0960IOL381-001 BELDEN
Document overview
- Manufacturer or author: Provided By digicamel.com
- PDF pages: 4
Technical content
Part Number: 0960 IOL 381-001 LioN-P, IO-Link I/O Hub, 16DI (8x M12), Class A, Metal, 60 mm Product Description LioN-P, IO-Link I/O Hub, IO-Link, industrial metal housing, 60 mm, up to IP69K, 16 digital input channels, 8 x M12 A-coded I/O connection, 5-poles, 1x M12 A-coded IO-Link Class A connection, 5-poles Technical Drawing Technical Specifications Product Description Product Family: I/O Systems: Active - Standalone Product Sub Family: LioN-P Item Description: 0960 IOL 381-001 Part Number: 934992002 Device Type: I/O Hub
Protocol: IO-Link I/O Function: 16DI Bus Connection: M12, 5-poles, A-coded Power Connection (System Supply): M12, 5-poles, A-coded I/O Connection: M12, 5-poles, A-coded Replacement for: 934992001 I/O Type: Digital Input General Data Housing Material: Metal, Zinc Die-cast Housing Plating: Nickel, matt Housing Color: Grey Metallic Protection Degree / IP Rating: IP65, IP67, IP69K Potted: Yes Dimensions (W x H x D): 60 mm x 31 mm x 159 mm Weight: 390 g Ambient Temperature (Operation): -20 °C to 70 °C Ambient Temperature (Storage/Transport): -25 °C to 85 °C Permissible Humidity (Operation): 5 % ... 95 % (For UL applications max. 80 %) Permissible Humidity (Storage/Transport): 5 % ... 95 % (For UL applications max. 80 %) Air Pressure (Operation): 80 kPa … 106 kPa (up to 2000 m above sea level) Air Pressure (Storage/Transport): 80 kPa … 106 kPa (up to 2000 m above sea level) Flammabilty Class: UL 94 (IEC 61010) Protection Class: III, IEC 61140, EN 61140, VDE 0140-1 Pollution Degree: 3 acc. to EN 60664-1, VDE 0110-1 Vibration Resistance: 15 g / 5 -500 Hz Shock Resistance: 50 g / 11ms Mean Time To Failure (MTTF): 2111 years. acc. to Telcordia SR-332 (2011) 20°C Contact Base Material: M12, A-coded, CuSn, Gold-plated Contact Bearer Material: PA O-Ring Material: FKM Mounting: 2 hole screw mounting. Use standard M4 x 25 / 30 screws with toothed lock washer (as per DIN 125) and self-locking nuts. Fastening Torque (Fixing Screw): M4: 1 Nm Fastening Torque (Ground Connection (FE)): M4: 1 Nm Fastening Torque (Bus Connection): M12: 0.5 Nm Fastening Torque (Power Connection): M12: 0.5 Nm Fastening Torque (I/O Connection): M12: 0.5 Nm IO-Links Protocol: IO-Link Connection: M12, 5-poles, A-coded Number of Connections: 1 Specification: V1.1.2 IO-Link Class: Class A Transmission Rate / COM Mode: COM 3 (230.4 kbps) Cycle Time / Update Rate: min. 1 ms Parameter Storage: Supported Frame Type: Type_2_V Process Data Length: 4 Bytes Input Data, 4 Bytes Output Data Configuration: IODD, Process Data Power Supply Connection Module Supply Voltage: M12, 5-poles, A-coded Number of Connections: 1 Current Carrying Capacity of Connector: max. 4 A Module Supply Voltage (Nominal): 24 V DC (SELV/PELV) Module Supply Voltage (Range): 18 V DC to 30 V DC
Current Consumption (typ.): 80 mA (at 24 V DC) Reverse Polarity Protection: Yes Status Indicator: LED green Diagnostic Indicator: LED red Connection Sensor Supply Voltage: M12 Power, 5-poles, L-coded Current Carrying Capacity of Connector: max. 4 A Sensor Supply Voltage (Nominal): 24 V DC (SELV/PELV) Sensor Supply Voltage (Range): 18 V DC to 30 V DC Reverse Polarity Protection: Yes Status Indicator: LED green Diagnostic Indicator: LED red Digital Input Channels Number of Digital Input Channels: max. 16, fixed Connection: M12, 5-poles, A-coded Number of Ports: 8x, X1 to X8 Channel Type: Type 1 acc. to IEC 61131-2 Input Wiring: 2-, 3-wire Nominal Voltage: 24 V DC via US (module power supply) Nominal Current: typ. 5 mA Sensor Current Supply: max. 700 mA per module (Consider 1L+ limitation of connected IO-Link Master) Sensor Type: PNP Input Voltage Range "0" signal: -0,3V DC ... 5 V DC Input Voltage Range "1" signal: 15 V DC ... 30 V DC Input Filter Time: 0 to 3 ms, configurable Protective Circuit: Electronicaly: Overload protection, short-circuit protection Status Indicator: LED white or yellow per channel Electrical Isolation US (System Supply Voltage) / FE: 500 V DC Bus connection / FE: 500 V DC EMC Conformance EMC Directive: 2014/30/EU EN 61000-4-2 Electrostatic Discharge (ESD): Criterion B; 4 kV contact discharge, 8 kV air discharge EN 61000-4-3 Electromagnetic Field: Criterion A; Field intensity: 10 V/m EN 61000-4-4 Fast Transients (Burst): Criterion B, 2 kV EN 61000-4-5 Surge Voltage: Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); For I/O ports with cables ≤ 30m EN 61000-4-6 Conducted immunity: Criterion A; Test voltage 10 V EN 55022 Radio Interference Properties: Class A Safety & Environmental Compliance CE: Yes RoHS Compliant: Yes China RoHS-Compliant: Yes Approvals UL: cULus Listed, UL 61010-1 UL-File: E230848 CSA: Yes, via UL IO-Link: Yes Notes Protection Degree / IP Rating Note: *only if mounted and locked in combination with Hirschmann / Lumberg Automation connector. System Power Supply Connection Note: *do not connect / disconnect under voltage! Update and Revision: Revision Number: 0.26 Revision Date: 08-29-2019
© 2019 Belden, Inc All Rights Reserved. Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without notice, and the listing of such information and specifications does not ensure product availability. Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein. All sales of Belden products are subject to Belden's standard terms and conditions of sale. Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden's knowledge, information and belief at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the product.