can be tested at any production location in the world and can be delivered to any location in the world without faulty switching of the input voltage. This reduces storage costs and logistical effort. An international approval package including UL 60950 for IT equipment and UL 508 for industrial control equipment enables the device to be used globally. Power Supply Unit, Primary Switched, Narrow Design MINI-PS-100-240AC/24DC/C2LPS Headquarters: © Phoenix Contact GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany Phone +49 - 52 35 - 30 0 • Fax +49 - 52 35 - 34 12 00 • www.phoenixcontact.com Local Contact: www.phoenixcontact.com/salesnetwork

PHOENIX CONTACT page 2 of 8 Solid Stranded Torque [mm ]A WG [Nm] [Ib in]

Description

primary switched, narrow design Technical Data Input Data Nominal input voltage Input voltage range (current consumption) Frequency Current consumption (for nominal values) Inrush current limiting/I t (+25°C [+77°F]) Mains buffering for a nominal load (typical) Switch-on time after applying the mains voltage Transient surge protection Input fuse, internal Recommended fuse Output Data Nominal output voltage U N /tolerance Setting range for the output voltage Output current during convection cooling and nominal values Nominal output current I N -25°C to +60°C (-13°F to +140°F) Derating Short-circuit current limit Startup of capacitive loads System deviation on: Static load change 10 - 90% Dynamic load change 10 - 90% Input voltage change ±10% Maximum power dissipation No load/nominal load Level of efficiency (typical) Response time U OUT (10% - 90%) Residual ripple/switching peaks (20 MHz) Can be connected in parallel Internal surge protection Resistance to return supply Signal Output Data DC OK (active) (U out > 0.9 x U N high signal) LED (U out > 21.5 V DC LED permanently on) MINI-PS-100-240AC/24DC/C2LPS

1 AC NEC Class 2

Type Order No. Pcs. Pkt. MINI-PS-100-240AC/24DC/C2LPS 28 66 33 6 100 - 240 V AC (wide-range input) 85 - 264 V AC 90 - 350 V DC 45 - 65 Hz 0 Hz 1.3 A (120 V AC)/0.8 A (230 V AC), approximately < 15 A/< 2.1 A s, typical > 20 ms (120 V AC)/> 100 ms (230 V AC) < 0.4 s Varistor T3.15 AL 250 V (device protection)

6 A, 10 A circuit breakers, characteristic B (EN 60 898)

24 V DC/±1%

22.5 - 26 V DC

3.8 A (U

= 22.5 - 26 V DC) From +60°C (+140°F), 2.5% per Kelvin

5 A, approximately

< 1%, typical < 3%, typical < 0.1%, typical

2.5 W/12 W

88% (at 230 V AC and at nominal values) 0.3 ms < 100 mV pp (for nominal values) To increase redundancy and power Yes, limited to 35 V DC, approximately

35 V DC

+24 V signal/20 mA, maximum Green LED 99 mm (3.898 in.) 67.5 mm (2.657 in.) 114.5 mm (4.508 in.) L (+) N (– ) DC OK Power Supply Unit, Primary Switched, Narrow Design – MINI-PS-100-240AC/24DC/C2LPS 3. Technical Data 7 mm (0.28 in.)

