© PHOENIX CONTACT - 03/2008101460_en_04 INTERFACE PLC-…24UC/1/S/H PLC-…24UC/1/S/L Data Sheet 1D e s c r i p t i o n The 6.2 mm PLC-…24UC/1/S… PLC INTERFACE module supports "Manual", "Zero", and "Automatic" functions. The load can be switched directly using the module.

1.1 Switching Function

Depending on the version, the switch can be operated either by hand or using a screwdriver. A floating contact provides confirmation for the "Automatic" switching state.

1.2 Optimum Use of Plug-In Bridges

The PLC INTERFACE module achieves maximum efficiency with the user-friendly FBST plug-in bridge system. The PLC-…24UC/1/S… makes effe ctive use of the bridging options for the A1/A2 connection on the coil side, for the supply at connection 13 on the contact side, and for the manual input at connection M. Especially effective here are the 500 mm long color-insulated continuous plug-in bridges that can easily be cut to the required length and quickly inserted in the bridge shafts. They eliminate the need for complicated and time-consuming loop bridges.

1.3 Additional Advantages

– Environmentally friendly, cadmium-free power contact material for loads up to 250 V AC/6 A – Integrated input/protective circuit – Safe isolation according to DIN EN 50178 – Spring-cage and screw connection types available –6 k V rms electrical isolation between coil and contact – Floating confirmation contac t for "Automatic" switching state Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com A conversion table is available on the Internet at This data sheet is valid for all products listed on the following page: PLC INTERFACE With Switch and Integrated Power Contact Relay

PLC-…24UC/1/S… 101460_en_04 PHOENIX CONTACT 2 2O r d e r i n g D a t a PLC INTERFACE With Switch (Operation by Hand) Description Type Order No. Pcs./Pck. PLC INTERFACE with switch (operation by hand) and integrated power contact relay for "Manual", "Zero", and "Automatic" functions, with screw connection, for mounting on 3 PLC-RSC- 24UC/1/S/H 2982236 10 PLC INTERFACE with switch (operation by hand) and integrated power contact relay for "Manual", "Zero", and "Automatic" functions, with spring-cage connection, for mounting on 3 PLC-RSP- 24UC/1/S/H 2982249 10 PLC INTERFACE With Switch (Operation Using a Screwdriver) Description Type Order No. Pcs./Pck. PLC INTERFACE with switch (operation using a screwdriver) and integrated power contact relay for "Manual", "Zero", and "Automatic" functions, with screw connection, for mounting on 3 PLC-RSC- 24UC/1/S/L 2834876 10 PLC INTERFACE with switch (operation using a screwdriver) and integrated power contact relay for "Manual", "Zero", and "Automatic" functions, with spring-cage connection, for mounting on 3 PLC-RSP- 24UC/1/S/L 2834889 10 For the protection of input and output, inductive loads must be dampened with an effective protective circuit. Accessories Description Type Order No. Pcs./Pck. Insulating plate PLC-ATP BK 2966841 25 For additional accessories such as power terminal blocks and plug-in bridges, please refer to the INTERFACE catalog or www.phoenixcontact.com. The PLC-ATP BK insulating plate should be used in the following ca ses: always fit at the start and end of a PLC terminal strip for voltages potential bridging) and for safe isolation between adjacent modules.

PLC-…24UC/1/S… 101460_en_04 PHOENIX CONTACT 3

3 Technical Data

Input voltage UN 24 V AC/DC, 50 Hz ... 60 Hz Permissible range (with reference to UN) See "Operating Voltage Range" on page 4 Typical input current at UN 11 mA Input circuit Yellow LED, bridge rectifier Output Data Contact type Single co ntact, 1 N/O contact Contact material Silver tin oxide AgSnO Maximum switching voltage 250 V AC/DC 1 Minimum switching voltage 12 V AC/DC Limiting continuous current 6 A Maximum inrush current On request Minimum switching current 10 mA Maximum shutdown power

24 V DC

48 V DC

60 V DC

110 V DC

220 V DC

250 V AC

Ohmic load τ = 0 ms 140 W 20 W 18 W 23 W 40 W 1500 VA Minimum switching power 120 mW 1 The PLC-ATP BK insulating plate must be installed for voltages greater than 250 V (L1, L2, L3) between the same terminal points on adjacent modules General Data Rated insulation voltage 250 V AC Impulse voltage withstand level 6 kV Ambient temperature range Operation Storage/transport -25°C ... 60°C -20°C ... 85°C Nominal operating mode 100% operating factor Inflammability class according to UL 94 (housing) V0 Air and creepage distances between the circuits DIN EN 50178/VDE 0160 (safe isolation, reinforced insulation I/O) Standards/specifications IEC 60664, IEC 60664 A, DIN VDE 0110, DIN EN 50155/VDE 0115-200 (in relevant parts), IEC 60255/DIN VDE 0435 (in relevant parts) Pollution degree 2 Surge voltage category III Mounting position Any Mounting Can be aligned without spacing Conductor cross-section Solid, with screw connection Stranded, with screw connection Solid, with spring-cage connection Stranded, with spring-cage connection Stripping length Screw connection Spring-cage connection 10 mm 8 mm Dimensions (W x H x D) 6.2 mm x 94 mm x 80 mm Housing material Polybutylene tereph thalate PBT, non-reinforced, green

PLC-…24UC/1/S… 101460_en_04 4PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49 - 52 35 - 30 0 PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300 www.phoenixcontact.com

4 Application Example

6 Operating Voltage Range

Direct alignment in the block, all devices 100% operating factor, horizontal or vertical mounting. Curve A Maximum permissible continuous voltage Umax with limiting continuous current on the contact side Curve B Minimum permissible relay operate voltage Uop following pre-excitation Confirmation "Automatic" mode, floating 30 V AC/DC / 50 mA, maximum

2 V AC/DC / 1 mA, minimum

A O M CTL2 CTL1 M VCC 1(CTL) M 2(CTL) 0,7 25 30 35 40 45 50 55 60 6520 1,3 0,8 0,9 1,1 1,2 1,4U U N T[ °C]U A B U=2 4VD C/2 4VA CN