PHOENIX CONTACT page 3 of 8 Power Supply Unit, Primary Switched, Narrow Design – MINI-PS-100-240AC/24DC/C2LPS General Data Insulation voltage: Input/output Approval package Electrical equipment of machines Safety transformers for switched-mode power supply units Electrical safety (of IT equipment) Industrial control equipment Limitation of output power Electronic equipment for use in electrical power installations Safety extra-low voltage Safe isolation Protection against electric shock, basic requirements for safe isolation in electrical equipment Limitation of harmonic line currents Mounting position Can be mounted with spacing - Vertically - Horizontally Degree of protection Class of protection MTBF Housing version Weight Dimensions (W x H x D) Climatic Data Ambient temperature Operation Storage Humidity Vibration According to IEC 68-2-6 Shock According to IEC 68-2-27 Pollution degree Climatic category cccc Conformance With EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC EMC (Electromagnetic Compatibility) Noise Immunity According to EN 61000-6-2: Electrostatic discharge (ESD) EN 61000-4-2 Housing Contact discharge: Air discharge: Electromagnetic HF field EN 61000-4-3 Housing Frequency: Field strength: Fast transients (burst) EN 61000-4-4 Input: Output: Signal: Surge current loads (surge) EN 61000-4-5 Input: Output: Conducted interference EN 61000-4-6 I/O/S: Frequency: U Voltage dips EN 61000-4-11 Input: Noise Emission According to EN 50081-2: Radio interference voltage EN 55011 Radio interference emission EN 55011 EN 55011 corresponds to CISPR11/EN 55022 corresponds to CISPR22 EN 61000 corresponds to IEC 1000 Criterion A: Normal operating characteristics within the speci fied limits. Criterion B: Temporary adverse effects on the operating characteristics, which the device corrects automatically. 3 kV AC (type test)/3 kV AC (routine test) EN 60 204 (Surge Voltage Category III) EN 61 558-2-17 EN 60950/VDE 0805 UL/C-UL Recognized UL 60 950 u UL/C-UL Listed UL 508 NEC Class 2 EN 50 178/VDE 0160 PELV (EN 60 204) SELV (EN 60 950) VDE 0100-410 DIN VDE 0106-101 According to EN 61000-3-2 On horizontal NS 35 DIN rail according to EN 50022 With spacing of 5 cm (1.969 in.) 0 cm (0 in.) IP20 ΙΙ , (in closed control cabinets) > 500,000 h according to IEC 1709 (SN 29 500) Polyamide PA, color green 0.4 kg, approximately -25°C to +70°C [-13°F to +158°F] (> +60°C [+140°F] derating) -40°C to +85°C (-40°F to +185°F) Up to 95% at +25°C (+77°F), no condensation < 15 Hz, amplitude ±2.5 mm/15 Hz - 150 Hz, 2.3 g 30 g all space directions 2 (according to EN 50 178) 3K3 (according to EN 60 721) Requirements EN 61 000-6-2 MINI-PS-100-240AC/24DC/C2LPS 4 kV 8 kV > Level 3 8 kV 8 kV 80 - 1000 MHz

10 V/m

4 kV (Level 4) 2 kV (Level 3) 1 kV (Level 2) 2 kV asymmetrical 1 kV symmetrical 0.5 kV asymmetrical 0.5 kV symmetrical 1 kV asymmetrical 4 kV (Level 4) 2 kV (Level 4) 0.5 kV (Level 1) 0.5 kV (Level 1) 0.5 kV (Level 1) asymmetrical 0.15 - 80 MHz 10 V Level 3 0.15 - 80 MHz 10 V 30% reduction of the input voltage for 0.5 periods See Input Data: Mains buffering >20 ms Class A EN 55011 (EN 55022) Class B Class A EN 55011 (EN 55022) Class B symmetrical: Cable to cable asymmetrical: Cable to ground Class A: Industrial applications Class B: Industrial and domestic applications U LISTED

PHOENIX CONTACT page 4 of 8 1111 AC input: 85 - 264 V AC input voltage Frequency 45 - 65 Hz (0.2 mm to 2.5 mm solid) (0.2 mm to 2.5 mm stranded) (25 - 14 AWG) Internal fuse T3.15 AL 250 V Recommended fuse

6 A or 10 A LS/characteristic B

DC output:

24 V DC output voltage (default),

can be set from 22.5 - 26 V DC using potentiometer (0.2 mm to 2.5 mm solid) (0.2 mm to 2.5 mm stranded) (25 - 14 AWG) The device is idling-proof and short-circuit-proof. 3333 DC OK output active 4444 Potentiometer 22.5 - 26 V DC 5555 DC OK LED 6666 Universal latching foot for EN DIN rails 5. Safety Notes and Warning Instructions To ensure that the device can be operated safely and all functions can be used, please read these instructions carefully. Caution: Never carry out work when the power is turned on, this is highly dangerous. L(+) N(-) MINI-PS-100-240AC/24DC/C2LPSOrder No.: 28 66 33 6 U INDUSTRIALCONTROL EQUIPMENT 1YD8 LISTED APPROV ALS u INFORMATIONTECHNOLOGY EQUIPMENT Power Supply INPUT OUTPUT AC: 100-240V50-60Hz Range: 85-264V 1.6-0.7ADC: 90-350V1.3-0.4A 24V DC±1% 3.8A Read installation instructions before connecting to mains www.interface.phoenixcontact.com TEMPERA TURE - 25 … + - 13 … + 140 –25 MINI POWER DCOK OUT DC 24V 3.8 A 22.5-26 V DC L(+) N(-) IN AC 100-240 V DCOK

5 Figure 04

Power Supply Unit, Primary Switched, Narrow Design – MINI-PS-100-240AC/24DC/C2LPS 4. Device View, Connections, and Control Elements Installation and startup must only be carried out by qualified personnel. The relevant country-specific regulations (e.g., VDE, DIN) must also be observed. Before startup it is particularly important to ensure that:

  • The mains has been connected correctly and protection is provided against electric shock.
  • The device can be switched off outside the power supply according to EN 60950 regulations (e.g., by the line protection on the primary side).
  • All supply lines have sufficient fuse protection and are the correct size.
  • All output cables are the correct size for the maximum device output current or have separate fuse protection.
  • Sufficient convection is ensured. MINI POWER is a built-in device. After installation the terminal area must be covered to provide sufficient protection against unauthorized access to live parts. This is ensured by installing the device in the control cabinet or distributor box. The device contains dangerous live elements and high levels of stored energy.

PHOENIX CONTACT page 6 of 8 Power Supply Unit, Primary Switched, Narrow Design – MINI-PS-100-240AC/24DC/C2LPS +LN – L N PE MINI +LN – L PEN MINI +LN – L N MINI +–MINI N PE L N +–MINI PEN L N +–MINI N L N PE L N MINI TN-S network TN-C network TT network 6.2. Connection of Various Types of Network: 100 - 240 V AC networks Figure 08 IT network L(+) N(-) MINI-PS-100-240AC/24D Order No.: 28 66 33 6 U LIS T APPRO VA Power Supply INPUT OUTPUT AC: 100-240V50-60Hz Range: 85-264V 1.6-0.7ADC: 90-350V1.3-0.4A 24V DC±1% 3.8A TEMPE R MINI POWER DCOK OUT DC 24V 3.8 A 22.5-26 V DC L(+) N(-) IN AC 100-240 V DCOK 2222 4444 1111 3333 Figure 09 Recommended Fuse:

6 A or 10 A circuit breaker, characteristic B (or

equivalent). A suitable fuse should be provided for DC applications. If the internal fuse is blown, this is most probably due to a device fault. In this case, the device should be checked in the factory. Connecting Cable: The device is equipped with COMBICON connectors. This reliable user-friendly connection method enables quick device connection and visible isolation of the electrical connection, if required. Only operate connectors when the power is switched off. The following cable cross sections can be connected: For reliable and safe-to-touch connections: Strip 7 mm (0.28 in.) from the connector ends. 6.3. Input ( 1111 , Figure 9) The 100 - 240 V AC connection is made using the L and N screw connections. The device can be connected to single-phase AC networks or to two external conductors for three-phase networks (TN, TT or IT network according to VDE 0100 T300/IEC364-3) with nominal voltages of 100 - 240 V AC. Protecting the Primary Side The device must be installed according to the specifications of EN 60 950. It must be possible to switch off the device using a suitable disconnecting device outside the power supply. Note that an all-pole disconnecting device must be provided for two-phase operation using two external conductors for a three-phase network. For this, line protection on the primary side, for example, is suitable. Further device protection is not required, as an internal fuse is present. Solid [mm2] Stranded [mm2] AWGT orque [Nm] [Ib in] 7 mm (0.28 in.)